Datasheet

2 EMC/EMI Products Schaffner Group Datasheets 2017
Filter selection table
Filter Rated current Leakage current* Inductance Capacitance Surge Energy Input/Output Weight
@ 40°C (25°C) @ 230 VAC/50 Hz L Cx Cy current absorption connections
[A] [μA] [mH] [nF] [nF] [A] [J] [g]
FN 332-1-05 1 (1.2) 340 10 15 2.2 -05 65
FN 332-3-05 3 (3.6) 340 2 15 2.2 -05 65
FN 332-6-05 6 (7.3) 340 0.8 15 2.2 -05 65
FN 332-10 A-05 10 (12) 340 0.5 15 2.2 -05 70
FN 332 Z-1-05 1 (1.2) 340 10 15 2.2 1200 26 -05 65
FN 332 Z-3-05 3 (3.6) 340 2 15 2.2 1200 26 -05 65
FN 332 Z-6-05 6 (7.3) 340 0.8 15 2.2 1200 26 -05 65
FN 332 Z-10-05 10 (12) 340 0.5 15 2.2 1200 26 -05 70
* Maximum leakage under normal operating conditions. Note: if the neutral line is interrupted, worst case leakage could reach twice this level.
Typical filter attenuation
Per CISPR 17; A=50 Ω/50 Ω sym; B=50 Ω/50 Ω asym; C=0.1 Ω/100 Ω sym; D=100 Ω/0.1 Ω sym
1 A types
3 and 6 A types
10 A types