Datasheet
Filter* Rated current Leakage current** Power loss Input/Output Weight
@ 50°C (40°C) @ 400VAC/50Hz @ 25°C/50Hz connections
[A] [mA] [W] [kg]
F
il
ter se
l
ect
i
on ta
bl
e
FN 256-8-46 8 (8.8) 3.4 2.7 -46 0.8
FN 256-16-46 16 (17.5) 3.4 6.0 -46 1.1
FN 256-25-47 25 (27) 3.4 11.6 -47 1.4
FN 256-36-47 36 (39) 3.4 14.8 -47 1.5
FN 256-64-52 64 (70) 3.4 18.4 -52 2.2
FN 256-80-.. 80 (88) 3.4 18.8 -28*** -34 4.5
FN 256-120-.. 120 (131) 5.0 25.1 -28*** -35 6.1
FN 256-160-.. 160 (175) 6.8 30.7 -28*** -40 8.0
FN 256-8-46-H 8 (8.8) 3.6 2.7 -46 0.8
FN 256-16-46-H 16 (17.5) 3.6 6.0 -46 1.1
FN 256-25-47-H 25 (27) 3.6 11.6 -47 1.4
FN 256-36-47-H 36 (39) 3.6 14.8 -47 1.5
FN 256-64-52-H 64 (70) 3.6 18.4 -52 2.2
FN 256-80-..-H 80 (88) 3.6 18.8 -28*** -34 4.5
FN 256-120-..-H 120 (131) 5.4 25.1 -28*** -35 6.1
FN 256-160-..-H 160 (175) 7.4 30.7 -28*** -40 8.0
* To compile a complete part number, please replace the -.. with the required I/O connection style.
** Maximum leakage under normal operating conditions, based on the assumption, that all 3 phases and the neutral conductor are connected to the supply and the consumer. In this case, the current
will mainly return through the neutral line, not as earth leakage.
*** Filters with -28 connections are rated for 40°C environmental temperature only.
Per CISPR 17; A = 50Ω/50Ω sym, B = 50Ω/50Ω asym, C = 0.1Ω/100Ω sym, D = 100Ω/0.1Ω sym
Typ
i
ca
l
fil
ter attenuat
i
on
8A types 16A types 25A types 36A types
64A types 80A types 120A types 160A types
> Components >
FN 256