Datasheet

> Components > FN 610
Filter* Rated current Leakage current** Inductance Capacitance Resistance Input/Output Weight
@ 40°C (25°C) @ 230VAC/50Hz L Cx Cy R connections -03/-06 -07
[A] [µA] [mH] [nF] [nF] [kΩ] [g] [g]
Filter selection table
FN 610-1-.. 1 (1.15) 190 3 33 2.2 -06 -07 55 65
FN 610-3-.. 3 (3.4) 190 2 33 2.2 -06 -07 60 70
FN 610-6-.. 6 (6.9) 190 0.75 33 2.2 -06 -07 60 70
FN 610-10-.. 10 (11.5) 190 0.45 33 2.2 -06 -07 85 95
FN 610-20-06 20 (23) 190 0.48 33 2.2 -06 220
FN 610-30-03 30 (34) 190 0.61 33 2.2 -03 630
FN 610A-1-.. 1 (1.15) 40 3 33 0.47 1000 -06 -07 55 65
FN 610A-3-.. 3 (3.4) 40 2 33 0.47 1000 -06 -07 60 70
FN 610A-6-.. 6 (6.9) 40 0.75 33 0.47 1000 -06 -07 60 70
FN 610A-10-.. 10 (11.5) 40 0.45 33 0.47 1000 -06 -07 85 95
FN 610B-1-.. 1 (1.15) 2 3 33 1000 -06 -07 55 65
FN 610B-3-.. 3 (3.4) 2 2 33 1000 -06 -07 60 70
FN 610B-6-.. 6 (6.9) 2 0.75 33 1000 -06 -07 60 70
FN 610B-10-.. 10 (11.5) 2 0.45 33 1000 -06 -07 85 95
FN 610B-20-06 20 (23) 2 0.48 33 1000 -06 220
* To compile a complete part number, please replace the -.. with the required I/O connection style (e.g. FN 610-1-06, FN 610B-30-03).
** Maximum leakage under normal operating conditions. Note: if the neutral line is interrupted, worst case leakage could reach twice this level.
Per CISPR 17; A = 50Ω/50Ω sym; B = 50Ω/50Ω asym; C = 0.1Ω/100Ω sym; D = 100Ω/0.1Ω sym
Typical filter attenuation
1 to 6A types 10 and 20A types
30A types