Datasheet

Three-Phase Filters > FN 258
Filter selection table
Filter*
Rated
current Typical drive
Leakage
current*** Power loss Input Output Weight
@ 50°C (40°C)
power
rating** @ 440VAC/50Hz
@
25°C/50Hz connections connections
[A] [kW] [mA] [W] [kg]
FN 258-7-.. 7 (7.7) 4 16.5 9 -29 -07 -29 1.0
FN 258-16-.. 16 (17.5) 7.5 18.3 20 -29 -07 -29 1.4
FN 258-30-.. 30 (33) 15 24.2 21 -33 -07 -33 1.7
FN 258-42-.. 42 (46) 22 25.8 30 -33 -07 -33 2.5
FN 258-55-.. 55 (60) 30 25.8 30 -34 -07 -34 2.9
FN 258-75-34 75 (82) 37 25.8 24 -34 -34 3.9
FN 258-100-35 100 (110) 55 25.8 51 -35 -35 5.5
FN 258-130-35 130 (143) 75 30.0 50 -35 -35 6.9
FN 258-180-.. 180 (197) 90 30.0 73 -40 -07 -40 11.0
FN 258-250-.. 250 (275) 132 30.0 79 -40 -07 -40 12.0
FN 258HV-7-29 7 (7.7) 5.5 13.0 9 -29 -29 1.0
FN 258HV-16-29 16 (17.5) 11 19.0 20 -29 -29 1.5
FN 258HV-30-33 30 (33) 22 19.0 21 -33 -33 1.8
FN 258HV-42-33 42 (46) 30 21.6 30 -33 -33 2.6
FN 258HV-55-34 55 (60) 45 21.6 30 -34 -34 3.0
FN 258HV-75-34 75 (82) 55 21.6 24 -34 -34 4.3
FN 258HV-100-35 100 (110) 90 21.6 51 -35 -35 5.6
FN 258HV-130-35 130 (143) 110 25.0 50 -35 -35 7.1
FN 258HVIT-7-29 7 (7.7) 5.5 13.0 9 -29 -29 1.0
FN 258HVIT-16-29 16 (17.5) 11 19.0 20 -29 -29 1.5
FN 258HVIT-30-33 30 (33) 22 19.0 21 -33 -33 1.8
FN 258HVIT-42-33 42 (46) 30 21.6 30 -33 -33 2.6
FN 258HVIT-55-34 55 (60) 45 21.6 30 -34 -34 3.0
FN 258HVIT-75-34 75 (82) 55 21.6 24 -34 -34 4.3
FN 258HVIT-100-
35
100 (110) 90 21.6 51 -35 -35 5.6
FN 258HVIT-130-
35
130 (143) 110 25.0 50 -35 -35 7.1
FN 258L-7-.. 7 (7.7) 4 0.8 9 -29 -07 -29 1.0
FN 258L-16-.. 16 (17.5) 7.5 0.8 20 -29 -07 -29 1.4
FN 258L-30-.. 30 (33) 15 0.8 21 -33 -07 -33 1.7
FN 258L-42-.. 42 (46) 22 0.7 30 -33 -07 -33 2.5
FN 258L-55-.. 55 (60) 30 0.7 30 -34 -07 -34 2.9
FN 258L-75-34 75 (82) 37 0.7 24 -34 -34 3.9
FN 258L-100-35 100 (110) 55 0.7 51 -35 -35 5.5
FN 258L-130-35 130 (143) 75 0.7 50 -35 -35 6.9
FN 258L-180-.. 180 (197) 90 0.7 73 -40 -07 -40 11.0
FN 258L-250-07 250 (275) 132 0.7 79 -40 -07 12.0
FN 258P-7-.. 7 (7.7) 4 3.3 9 -29 -07 -29 1.0
FN 258P-16-.. 16 (17.5) 7.5 3.3 20 -29 -07 -29 1.4
FN 258P-30-.. 30 (33) 15 3.3 21 -33 -07 -33 1.7
FN 258P-42-.. 42 (46) 22 3.5 30 -33 -07 -33 2.5
FN 258P-55-.. 55 (60) 30 3.5 30 -34 -07 -34 2.9
FN 258P-75-34 75 (82) 37 3.5 24 -34 -34 3.9
FN 258P-100-35 100 (110) 55 3.5 51 -35 -35 5.5
FN 258P-130-35 130 (143) 75 3.5 50 -35 -35 6.9
FN 258P-180-.. 180 (197) 90 3.5 73 -40 -07 -40 11.0
FN 258P-250-07 250 (275) 132 3.6 79 -40 -07 12.0
* To compile a complete part number, please replace the -.. with the required output connection style.
** Calc ulated at rated c urrent, 440VAC (FN 258) / 690VAC (FN 258HV) and cos phi = 0.8. The exact value depends upon the effic iency of the drive, the motor and the entire
application.
*** Maximum leakage under normal operating conditions (FN 258 at 440V, FN 258HV at 690V). Note: if two phases are interrupted, worst case leakage c ould reach 5.7 times
higher levels.
Typical filter attenuation
Per CISPR 17; A = 50Ω/50Ω sym; B = 50Ω/50Ω asym; C = 0.1Ω/100Ω sym; D = 100Ω/0.1Ω sym
7 to 30A types 42 to 100A types 130A types 180 and 250A types
Note: typical attenuation performanc e of FN 258 standard filters. The behavior of FN 258HV, FN 258HVIT, FN 258P and FN 258L may be slightly different.