Datasheet
Single-Phase Filters > FN 2080
Filter selection table
Filter* Rated current Leakage current** Inductance Capacitance Resistance Input/Output Weight
@ 40°C (25°C) @ 230VAC/50Hz L L1 Cx Cy R connections
[A] [mA] [mH] [μH] [μF] [nF] [kΩ]
[g]
FN 2080-1-.. 1 (1.2) 0.734 22 490 0.33 4.7 1000 -06 -07 200
FN 2080-3-.. 3 (3.5) 0.734 9.8 160 0.47 4.7 470 -06 -07 270
FN 2080-6-.. 6 (6.9) 0.734 7.8 110 1 4.7 220 -06 -07 470
FN 2080-10-.. 10 (11.5) 0.734 4.5 60 1 4.7 220 -06 -07 750
FN 2080-12-.. 12 (13.8) 0.734 3.25 50 1 4.7 220 -06 -07 750
FN 2080-16-.. 16 (18.4) 0.734 2.8 43 1 4.7 220 -06 -07 -08 1020
FN 2080A-1-.. 1 (1.2) 0.074 22 490 0.33 0.47 1000 -06 -07 200
FN 2080A-3-.. 3 (3.5) 0.074 9.8 160 0.47 0.47 470 -06 -07 270
FN 2080A-6-.. 6 (6.9) 0.074 7.8 110 1 0.47 220 -06 -07 470
FN 2080A-10-.. 10 (11.5) 0.074 4.5 60 1 0.47 220 -06 -07 750
FN 2080A-12-.. 12 (13.8) 0.074 3.25 50 1 0.47 220 -06 -07 750
FN 2080A-16-.. 16 (18.4) 0.074 2.8 43 1 0.47 220 -06 -07 -08 1020
FN 2080B-1-.. 1 (1.2) 0.002 22 490 0.33 1000 -06 -07 200
FN 2080B-3-.. 3 (3.5) 0.002 9.8 160 0.47 470 -06 -07 270
FN 2080B-6-.. 6 (6.9) 0.002 7.8 110 1 220 -06 -07 470
FN 2080B-10-.. 10 (11.5) 0.002 4.5 60 1 220 -06 -07 750
FN 2080B-12-.. 12 (13.8) 0.002 3.25 50 1 220 -06 -07 750
FN 2080B-16-.. 16 (18.4) 0.002 2.8 43 1 220 -06 -07 -08 1020
* To c ompile a complete part number, please replac e the -.. with the required I/O c onnec tion style (e.g. FN 2080-16-08, FN 2080B-10-06).
** Maximum leakage under normal operating conditions. Note: if the neutral line is interrupted, worst case leakage could reach twice this level.
Typical filter attenuation
Per CISPR 17; A = 50Ω/50Ω sym; B = 50Ω/50Ω asym; C = 0.1Ω/100Ω sym; D = 100Ω/0.1Ω sym
1 to 6A types 10 and 12A types 16A types