Datasheet

Features and benefits
FN 2080 two-stage filters are designed
for easy and fast chassis mounting.
FN 2080 filters are also available as B
versions without Y-capacitors for
medical applications as well as A
version with low capacitance for safety
critical applications with necessity for
low leakage currents.
All filters provide a high conducted
attenuation performance, based on
chokes with high saturation resistance
and excellent thermal behavior.
FN 2080 two-stage filters are designed
with good low frequency attenuation.
FN 2080 filters are also available as
single- stage filters.
Various terminal options allow you to
select the desired connection style.
Typical applications
Electrical and electronic equipment
Consumer goods
Household equipment
Building automation
Industrial applications
Machinery
Medical equipment
Electronic data processing equipment
Office automation and datacom
equipment
Various noisy applications requiering
good filter performance
Single-Phase Filters
FN 2080
Multi-stage High Performance EMI
Filter
Rated currents from 1 to 16A
High differential and common-
mode attenuation
Good low frequency attenuation
Optional medical versions (B type)
Optional safety versions (A type)
Approvals
Technical specifications
Maximum continuous operating voltage: 250VAC, 50/60Hz
Operating frequency: dc to 400Hz
Rated currents: 1 to 16 A @ 40°C max.
High potential test voltage: P –> PE 2000VAC for 2 sec
P –> PE 2500VAC for 2 sec (B types)
P –> N 1100VDC for 2 sec
Temperature range (operation and
storage):
-25°C to +100°C (25/100/21)
Flammability corresponding to: UL 94V-2 or better
Design corresponding to: UL 1283, CSA 22.2 No. 8 1986, IEC/EN
60939
MTBF @ 40°C/230V (Mil-HB-217F): 1,650,000 hours
1,700,000 hours (B types)
Typical electrical schematic

Summary of content (5 pages)