Inverters
1 or 3-Phase Output from 200VA to 45kVA, switchmode
DC / AC Inverters, AC / AC Frequency Converters & Static Switches
Sine Wave
Continuous short circuit protection
Thermal shutdown with auto-restart for
1-phase inverters >1.2kVA
3-phase inverters >3.6kVA
Suitable for complex load
Surge power capability
Industrial grade components
Compact and robust design
3-phase output: Unsymmetrical load permissible,
modular system with interchangeable inverters
Input voltage: 10-800V DC or
115/ 230V AC, single phase, 47-400Hz or
200/ 400/ 480V AC, three phase, 47-400Hz
Output voltage: 115/ 230 V AC, single phase
or 200/ 400/ 480V AC, three phases
Output frequency: 50/ 60/ 400/ 800Hz
(crystal stabilized) or programmable within
40-400Hz or 400-800Hz
Output power: 200VA - 45kVA
Features
Specifications
AC
or
DC
AC
Input
Voltage range unit switches off at under- and
overvoltage
No-load input power 10 – 30 W
Inrush current for AC input and DC input >160V:
limited by thermistor
Hold-up time AC input: 10 ms typical
Series CI: 20ms typical
Immunity acc. to EN 61000-6-2
General
Efficiency 80 – 92 %
Operating temperature – 20 to + 75°C
optional: -40 to +75°C
Load derating 2.5%/°C above + 55°C
Storage temperature -40 to + 85°C
Cooling
(details see page 131)
= natural convection
= incl. temperature controlled fans
Humidity up to 95 % RH, non-condensing
Safety / Construction acc. to EN 60950-1 / EN 50178
Protection category IP20 acc. to EN 60529,
NEMA or others upon request
EMI acc. to EN 61000-6-4,
class A, optionally class B
MTBF @40°C acc. to
MIL -HDBK-217E (notice1)
series IT:
120.000h
series CI:
70.000h
series IV:
50.000h
Output
Output voltages
115V AC 230V AC
3x200VAC 3x400VAC 3x480VAC
or any other
Output power from 200 VA up to 45k VA
Line regulation (±10%) 0.1 % for series CI,
2 % for series IT and IV
3 % for series IT and IV @ 400Hz
Load regulation (10-90%) 1 % typical, 3 % max.
(400 Hz: 3 % typical, 5 % max.)
Turn-on rise time soft-start, 100ms typical
Waveform sine wave or any wave shape pro-
grammable by external signal
Frequency 40 – 800 Hz: adjustable or
programmable or any fixed
frequency (crystal stabilized)
Distortion 3 % typical, 5 % @ 400 Hz,
7 % @ 40 – 400 Hz, 800Hz
Overload protection
(steady state)
current limited to approx. 1.05 x
nominal current
Surge power 2 x nominal power for 1 s
Short circuit protection electronically limited to 3 x no-
minal current, unit switches off
after 1 s
Crest factor approx. 3
Power factor cos 0.7 inductive / capacitive
Options
Input
Inrush current limiting for DC input
Reverse polarity protection for DC input
Autoranging for 115 / 230 VAC input
Special circuit for 16.6Hz AC input
Output
Remote on / off (inhibit)
Static Switch (details see page 97)
Parallel operation for redundancy or increased power:
series IT5xxx
Signals
via relay contacts
Power ok (input)
AC ok (output)
Monitoring
of input / output voltage, current or frequency via
analog signal
interface card RS232 or CAN Bus (external)
Programming
of output voltage, current or frequency via
potentiometer
analog signal
interface card RS232 or CAN Bus (external)
Mechanics / environment:
19” sub-rack for eurocassette, refer to page 121
Wall mount
Increased mechanical strength
Tropical protection
Extended temperature range to –40 °C
Temperature controlled fans for 19” units