User manual
12
10987654321
ON
Buzzer
Miniature switch
L
L
N
N
PE
PE
S
G
Ö
Relay plug-in card
connection
L
N
PE
Sensor 1
Float switch
Sensor 2
Float switch
Sensor 3
Float switch
Sensor 4
Float switch
Magnetic cut-off valve
(closed in non-operating condition)
Relay
8A/230V
Option:
9V battery
Operating voltage
230 V AC
50-60 Hz
6.4 Settings of the miniature switch
At the delivered condition of the product, the miniature switch
is set, as depicted in the picture on the right.
Switch1: ON = Battery monitoring is shut off
Switch2: ON = Storage function for Sensor 1 is switched on
Switch3: ON = Storage function for Sensor 2 is switched on
Switch4: ON = Storage function for Sensor 3 is switched on
Switch5: ON = Storage function for Sensor 4 is switched on
Switch6: ON = Buzzer is for all channels active
Switch7: ON = Buzzer for Channel 1 is active
Switch8: ON = Buzzer for Channel 2 is active
Switch9: ON = Buzzer for Channel 3 is active
Switch10: ON = Buzzer for Channel 4 is active
6.5 Relay connection conguration
When connecting additional devices to the potential-free relay, please note that the switching
capacity may not be exceeded.
Relay status in monitoring mode: ►
The relay is „energized“ (make contact closed/break contact open)
Relay status in alarm mode: ►
The relay „decreases“ (make contact open/ break contact closed)
Wiring example: Magnetic cut-off valve
ENGLISH