For your own safety, we recommend that you carry out this test constantly!
5. OPERATION / FUNCTION DISPLAY
5.1 Operation of the water detector SHT 5001
LED POWER is green: The SHT 5001 water detector is connected to the mains supply and
mains voltage.
LED SENSORS lights up: As soon as the sensor recognizes a rising water level, its LED will
blink red. The alarm is set off and the potential-free relay 1 and 2 switches.
The acoustic alarm (Relay 2) is deactivated by pressing the button <RESET> once.
Alarm message with storage function: The alarm stays and the relay 1 is switched on,
until the message is removed by pushing the <RESET> button.
Alarm message without storage function: The alarm remains and the relay 1 is switched
on, until the sensor no longer reports water.
6. TECHNICAL SPECIFICATIONS
Operating voltage: 230 V AC (+/-10%) / 50-60 Hz
Power consumption: approx. 3 W
Sensor connection: 5 (parallel)
Cable length of sensor: up to 50 m (max.)
Relay contact: 2 potential-free two-way contacts
Switching capacity relay: max. 5 A / 230 V
Operating temperature: 0 °C / +40 °C
Protection type: IP 20
Dimensions (HxWxD): 57x72x90 mm
5.2 Function test
5.2.1 Function test SHT 5001
By pushing the <TEST> button, the alarm LEDs of the sensor m ust blink red, and the relay
must switch. The pushing of the <RESET> button ends the function test.
5.2.2 Funktionstest SHT 5006
Touch both sensor contacts with a waterlogged cloth or an electric conductive metal and the
alarm is set off immediately.