In a heat storage the thermal
energy or charging power is
obviously di splayed incorrectl y. 1
kWh = 1° C increase in temperature
of 1 000 liters of water shows as a
rough est imat e other values
The volume of the buffer is set
incorrectly. The buffer temperature
probe wil l be delivered with a
default setting for the 1000 liters of
storage
Determine the volume of th e
installed heat-storage
Select at the controller under
Settings ->Buffer, your´s and enter
under " volume " the size of the
installed buffer
An S0 met er adapte r indicates
obviously in correct values. The
counts in th e display on the meter
and jn the controller increases in
different rates
The weighting of the p ulses is set
incorrectly. The adapt er will be
delivered w it h a default setting of
1000 pulse s / kWh for Eltako meter
Determine the pulses / kWh out of
your met ers data sheet
Select at the controller under
Settings ->Meter, your´s and enter
under " weig ht " the value of your
meter
Problem Cause Rectification
Troubleshooting