User Manual

7 Specifications
Type
OTC95
STP1309
Length
[mm]
775
925
Width
[mm]
850
1509
Height
[mm]
920
920
Display area
[m²]
0.38
1.0
Useful capacity
[l]
125
328
Weight
[kg]
100
185
Energy consumption
[kWh/24h]
5.0
13.5
Power consumption
(refrigeration)
[w]
275
600
Power consumption
(defrosting)
275
700
Fusing, (slow)
[A]
10
Operating voltage
[V/Hz]
230/50
No. of defrosts
[min./24h]
6x20
6x20
Storage temperature
[°C]
+2...+8
+2...+8
Refrigerant
R290
[kg]
0.07
0.07
Max. loading capacity of
shelves
[kg]
72
178
Noise level
dB(A)
70
8 Troubleshooting
Any trouble occurring might be due to a minor problem that you can correct
yourself following the instructions below. Do not try any further action if the
pointers given cannot solve the problem!
Repairs on the cabinet must be made only by qualified specialists.
Incompetent repair work can cause serious personal danger,
contract your Service Organization for any repairs needed.
Trouble
Possible cause
Corrective measures
The cabinet does
not work (no
audible running
noise or only fan
noise audible.)
Automatic evaporator
defrosting active or
electronic controller
switched off.
Power plug not
connected or remote
control switch (where
provided) switched off.
Fuse blown, power plug
or socket defective.
Condenser fins fouled.
Nor required, as cooling will
switch on automatically
again.
Insert power plug
properly in or switch remote
control switch on.
Contact your electrician or
the Service Organization.
Perform maintenance.
Cabinet stops
running after
short operation.
Condenser fins fouled.
Perform maintenance.
Storage
temperature is
too high.
Automatic evaporator
defrosting active.
Ambient temperature
too high or electronic
controller misadjusted.
The warm air outlet or
another cabinet is
directly taken in as air
Not required, temporary
minor temperature rise
during defrosting is normal.
Avoid extreme operating
environment, readjust
storage temperature.
Observe single-row line-
up and group installation.