Specifications

4.3.1 Mantel Clearances
4.3.2 Hearth and floor protection requirements:
When the bottom of the fireplace is installed less than 3 1/2” (88 mm) to the floor, the floor
requires thermal protection of 3/4 inch (19 mm) thick mineral fiber millboard with a value of
k=1.12 BTU/IN FT
2
HR
o
F. The protection must extend forward 24 inches (610 mm) and 8 inches
(203 mm) to each side of the door opening.
When the bottom of the fireplace is installed less than 7” (177 mm) but more than 3 1/2” (89
mm) from the floor, the floor thermal protection only needs to be 1/2 inch (12.5 mm) thick
k=1.68 BTU/IN FT
2
HR
o
F. The protection must extend forward 24 inches (610 mm) and 8 inches
(203 mm) to each side of the door opening.
When the bottom of the fireplace is installed 7” (178 mm) or greater from the floor, the floor
only needs to be covered with non-combustible material, minimum 3/8 inch (10 mm) thick
extending forward 16 inches (455 mm) and 8 inches (203 mm) to each side of the door opening
in the U.S. (In Canada: 18 inches / 407 mm).
To substitute alternate insulation material, you need to know the “k” factor for that material, and
calculate the required thickness for the alternate material; use the following formula:
Example: “K” value of brick = 5
4.5 inches of brick is required to meet the requirement.
”K”/ 0.84 *(specified thickness)
5/084*0.75 = 4.464 inch
3 inches of brick is required to meet the requirement.
5/084*0.50 = 2.976 inch
9