SBS-6000 Battery Analyzer User’s Manual V2.0 Storage Battery Systems, Inc.
Exception Clause This information and all other documents in printed or electronic form are only provided for reference. Although efforts have already been made to confirm the integrality and accuracy of this information, the Storage Battery Systems, Inc.
unless otherwise expressly provided in this software license agreement. © All rights reserved 2005 – 2012. Storage Battery Systems, Inc. DADI Science & Technology District, Liuzhou New & High-tech industrial Development Zone, Liuzhou, Guangxi, China All rights reserved. Printed in China. Trademark Dadi is the registered trademark of the Storage Battery Systems, Inc. In China and other countries. Pentium and Intel are the registered trademarks of the Intel Corporation in U.S.A. and other countries.
Warning Battery charging Charging the battery must use the charger from the manufacturer. You can’t use any unauthorized charger, lest cause tester damage or accident. Battery replacement Please use the manufacturer configured Li batteries. You can’t operate the tester in inflammable or explosive environment. Do not use the tester in environment with inflammable or explosive liquid or steam. In this environment, it will be dangerous with any electrical instruments.
Catalogue Chapter 1 General ................................................................................ 7 Chapter 2 Inspection ............................................................................ 7 2.1 Unpack the Instrument ........................................................... 7 2.2 Accessory and Option ............................................................. 8 2.3 Power Supply ..........................................................................
5.4.4 Compare Functions ..................................................... 42 5.4.5 Re-test Functions......................................................... 44 5.4.6 Gear Setup................................................................... 45 Data save function....................................................... 47 5.4.7 5.5 System setting ...................................................................... 48 5.5.1 Network setting ...........................................................
Chapter 1 General SBS-6000 Storage Battery Impendence Analyzer is the most powerful and well performed storage battery test equipment. It is a multipurpose impendence instrument and micro ohm meter with the most complete functions and supports the domestic and foreign standards. The equipment can test all kinds of battery like 2V, 4V, 6V, 8V, 12V, 24V, 48V, it can also test resistance of conductor and metal connector, the test precision reaches 1μΩ.
2.2 Accessory and Option Accessories to the SBS-6000, please refer to the packing list. If received articles are not the same with what is specified in the packing list, please inform us immediately so as not to make any influence on using. 2.3 Power Supply The SBS-6000 supports two power supply modes, DC and battery, with a built-in large capacity rechargeable lithium battery for 8-hour long consecutive operation after being fully charged.
Chapter 3 General operation and use guide 3.1 Operation standard Test interface Please connect the wire to test interface, and then connect the wire to tested line. Please don’t touch the bare metal part of test clips, lest there is high voltage on wire. RS232 port Don’t connect with RS232 port with electricity, also don’t short-circuit the interface by metal, otherwise easily damage the internal circuit. Display The new tester has a protective mask on LCD, please rip it before use.
Faults If the internal emit strange voice, smell or smoke, please immediately shut off the tester and power supply, and contact us. 3.2 10 Use notes When you use the tester for the first time, please fully charge the battery. If there appear abnormal pages or crashed, please shutdown the tester and then restart again. Please don’t let the tester in direct sunlight or close to heat place, which maybe cause adverse affect to inside circuit or shell.
Chapter 4 Menu 4.
4.2 Instrument’s Buttons F1 F2 F3 F4 Function Key Esc Enter Return Key Reset Key Confirm Key Tab 1@ 2 ABC 3 DEF 4 GHI 5 JKL 6 MNO Help 7 PQRS 8TUV 9WXYZ 0 A Direction Key Power Key Rst Reset 0 Number Key Rst Pwr Keyboard introduction It includes power key, reset key, return key, function key, arrow key, OK key and number key. The key functions are as follows: Power key: power on/off.
allowed error range: ±10%, output 8.4V. TEST CABLE test interface TEST CABLE test interface is the special interface for battery resistance test line. Ethernet interface This interface is standard RJ45 interface, use Ethernet crossed line. RESERVE interface Standby interface. RS232 interface Professional external RS232 parallel serial Line for the connection between instruments & PC. 4.
Chapter 5 Operation Instructions 5.1 Power on/off Power on Instrument: Press the power on/off button, and it will display LOGO icon and then enter into the below operation display: 2011-05-10 09:01:23 STRING TEST 测试设置 Power off instrument: A long press the power on/off button, about 5 seconds. 5.2 Instruction of tester’s LCD display It will show the main display when power on the tester. It includes: Battery indicator, Date and time, status bar and function icon.
Function Name Date And Time Capacity Display 2011-05-10 09:01:23 STRING TEST Function Ico 测试设置 It includes series function icon, and each icon indicates a function. Please select the related icon and click the ENTER button into a function. 5.3 Test Setting Functions description Please process the parameter setting before test. It include: String setting, Cell setting, Conn setting, Data Storage, Alarm Threshold setting, test type setting, Battery sampling and zero resistance setting.
Navigation Date \Time And Power 2011-05-10 09:01:23 TEST SETTING 1. String Mode: Settings functions function keys 5.3.1 2. Cell Mode: 3. Conn Mode: 4. Save Mode: 5. Set Warning: 6. Input Comp: 7. Set Test Type: 8. Sample Test: Esc Station:01 String:01 V Type:2 V-0500AH V Warning:02.00V REF: 000.483mΩ Settings content Enter String setting Functions description Set the String setting parameters like: Station No., Group No., Battery type, Low pressure alarm value and Group reference value.
and Station No. to build a new string and then set the related string parameters. There have shortcut keys of some parameters, for the one do not have shortcut keys, User’s can input NO.. Detail as follow: 2011-05-10 09:01:23 TEST SETTING 1. String Mode: 2. Cell Mode: 3. Conn Mode: 4. Save Mode: 5. Set Warning: 6. Set Test Type: 7. Sample Test: 8. Zero Setting: Station:01 String:01 V Type:2 V V Warning:02.10V REF: 000.483mΩ Esc Enter Support voltage type: 2V, 4V, 6V, 8V, 12V, 24V.
Comparison threshold value setting include: Manual Input directly or Select threshold value. Select threshold means choose the Built-in set value. The Build-in values can get directly from the sampling battery testing or the configured download software. Details please take the chapter “Sampling Battery” for reference. Display of Manual Input value as follow: 2011-05-10 09:01:23 TEST SETTING 1. String Mode: 2. Cell Mode: 3. Conn Mode: 4. Save Mode: 5. Set Warning: 6. Set Test Type: 7. Sample Test: 8.
Select the saved threshold value, click function key <-1><+1> to change the serial No. and choose value. It will show in Gray color if it can not configure. The display of select threshold value as follow: 2011-05-10 09:01:23 TEST SETTING 1. String Mode: 2. Cell Mode: 3. Conn Mode: 4. Save Mode: 5. Set Warning: 6. Set Test Type: 7. Sample Test: 8. Zero Setting: Esc 5.3.2 Station:01 String:01 V Type:2 V- 0500AH V Warning:02.10V REF: 001 2V:0500AH:0.
11-05-10 09:01:23 TEST SETTING 1. String Mode: 2. Cell Mode: 3. Conn Mode: 4. Save Mode: 5. Set Warning: 6. Set Test Type: 7. Sample Test: 8. Zero Setting: 2V 4V V Type:2 V- 0500AH V Warning:02.10V REF: 000.483mΩ 6V More Support voltage type: 2V, 4V, 6V, 8V, 12V, 24V. Click related shortcut keys for setting, like below: 2011-05-10 09:01:23 TEST SETTING 1. String Mode: 2. Cell Mode: 3. Conn Mode: 4. Save Mode: 5. Set Warning: 6. Set Test Type: 7. Sample Test: 8.
testing or the configured download software. Details please take the chapter “Sampling Battery” for reference. When the test type is resistance, the display of manual input threshold value of Cell setting as follow: 2011-05-10 09:01:23 TEST SETTING 1. String Mode: 2. Cell Mode: 3. Conn Mode: 4. Save Mode: 5. Set Warning: 6. Set Test Type: 7. Sample Test: 8. Zero Setting: Srlect Esc V Type:2 V- 0500AH V Warning:02.10V REF: 000.
Select the saved threshold value, press function key <-1><+1> to change the serial No. and choose value. It will show in Gray color if it can not configure. The display of select threshold value as follow: 2011-05-10 09:01:23 TEST SETTING 1. String Mode: 2. Cell Mode: 3. Conn Mode: 4. Save Mode: 5. Set Warning: 6. Set Test Type: 7. Sample Test: 8. Zero Setting: -1 5.3.3 Srlect V Type:2 V- 0500AH V Warning:02.10V REF: 001 2V:0500AH:0.
the Pole No. of each Cell battery, the serial No. of Connector is based on the No. of Pole. During resistance testing, the display of Connector setting as follow: 2011-05-10 09:01:23 TEST SETTING 1. String Mode: 2. Cell Mode: 3. Conn Mode: 4. Save Mode: 5. Set Warning: 6. Set Test Type: 7. Sample Test: 8. Zero Setting: Esc Station: 01 String:01 REF:000.050mΩ Post Per JAR:2 Enter During Conductance testing type, manual input threshold value display as follow: 2011-05-10 09:01:23 TEST SETTING 1.
5.3.4 Data storage setting Functions description Set the related parameters of String testing, Cell testing, Conn testing and data storage saving. There are two saving types of data storage: Manual & Auto. When you set Manual saving, you should click the related saving keys to store the data. If you set Auto saving, the instruments will auto saving the date once the testing results coming stable. How to use Select the data storage saving type and click OK key to enter into.
5.3.5 Alarm Threshold Setting Functions description Set the alarm & replacement value of the battery resistance. If test battery’s resistance, the setting value should be the multiple of the reference value. If test conductance, the setting value should be the percentage of the reference value. How to use Select the alarm threshold setting and enter into the setting display, if it is resistance testing, the display as follow: 2011-05-10 09:01:23 TEST SETTING 1. String Mode: 2. Cell Mode: 3. Conn Mode: 4.
During Conductance testing type, manual input threshold value display as follow: 2011-05-10 09:01:23 TEST SETTING 1. String Mode: 2. Cell Mode: 3. Conn Mode: 4. Save Mode: 5. Set Warning: 6. Set Test Type: 7. Sample Test: 8. Zero Setting: Esc +1% Warning:65% REF Fail:50% REF -1% Enter Click up & down keys to select the items you want to set. Click <+1%><-1%> function key to set the alarm and replacement threshold and then save.
already confirmed before you set up the testing string. If you want to amend the test type of String & Conn testing, you should re-build testing string. How to use Select the test type setting and enter into the display show as follow: 2011-05-10 09:01:23 TEST SETTING 1. String Mode: 2. Cell Mode: 3. Conn Mode: 4. Save Mode: 5. Set Warning: 6. Set Test Type: 7. Sample Test: 8. Zero Setting: Esc R Set Test Type: Resistance G Enter Click function key to set the testing type. 5.3.
2011-05-10 09:01:23 TEST SETTING 1. String Mode: 2. Cell Mode: 3. Conn Mode: 4. Save Mode: 6. Set Test Type: 6. Set Test Type: 6. Set Test Type: 8. Zero Setting: Esc NO. 001 002 003 004 005 006 Set Comp Sample Test: REF AH V 6.500 mΩ 12V 45 2V 500 0.380 mΩ 2V 1000 0.200 mΩ 2V 100 1.000 mΩ 2V 2000 0.100 mΩ 2V 200 0.
new battery for sampling while the sample number no less than 10 items is highly recommended . When setup finished, click key enter into the sampling interface as below: 2011-05-10 09:01:23 Sample Test Sample:30 REF Number:001 R 0 . 421 (mΩ) Sample NO.1 Range:4 mΩ Esc Save Save test results once data became stable until all samples are tested, at this time, the test interface will display Min and Average value.
2011-05-10 09:01:23 Sample Test Sample:30 REF Number:001 R 0 . 421 (mΩ) Sample NO.30 Min:0.412(mΩ) Average:0.432(mΩ) Range:4 mΩ Esc 5.3.8 Save Ave Save Min Impedance Zero Adjustment Function Functions description This impedance zero functions is used to calibrate the tester by adjusting impedance 0 range value, in order to make the test results are much more reliable.
When using probes testing cable for zero setting, four probes have to insert to related four holes, below is probes and setting board connection diagram.
below interface. 2011-05-10 09:01:23 TEST SETTING 1. String Mode: 2. Cell Mode: 3. Conn Mode: 4. Save Mode: 5. Set Warning: 6. Set Test Type: 7. Sample Test: 8. Zero Setting: Func On Zero Adjust Connect zero board 0.000(mΩ) Range:4mΩ Function OFF Func Off Range Esc When tester is in impedance zero setting interfaces, it will alert “Please connect to zero setting board” you have to connect testing clip or probes to setting board, tester will be in auto zero setting.
When tester in zero setting it will auto shut off zero setting function, when setting finished, tester will display “Complete” and automatic power on zero setting function. You also can use functional keys to power on or functional keys to power off zero setting as below interface. 2011-05-10 09:01:23 TEST SETTING 1. String Mode: 2. Cell Mode: 3. Conn Mode: 4. Save Mode: 5. Set Warning: 6. Set Test Type: 7. Sample Test: 8. Zero Setting: Func On Zero Adjust Complete 0.
5.4 Test Functions Functions description Test functions contain three methods: string testing, Cell testing and Conn testing. Each function adapts to different type of testing. String testing is used to the whole battery testing, and that can manage the series number of battery test results, and analysis the data, find out the inequality Cell battery in fast way. View data and check out battery Chart so that search invalid battery rapidly.
“Test clip” connect to battery terminal sketch When test type is resistance test, the interface is as below: Function tip Test function Station\ String\NO. Test Content Range function keys SBS-6000 STRING TEST Adjust Station:01 V State tip Date \Time And Power 2011-05-10 09:01:23 Testing Auto String:01 Test mode instructs Cell No.002 R 2 . 1 1 2 (V) 0 . 5 37 (mΩ) Test results indicate T 25.0 (℃) Reference and Comparison results Range:4 mΩ Esc REF : <0.483mΩ> Cancel Range 1.
Test type is conductivity test interface as below: Function tip Test function Station\ String\NO. Test Content STRING TEST Adjust Station:01 V State tip 2011-05-10 09:01:23 Testing Auto String:01 Test mode instructs Cell No.002 G 2 . 1 1 2 (V) 1862 ( S ) Test results indicate T 25.0 (℃) Reference and Comparison results REF : <2070S> function keys Date \Time And Power Esc Cancel Range 89% REF Save Test function Three types: String testing, Cell testing and Conn testing.
auto test and save data automatically. Group, Station, Battery number Display current group, station, battery number three types of test status and display them in different ways. Test display Display test results, string testing and Cell testing display: voltage, impedance and temperature, Conn display impedance and temperature. Range Display impedance test use the current gear, if the test type is conductivity that would not display gear.
Reference value and compare results (Test type is conductivity) “REF: 2070S” stands for 2070S, “89%REF” stands for test conductivity reference value is 89%. When impedance and voltage value marked as means test value exceed alarm threshold, battery status is normal, but if test voltage marked as that means battery voltage is lower than alarms, impedance marked as means compare results lower than replaced value of setup alarm threshold.
How to use Click String testing icon that may enter into the string testing interface as below: 2011-05-10 09:01:23 Manual STRING TEST Station:01 V String:01 R 2 . 1 1 2 (V) 0 . 5 37 (mΩ) T 25.0 (℃) Range:4 mΩ Esc REF : <0.483mΩ> Cancel Range Cell No.002 1.11 REF Save Connection method can refer to “Test Functions” Chapter Before string testing you have to setup parameter of test strings, detailed operation please go for the “String Testing Setup” Chapter.
impedance and temperature at the same time. How to use Click Cell testing icon that can enter into Cell test interface such as follows: 2011-05-10 09:01:23 Saved Manual CELL TEST Cell No.002 V R 2 . 1 1 2 (V) 0 . 5 37 (mΩ) T 25.0 (℃) Range:4 mΩ Esc REF : <0.483mΩ> Cancel Range 1.11 REF Save Connect method please refer to the “Test Functions” Chapter. Before Cell testing please setup Cell parameter, detailed operation method refer to “Cell Testing Setup” Chapter.
temperature of connector. How to use Click connector icon, and then enter into the Conn test interface as follows: 2011-05-10 09:01:23 Saved Manual CONN TEST Station:01 String:01 R 0 . 5 37 (mΩ) T 25.0 (℃) Joint:002-1 Range:4 mΩ REF : <0.483mΩ> 1.11 REF Range Save Esc Cancel Connection method please refer to Chapter “Test Functions” Before Conn testing please setup the parameter of connector first, detailed operation method please refer to “Conn Test Setup” Chapter.
5.4.4 Compare Functions Functions description Compare function that means compare current test result and setup reference value, thereby in this way to judge tested battery health status. Before compare functions, you need to setup comparator (input or test battery sample to obtain reference value), this tester support 300 items data compare. Comparator setup can be down by PC software or also by tester.
2011-05-10 09:01:23 Saved Manual STRING TEST Station:01 V String:01 R 2 . 1 1 2 (V) 0 . 5 37 (mΩ) T 25.0 (℃) Range:4 mΩ Esc REF : <0.483mΩ> Cancel Range Cell No.002 1.11 REF Save When test type is in the mode of Conductivity, “REF:2070S”that means reference value is 2070S ,“ 89%REF ” that means tested conductivity reference value is 89%. When impedance and voltage test value checked by means test results didn’t exceed alarm threshold, and also battery status in normal.
2011-05-10 09:01:23 Saved Manual STRING TEST String:01 Station:01 V G 2 . 1 1 2 (V) 1862 ( S ) T 25.0 (℃) REF : <2070 S> Esc 5.4.5 Cancel Cell No.002 89% REF Save Re-test Functions Functions description In the circumstances of auto save, three test modes are all have Re-test functions, when test clip still connect with tested battery, you need to re-test the battery again, the new test data can overlay last auto save test data.
2011-05-10 09:01:23 Saved Auto STRING TEST Station:01 V String:01 R 2 . 1 1 2 (V) 0 . 5 37 (mΩ) T 25.0 (℃) Range:4 mΩ Esc REF : <0.483mΩ> Cancel Range Cell No.002 1.
2011-05-10 09:01:23 Manual CELL TEST Cell No.001 V R 2 . 1 1 2 (V) 0 . 5 37 (mΩ) T 25.0 (℃) Range:4 mΩ 4 mΩ REF : <0.483mΩ> 40 mΩ 400 mΩ 1.11 REF More Confirm selection by clicking related gear, click functional keys would display other gears setup, as follows: 2011-05-10 09:01:23 Manual CELL TEST Cell No.001 V R 2 . 1 1 2 (V) 0 . 5 37 (mΩ) T 25.0 (℃) Range:4 mΩ REF : <0.483mΩ> 4 Ω 40 Ω 400 Ω 1.
CELL TEST 2011-05-10 09:01:23 Manual Cell No.001 V R 2 . 1 1 2 (V) 0 . 5 37 (mΩ) T 25.0 (℃) Range:4 mΩ REF : <0.483mΩ> 1.11 REF Auto More Esc Click functional keys would display first page gear setup; click functional keys would drop out gears switch functions and get back functional keys of test interface, click gear functional keys would select a proper gear to test. 5.4.
2011-05-10 09:01:23 Saved Manual CELL TEST Cell No.002 V R 2 . 1 1 2 (V) 0 . 5 37 (mΩ) T 25.0 (℃) Range:4 mΩ Esc 5.5 REF : <0.483mΩ> Cancel Range 1.11 REF Save System setting Functions description It is for system time setting, network parameter setting, key voice setting, timing shutdown setting, language setting, restore default setting, Back Light setting, and software version No. view. How to use Click system setting icon, you will enter into system setting choose window.
Navigation Date \Time And Power 2011-05-10 09:01:23 SYSTEM Settings functions 1. Net Set: 2. Time Set: 3. Sound Set: 4. Self-off: 5. Language: 6. Factory Set: 7. Backlight: 8. Version: function keys Esc IP :010. 001. 092. 141 MASK:255. 255. 255. 000 PORT : 06800 Settings content Enter After choose the setting item, press, you will enter into the related setting window. 5.5.
Move to the number which you want to modify by direction key, press number key to input numbers, press to save, pressto quit the network configuration, and won’t save it. 5.5.2 Time setting Functions description It is used to set time and date. How to use After choose the time setting item, press, you will enter into the time setting window. As following: 2011-05-10 09:01:23 SYSTEM 1. Net Set: 2. Time Set: 3. Sound Set: 4. Self-off: 5. Language: 6. Factory Set: 7. Backlight: 8.
How to use After choose the key voice setting item, press, you will enter into the key voice setting window. As following: 2011-05-10 09:01:23 SYSTEM 1. Net Set: 2. Time Set: 3. Sound Set: 4. Self-off: 5. Language: 6. Factory Set: 7. Backlight: 8. Version: Esc Sound Set:ON ON OFF Enter Pressorto set key voice, press to save, pressto quit the key voice setting, and won’t save it. 5.5.
2011-05-10 09:01:23 SYSTEM 1. Net Set: 2. Time Set: 3. Sound Set: 4. Self-off: 5. Language: 6. Factory Set: 7. Backlight: 8. Version: 10 Min 20 Min Self-off:10 Min 30 Min 60 Min Press<10 Min>,<20 Min >,<30 Min>or<60 Min>to set the shutdown time<10 Min>,<20 Min >,<30 Min>or<60 Min>, press to save, pressto quit the key voice setting, and won’t save it. 5.5.5 Language setting Functions description Setting the tester using language, now the SBS-6000 supports Chinese and English.
2011-05-10 09:01:23 SYSTEM 1. Net Set: 2. Time Set: 3. Sound Set: 4. Self-off: 5. Language: 6. Factory Set: 7. Backlight: 8. Version: Esc 5.5.6 Language: English 简体中文 English Enter Restore default setting Functions description It is used to restore the system setting parameters to be the default parameters. How to use After choose the restore default setting item, press, you will enter into the restore default setting window. As following: 2011-05-10 09:01:23 SYSTEM 1. Net Set: 2. Time Set: 3.
press to restore the default parameters and save, pressto quit the setting, and won’t save it. 5.5.7 Back Light setting Functions description It is used to set the LCD display Back Light. How to use After choose the Back Light setting item, press, you will enter into the Back Light setting window. As following: 2011-05-10 09:01:23 SYSTEM 1. Net Set: 2. Time Set: 3. Sound Set: 4. Self-off: 5. Language: 6. Factory Set: 7. Backlight: 8.
2011-05-10 09:01:23 SYSTEM 1. Net Set: 2. Time Set: 3. Sound Set: 4. Self-off: 5. Language: 6. Factory Set: 7. Backlight: 8. Version: VERSION:V2.0 Esc 5.6 Data Browsing Functions description It is used to browse the testing record of string, cell and connector. The string data has the functions of data analysis, Chart for resistance and voltage. The max value, min value and average value can be got by string data analysis. There is no data analysis for cell which can just review the testing data.
2011-05-10 09:01:23 DATA BROWSE -> STRING BROWSE Select the target icon and press . 5.6.1 String Data Browsing Functions description It ‘s for the browsing of string data which display the base station number, string number, batteries in the string and saving time of the last battery. The string tests the deletion of a string and strings. Browse the testing data of each string, testing data analysis, voltage Chart and resistance Chart.
2011-05-11 09:01:23 DATA BROWSE -> STRING BROWSE R Data Station String 01 01 01 02 01 03 01 04 01 05 01 06 01 07 01 08 Page Up Total 005 020 030 046 050 043 052 033 Next Test Time 2011-05-10 09:03:23 2011-05-10 11:10:20 2011-05-10 13:20:32 2011-05-10 14:50:29 2011-05-10 15:10:53 2011-05-10 16:01:13 2011-05-10 16:35:50 2011-05-10 17:03:25 DEL One Clear Select the target string by arrow keys and press . Previous page and next page keys are used for shift pages. String data supports string deletion.
Press in the string data and data analysis is preceded. Max value, min value and average value can be generated by data analysis. STRING BROWSE NO. V (V) R (mΩ) T (℃) Result State H/M/S Y/M/D Switch Max 005 2.112 0.570 25.0 1.17 PASS 09:15:21 11/06/02 2011-05-11 09:01:23 Resistance Min 002 2.112 0.566 25.0 1.17 PASS 09:03:29 11/06/02 REF : <0.483mΩ> Average 2.112 0.568 25.0 Chart There are two ways for data analysis: resistance analysis and voltage analysis.
2011-05-10 09:01:23 Valtage Chart (V) Max:2.113 Average:2.112 Min:2.111 2.000 1 Esc 5 Page Up Next There are max value, min value, average value, reference line and alarm line in resistance Chart. It shows 32 batteries in each page and the user can shift pages by the corresponding keys. 2011-05-10 09:01:23 Resistance Chart (mΩ) Max:0.570 Average:0.568 Min:0.566 Warn 0.483 1 Esc 5 Page Up Next If conductance is tested in the string, a conductance Chart will be generated.
2011-05-10 09:01:23 Conductance Chart (S) Max:1766 Average:1750 Min:1754 2070 Warn 1754 1-1 退出 Page Up Next If there is no string data or the data has been deleted, it will show the following interface. 2011-05-10 09:01:23 DATA BROWSE -> STRING BROWSE NO TEST DATA OF STRING Esc 5.6.2 Cell Data Browsing Functions description It is used for the review of cell test data. The use can view all the data by shifting pages. All cells test data deletion.
How to use Select cell browsing icon , and press . 2011-05-10 09:01:23 DATA BROWSE -> CELL BROWSE Cell NO. 001 002 003 004 005 006 007 008 Page Up Test Time 2011-05-10 09:01:23 2011-05-10 11:10:20 2011-05-10 13:20:32 2011-05-10 14:50:29 2011-05-10 15:10:53 2011-05-10 16:01:13 2011-05-10 16:35:50 2011-05-10 17:03:25 Next Clear Select the target testing serial by arrow keys and press . The user can shift pages for more records. All cell testing data can be deleted by .
2011-05-10 09:01:23 DATA BROWSE -> CELL BROWSE NO. V (V) R (mΩ) T (℃) Result State Time H/M/S Date Y/M/D Esc 001 2.112 0.568 25.0 1.17 PASS 09:01:23 11-5-10 REF : <0.483mΩ> Up Down If there is no cell data or the data has been deleted, it shows the following interface. 2011-05-10 09:01:23 DATA BROWSE -> CELL BROWSE NO TEST DATA OF CELL Esc 5.6.
number, group number, batteries in the string and saving time of the last battery. The Conn tests string deletion and dele all records in connector. Browse the testing data of each Connector, data analysis and Chart. How to use and press .
JOINT BROWSE NO. R (mΩ) T (℃) Result State TimeH/M DateM/D 2011-05-10 09:01:23 Station:01 String:01 001-1 002-1 003-1 004-1 0.568 0.566 0.568 0.568 25.0 25.0 25.0 25.0 1.17 1.17 1.17 1.17 PASS PASS PASS PASS 09:02 09:02 09:03 09:04 06/02 06/02 06/02 06/02 005-1 0.570 25.0 1.18 PASS 09:05 06/02 REF : <0.483mΩ> Page Up Analyse Next There is data analysis function in the testing data of Connector. Press and it will analyzer the current data. Please refer to the following graph.
It will show max value, min value, average value, reference line and alarm line in the resistance Chart. Each page will display 32 batteries and the user can shift pages for more records. 2011-05-10 09:01:23 Resistance Chart (mΩ) Max:0.570 Average:0.568 Min:0.566 Warn 0.483 1 Esc 5 Page Up Next If test type of Connector is conductance, it will show the conductance Chart with max value, min value, average value, reference line and alarm line.
Chart (S) 2011-05-10 09:01:23 Conductance Max:1766 Average:1750 Min:1754 2070 Warn 1754 1-1 退出 Page Up Next If there is no data of Connector or all data has been deleted, it shows the following: 2011-05-10 09:01:23 DATA BROWSE -> CONN BROWSE NO TEST DATA OF CONNECTOR Esc 66 SBS-6000
5.7 PC analysis software operation 5.7.1 Profile BatteryManage is a PC management software developed by SBS for SBS-6000. It can communicate with SBS-6000 by RS-232 serial interface or TCP/IP network interface. Main functions: (1) Read the testing records and save them in the computer. (2) Print the records in computer. (3) Delete the records. (4) Delete the records saved in computer. (5) Synchronous clock. (6) Read or allocate the parameters of the equipment.
Step 2. Select the target language and click “Next”. Step 3. Pop up the box of “Installation - Battery Test Manage” and click “Next”.
Step 4. Click “browse” to locate the software and click “Next”. If locate as default, click “Next”. Step 5. Shortcut for the location of program, recommend to use default setting and click “Next”. Step 6. The options for adding shortcuts, recommend to use default setting and click “Next”.
Step 7. Installation preview. Click “Installation”. Step 8. Click “Finish” to retreat the program and complete the installation.
Uninstall Step 1. Double click “unins000.exe” to uninstall the software. Step 2. Click “Yes” in the popping up dialogue box of Battery Test Manage. Step 3. Click “OK” to retreat the program and complete the uninstall. 5.7.
details: Items Drop-down menu Functions Historical data Open the window of “Historical data” Log out Deactivate the software Device parameter Open the window of “Parameter” File Parameter Communication parameter Testing data Help 72 Open the window of “Local communication parameter” Read Cell data Open “Cell data” window to read testing data in current communication mode. Read string data Open “string data” window to read testing data in current communication mode.
There are 4 operation windows in the software and to get more in the following table: Items Historic Data Functions Display entire testing data saved in computer and print. Read equipment parameter Set equipment parameter Device Parameter Synchronous equipment clock Set comparison reference data of equipment and save it in computer. Set comparison parameter (write the comparison reference data in equipment.) Read string testing data (to display and read string testing data saved in equipment.
Voltage analysis(display the selected voltage Chart and analyzer the max value, min value and average value.) Read cell testing data(display and read the cell testing data saved in equipment.) Cell Data Delete cell data (delete cell testing data saved in equipment.) Save cell data (Save the cell testing data read from the equipment to computer and display them in historic data window.) Read Connector testing data (to display and read Connector testing data saved in equipment.
Set network communication parameters (set IP address and interfaces of the equipment) 5.7.4 Functions of windows 1. Local communication configuration Please configure the communication parameter before other operations to make sure the proper use of software and equipment. The following is the local communication configuration: The serial communication parameters are used to set up a computer system communicating with the equipment's serial number.
address, interface serial should be confirm with the equipment’s. 2. Equipment Parameters The user can read equipment parameter, equipment parameter setting, synchronous equipment clock and comparison parameter setting in this window.
The function of synchronous equipment clock is to write the clock information of the computer in the equipment. The function of ADD is save the information like serials, resistance, unit, voltage type of the equipment parameter window in to the computer as new comparison reference data. The function of DELETE is deleting the comparison reference data from the computer. The function of comparison reference data setting is write all comparison reference records in the equipment. 3.
testing data saved in the equipment and display them in the device data control window according to the current communication setting. The function of Connector testing data delete is to delete all the Connector testing data in the equipment. The function of testing data saving is to save the testing data displayed in the equipment data control window in the computer and show them in the historic data window. The user needs to fill the notes when save the files. If the testing time is wrong (e.g.
The function of cell testing data read is to read the entire cell testing data saved in the equipment and display them in the device data control window according to the current communication setting. The function of cell bar testing data delete is to delete all the cell testing data in the equipment. The function of cell testing data saving is to save the testing data displayed in the equipment data control window in the computer and show them in the historic data window.
The function of string testing data read is to read the entire string testing data saved in the equipment and display them in the device data control window according to the current communication setting. The function of string testing data delete is to delete all the string testing data in the equipment. The function of string testing data saving is to save the testing data displayed in the equipment data control window in the computer and show them in the historic data window.
The entire testing data of the records table is displayed in data displaying area. The function of DELETE is to delete the entire testing data in the selected records table. The function of PRINT is to print the entire testing data in the selected records table. Resistance analysis is to analyzer the resistance results of selected strings and displays the max value, min value, average value and resistance Chart(Only string data and Connector data have this function).
5.8 Instrument charging There is built-in 7.4V 4400mAh Li battery in this instrument. When battery sign is empty, the instrument will prompt no battery and shut down 1 minute later automatically. In order to not affect your usage, please charge it immediately. Li battery can be charged anytime because it has no memory effect. We advise you to charge the battery immediately when it has one grid so as to affect normal use.
Chapter 6 Summary Of Faults Faults Fail to power on Cause Battery electricity exhausted. Display abnormal measurement value Test cable connection is good or not. Abnormal comparison result Set comparison threshold correctly or not. Set comparison threshold value correctly. PC management software can not get data from tester 1. Ethernet cable or RS232 serial cable connects or not. 1.Connect Data Line. 2. Set parameter correctly or not. 3. Whether the internal have data already.
Chapter 7 Technical Parameter Dimension(L × W × H) 190mm×108mm×50mm Weight 1kg Display 3.5 inches LCD, 320*240 Range: 1µΩ ~ 400Ω Precision: Test resistance The Gear of 4mΩ:±1.0%rdg ±8dgt Other Gears: ±0.8%rdg ±6dgt Range: DC 0 ~ 80V Test voltage Precision: ±0.
External Power: Power Adapter Battery: Rechargeable Lithium Battery(8.4V/4400mAh) Power Battery Operation Time: About 8 hours Battery Charging Time: About 6 hours for full discharge Service Information Web Site: www.sbsbattery.com Business Telephone: (262) 703-5800 Technical Support Telephone: (800) 554-2243 techsupport@sbsbattery.