Operating instructions
© National Instruments Corporation 17 cRIO-9022 Operating Instructions and Specifications
Physical Characteristics
If you need to clean the controller, wipe it with a dry towel.
Screw-terminal wiring............................ 12–18 AWG copper conductor
wire with 10 mm (0.39 in.) of
insulation stripped from the end
Torque for screw terminals .................... 0.5 to 0.6 N · m
(4.4 to 5.3 lb · in.)
Weight.................................................... Approx. 609 g (21.5 oz)
Environmental
The cRIO-9022 is intended for indoor use only. For outdoor use, mount the
CompactRIO system in a suitably rated enclosure.
Operating temperature
(IEC 60068-2-1, IEC 60068-2-2)........... –20 to 55 °C
Caution For information about how mounting configuration can affect the accuracy of
C Series modules, go to
ni.com/info and enter the info code rdcriotemp.
Storage temperature
(IEC 60068-2-1, IEC 60068-2-2)........... –40 to 85 °C
Ingress protection................................... IP 40
Operating humidity
(IEC 60068-2-56)................................... 10 to 90% RH, noncondensing
Storage humidity
(IEC 60068-2-56)................................... 5 to 95% RH, noncondensing
Maximum altitude .................................. 2,000 m
Pollution Degree (IEC 60664) ............... 2