Technical data

21
2000225294A
6 Boiler Location, Flue and Ventilation
6.3 Terminal guard
A terminal guard is required if persons could come into contact
with the terminal or the terminal could be subject to damage.
If a terminal guard is required, it must be positioned to provide
a minimum of 50mm clearance from any part of the terminal and
to be central over the terminal.
A suitable terminal guard type K3, see diagram 6.2 can be
supplied by:
Tower flue components Ltd.
Morley road, Tonbridge, Kent, TN9 1RA.
6.4 Flue options
There are various flue systems to choose from as follows:
Horizontal top flue, Flue Extension, 90
O
Vertical flue. Flue Extensions 45
O
and 90
O
Twin flue. Flue Extensions 45
O
and 90
O
For detailed information refer to flue options guide. This is
available from your nearest stockist.
6.5 Timber Frame Buildings
If the boiler is to be installed in a timber frame building it should
be fitted in accordance with the Institute of Gas Engineers
document IGE/UP/7/1998. If in doubt seek advice from the local
gas undertaking or Saunier Duval.
6.6 Room Ventilation
The boiler is room sealed, so when it is installed in a room or
space, a permanent air vent is not required.