PM172 Quick Start Guide Quick Start Guide PM172 Series Powermeters PM172P/PM172E/PM172EH Series PM172 Powermeters 1
PM172 Quick Start Guide Introduction The PM172 is a compact, multi-function, three-phase AC powermeter and power quality analyzer specially designed to meet the requirements of users ranging from electrical panel builders to substation operators. If you are familiar with the PM172 Powermeter, use this quick start guide to prepare the units for operation. If you are not familiar with the PM172, read the Installation and Operation Manual carefully before installing and using the unit.
PM172 Quick Start Guide Figure 2 STEP 1 (ANSI 4" round cutout): Mount the display module in cutout Figure 3 STEP 1 (DIN 92x92mm square cutout): Mount the display module in cutout Series PM172 Powermeters 3
PM172 Quick Start Guide Figure 4: Slide and position the meter on locating studs Figure 5: Affix the meter using the thumb nuts 4 Series PM172 Powermeters
PM172 Quick Start Guide Electrical Installation IMPORTANT! Only qualified personnel can perform setup. All incoming power sources must be turned off during installation. During operation of the Powermeter, hazardous voltages are present on the input terminals. Failure to observe precautions can result in serious or even fatal injury, or damage to equipment. Refer to the installation and operation manual for further information.
PM172 Quick Start Guide Figure 7: Typical Installation 1 The typical installation diagram above shows a 4-Wire Wye 3-element connection using 3 PTs and 3 CTs. The wiring mode is 4LL3 or 4Ln3.
PM172 Quick Start Guide The typical installation diagram above shows a 4-Wire Wye 2½-element connection using 2 PTs and 3 CTs. The wiring mode is 3LL3 or 3Ln3. The voltages must be balanced for the configuration to provide accurate power measurements. There are approximately nine different wiring configurations in the PM17X Series. Refer to the Installation and Operational Manual for additional configurations. For electrical installation of the display panel follow the following steps: 1.
PM172 Quick Start Guide Setup is performed directly from the display panel or via the communication ports using PAS communication software. In Data Display mode, the navigation buttons function as follows. The MIN/MAX button switches to the Min/Max Maximum Demands display pages. When briefly pressed again, it switches back to the common measurements display. The TDD/THD/ESC button switches between different total harmonics (THD/TDD) displays.
PM172 Quick Start Guide Basic Setup Entering the Password The setup change menu is secured by a four-digit user password. The meter is primarily shipped with the password preset to 0, and password protection disabled. You can change the password and enable password protection through the Access Control menu. If authorization is not required, just press the ENTER button to move to the Main menu; otherwise enter a correct password to be authorized to access the meter setup.
PM172 Quick Start Guide To change the option: 1. Press the SELECT button to activate the lower window. 2. Use the UP and DOWN arrow buttons to select the desired option. 3. Press ENTER to confirm your changes and to store your new setting, or press ESC to discard changes. The table below lists the available options. 4. Press ESC to exit the menu.
PM172 Quick Start Guide Setting the Communications You communicate with the meter via a changeable COM1 communication port, or through a second factory set serial RS-485/RS-422 COM2 port. Communications Connections Several communication options are available for the PM172: • COM1 (check the label on the back of your meter): RS-232/RS-422/RS-485 56K Dial-up modem Ethernet 10/100BaseT Profibus DP • COM2: RS-422/RS-485 The RS-232/RS-422/RS-485 port is the standard port for COM1.
PM172 Quick Start Guide 4. In the Sampling Rate box, select a rate at which PAS updates data on your screen when you continuously poll the device in the PAS Data Monitor. The communication protocol and port settings in PAS must match the settings made in your device. COM1 Settings Code Parameter Options Description Prot Communications protocol ASCII, rtu*, dnP3 ASCII, Modbus RTU or DNP3.0 protocol rS Port Interface, depends on order 232 = RS-232 485 = RS-485 422 = RS-422 dial = Dial-up Modem Eth.
PM172 Quick Start Guide AC0140 05-12001-3 Figure 10: COM1 Telephone Line Connection AC0139 RJ45 05-12001-4 Figure 11: COM1 Ethernet Connection Series PM172 Powermeters 13
PM172 Quick Start Guide Communicating via the Internet If you are communicating through the Ethernet port, define the IP address of your meter on the network. 1. On the Instrument Setup tab, select Internet Site. 2. Click on the Connection tab. 3. Select the IP Address and type in the IP address of your meter. The default IP address preset at the factory is 192.168.0.203. 4. In the Protocol box, select the communications protocol for the TCP port.