Chapter 5 Data Display 43
Fast Reset of Accumulated Data
Select a display page where the data you want to reset is displayed. To reset:
Min/Max log registers: select a Min/Max page from the Min/Max measurements
display (where Lo or Hi is displayed in the PAGE window in the PM296 or at the left
in the lower window in the RDM096).
Ampere and volt maximum demands: select the maximum demands page in the
PM296, or select the ampere or volt maximum demand page from the Min/Max
measurements display in the RDM096 (where Hd is displayed at the left in the lower
window, and volts or amps arrow LEDs at the right are lit).
Power maximum demands in the RDM096: select the power maximum demand page
from the Min/Max measurements display (where Hd is displayed at the left in the
lower window, and kVA/MVA and kW/MW arrow LEDs at the right are lit).
Total and phase energies: select the energy measurements display (not a TOU
register).
While holding the key, press and hold for about 5 seconds. The
displayed data is reset to zero.
5.2 Data Display Formats
Tables 5-1 and 5-2 specify all front panel local displays available in the display
mode.
The PM296 Data Display
The display windows are labeled in the table in the direction up-to-down and left-
to-right as shown in the following picture.
11
1 4
2
3
5
6
kVA total
7
8
9
10
Table 5-1 Displayed Parameters for the PM296
Page Window PAGE Parameter Digits Unit
LEDs
Common Measurements
1 1 Voltage L1/L12 4 V/kV
1 2 Voltage L2/L23 4 V/kV
1 3 Voltage L3/L31 4 V/kV
1 4 Current L1 4 A
1 5 Current L2 4 A
1 6 Current L3 4 A
1 7 Frequency 4 Hz
1 8 Total kW 5 kW/MW
ENTERSELECT