User Manual
Chapter 4 Setup Menus 29
Code Parameter Unit Scale
rt P
Total kW kW/MW -Pmax to Pmax
rt q
Total kvar kvar/Mvar -Pmax to Pmax
rt S
Total kVA kVA/MVA 0 to Pmax
rt PF
Total PF -0.000 to 0.000
rt PF.LG
Total PF lag 0 to 1.000
rt PF.Ld
Total PF lead 0 to 1.000
rt Au.C
Auxiliary current A/mA 0 to Imax aux
rt nEU.C
Neutral current A 0 to Imax
rt Fr
Frequency Hz 0 to 100.00
rt U.dC
DC Voltage V 0 to 9999.00
Average Measurements
Ar U 1
Voltage L1/L12 V/kV 0 to Vmax
Ar U 2
Voltage L2/L23 V/kV 0 to Vmax
Ar U 3
Voltage L3/L31 V/kV 0 to Vmax
Ar U.AG
3-phase average voltage V/kV 0 to Vmax
Ar U.L12
Voltage L12 V/kV 0 to Vmax
Ar U.L23
Voltage L23 V/kV 0 to Vmax
Ar U.L31
Voltage L31 V/kV 0 to Vmax
Ar U.L.AG
3-phase average L-L voltage V/kV 0 to Vmax
Ar C1
Current L1 A 0 to Imax
Ar C2
Current L2 A 0 to Imax
Ar C3
Current L3 A 0 to Imax
Ar C.AG
3-phase average current A 0 to Imax
Ar P
Total kW kW/MW -Pmax to Pmax
Ar q
Total kvar kvar/Mvar -Pmax to Pmax
Ar S
Total kVA kVA/MVA 0 to Pmax
Ar PF
Total PF -0.000 to 0.000
Ar PF.LG
Total PF lag 0 to 1.000
Ar PF.Ld
Total PF lead 0 to 1.000
Ar Au.C
Auxiliary current A/mA 0 to Imax aux
Ar neU.C
Neutral current A 0 to Imax
Ar Fr
Frequency Hz 0 to 100.00
Present Demands
Acd.P.i
Accumulated kW import demand kW/MW 0 to Pmax
Acd.P.E
Accumulated kW export demand kW/MW 0 to Pmax
Acd.q.i
Accumulated kvar import demand kvar/Mvar 0 to Pmax
Acd.q.E
Accumulated kvar export demand kvar/Mvar 0 to Pmax
Acd.S
Accumulated kVA demand kVA/MVA 0 to Pmax
Imax (100% over-range) = 2 × CT primary current [A]
Imax aux (100% over-range) = 2 × Auxiliary CT primary current [A]
Direct wiring (PT Ratio = 1):
Vmax
(690 V input option) = 828.0 V
Vmax (120 V input option) = 144.0 V
Pmax = (Imax × Vmax × 3) [kW x 0.001] @ wiring modes 4Ln3, 3Ln3
Pmax = (Imax × Vmax × 2) [kW x 0.001] @ wiring modes 4LL3, 3OP2, 3dir2, 3OP3, 3LL3
NOTE: Pmax is rounded to nearest whole kW units.
If Pmax is more than 9999.000 kW, it is truncated to 9999.000 kW