User Manual

Chapter 4 Setup Menus
24
Code Parameter Options Description
dAtA
Data format
7E
7 bits, even parity
8n
8 bits, no parity
8E
8 bits, even parity
H.Sh
Incoming flow
nonE
No handshaking
control (handshaking)
SOFt
Software handshaking
(XON/XOFF protocol)
Hard
Hardware handshaking (CTS
protocol)
Ctrl
Outgoing flow control
nonE
RTS signal not used
(RTS/DTR)
dtr
RTS permanently asserted
(DTR mode)
rtS
RTS asserted during the
transmission
Prn.P
Printout period
1, 2, 5, 10, 15,
Time interval between
20, 30, 60 min successive printouts
COM2
Code Parameter Options Description
Prt.2
Communications
protocol
ASCII
rtu
dnP3
ASCII protocol
Modbus RTU protocol
DNP3.0 protocol
rS
Interface standard
422
RS-422 interface
485
RS-485 interface
Addr
Address
0-99 ASCII
1
-247 Modbus
Powermeter address
bAud
Baud rate
110
110 baud
300
300 baud
600
600 baud
1200
1200 baud
2400
2400 baud
4800
4800 baud
9600
9600 baud
19.20
19,200 baud
38.40
38,400 baud
dAtA
Data format
7E
7 bits, even parity
8n
8 bits, no parity
8E
8 bits, even parity
CPtb
ASCII compatibility
mode
diS
, En
Disables/enables ASCII
compatibility mode. For more
information, see ASCII
Communications Protocol
Reference Guide