User Manual
Chapter 2 Installation 17
2.2.7 Analog Output
The PM296/RPM096 provides two optically isolated analog outputs with an internal
power supply and current output options of 0-20 mA and 4-20 mA (current loop load of
up to 500 Ohm), 0-1 mA and ±1 mA (current loop load of up to10 kOhm).
Figure 2-15 Analog Output Connection
2.2.8 DC Input
34
54
+
-
VDC
REAR VIEW
Figure 2-16 DC Input Connection