Owner's manual
Chapter 1 General I N F O R M A T I O N Customized O P T I O N S
PM130 PLUS Powermeter Series 15
2 electro-mechanical or solid-state relay outputs (RO) for alarms
and controls, and for output energy pulses; unlatched, latched
and pulse operations, failsafe operation for alarm notifications;
programmable pulse width; direct remote relay control through
communications; 1-cycle update time.
12DI/4DO module
12 dry contact digital inputs (DI) for monitoring external contacts
and receiving pulses from energy, water, and gas meters
Programmable de-bounce time; 1-ms scan time.
4 electro-mechanical relay outputs (RO) for alarms and controls,
and for output energy pulses; unlatched, latched and pulse
operations, failsafe operation for alarm notifications;
programmable pulse width; direct remote relay control through
communications; 1-cycle update time.
Analog Output
The PM130 PLUS analog output (AO) expansion module provides:
4 optically isolated analog outputs with an internal power supply;
Options for 0-20mA, 4-20mA, 0-1mA, and 1mA output; 1-cycle
update time.
Additional Communication Port – COM2
A second COM2 communication port can be ordered as an expansion
module. COM2 options available:
Ethernet 10/100BaseT port; MODBUS/TCP , DNP3/TCP and IEC
60870-5-104 communications protocols
Profibus DP port
RS-232/RS-422/RS-485 port; MODBUS RTU, DNP3, SATEC ASCII
and IEC 60870-5-101 communication protocols;
GPRS communications port
TOU - Battery-Operated Clock Unit
The TOU module provides:
A precise clock with battery backup; 6-year clock retention time
4 dry contact digital inputs (DI) for monitoring external contacts
and receiving pulses from energy, water and gas meters;
programmable de-bounce time; 1-ms scan time.
1.3 Customized Options
Presentation of data on the front display and via communications can be
customized to best suit the user application.
Device Resolution
A low or high-resolution option can be selected for the presentation of
voltage, current, and power for use in high and low power applications.
See Measurement Units for more information.
Energy Rollover
The energy rollover limit can be changed in the meter to provide 4-digit to
9-digit energy resolution. See Device Options in Chapter 5 for details. The
meter display is capable of showing full 9-digit energy counters using two
LED windows.