PM130 PLUS Powermeter Series PM130P/PM130E/PM130EH Installation and Operation Manual BG0425 Rev.
LIMITED WARRANTY The manufacturer offers the customer a 24-month functional warranty on the instrument for faulty workmanship or parts from date of dispatch from the distributor. In all cases, this warranty is valid for 36 months from the date of production. This warranty is on a return to factory basis. The manufacturer does not accept liability for any damage caused by instrument malfunction.
Do not use the instrument for primary protection functions where failure of the device can cause fire, injury or death. The instrument can only be used for secondary protection if needed. Read this manual thoroughly before connecting the device to the current carrying circuits. During operation of the device, hazardous voltages are present on input terminals. Failure to observe precautions can result in serious or even fatal injury or damage to equipment.
Quick Start Guide This section can be used by a licensed electrician to install and perform basic PM130 PLUS setup. For more detailed PM130 PLUS setup and use instructions, see the following chapters in this manual. This quick start guide will assist you to have the unit running for the first time. During the operation of the meter, hazardous voltages are present in the input terminals. Failure to observe precautions can result in serious or even fatal injury, or damage to equipment.
Mounting two PM130 PLUS side by side Connecting the PM130 PLUS Unit To connect the PM130 PLUS: 1. Ensure that all incoming power sources are OFF. 2. Check that you have the appropriate power supply. 3. Connect to the external CT by passing the external CT wire through the meter CT core. Observe the arrow that indicates the current direction. 4. In case of a retrofit application where each external CT ends with two wires: Pass one wire through the meter CT core.
Common Wiring Mode: 4LL3 or 4Ln3 CT wiring 6 PM130 PLUS Powermeter Series
To connect an Option module: 1. Assemble the module on the meter. 2. Power the PM130 PLUS unit on. Assembling a module To operate the PM130 PLUS: 1. Perform device diagnostics. 2. Configure the device through the PM130 PLUS unit front panel display. 2. Configuring the PM130 PLUS remotely 1. Install the PAS application software on your PC. 2. Configure the PAS database for your meter.
3. Configure the PAS communications settings. 4. Upgrade the meter firmware if a new version is available. 5. Set up the meter using the PAS application software. 6. Configure your security settings through the meter security setup. 7. Configure your communication protocol settings. 8. Configure Billing/TOU registers. At this stage, the PM130 PLUS should be ready for operation.
Table of Contents Chapter 1 General Information ..........................................................................12 1.1 Features.......................................................................................................................12 1.2 Available Options .......................................................................................................14 Digital I/O ............................................................................................................
Min/Max and Maximum Demand Display ................................................................. 47 Harmonics Display (PM130EH) ............................................................................... 48 Energy Display (PM130E/EH).................................................................................. 49 3.3 Status Display.............................................................................................................50 Pulse and Time Counters...............................
Chapter 6 6.1 6.2 6.3 6.4 6.5 6.6 Resetting Accumulators, Maximum Values and Files ...................................... 106 Updating the Meter Clock...................................................................................... 107 Viewing and Clearing Device Diagnostics .......................................................... 109 Viewing Communication Status and Statistics.................................................. 110 Remote Relay Control ................................................
Chapter 1 General Features I N F O R M A T I O N Chapter 1 General Information The PM130 PLUS is a compact, multi-function, three-phase AC powermeter specially designed to meet the requirements of users ranging from electrical panel builders to substation operators.
Chapter 1 General I N F O R M A T I O N Features True RMS, volts, amps, power, power factor, neutral current, voltage and current unbalance, frequency Ampere/Volt demand meter 25/50/60/400 Hz measurement capabilities Billing/TOU Energy Meter (PM130E and PM130EH) Class 0.
Chapter 1 General Available I N F O R M A T I O N O P T I O N S LED bar graph showing percent load with respect to userdefinable nominal load current Real-time Clock Internal clock with 20-second retention time Optional battery-operated clock unit (see Available Options) Communications Standard 2-wire RS-485 communication port; Modbus RTU, DNP3, SATEC ASCII communication protocols and IEC 61870-5-101 Optional second communication port (see Available Options); Modbus RTU, Modbus/TCP,
Chapter 1 General I N F O R M A T I O N Customized O P T I O N S 2 electro-mechanical or solid-state relay outputs (RO) for alarms and controls, and for output energy pulses; unlatched, latched and pulse operations, failsafe operation for alarm notifications; programmable pulse width; direct remote relay control through communications; 1-cycle update time.
Chapter 1 General Measured I N F O R M A T I O N P A R A M E T E R S Display Options Different display options are available for customization to be used in dark or non-safe locations, or in places that are hardly accessible for observation. See Configuring the Display in Chapter 5 for more information. 1.4 Measured Parameters Table 1: Measured and Displayed Parameters Parameter Display Comm.
Chapter 1 General Measured I N F O R M A T I O N Parameter kW Predicted Demand Import & Export Display Comm.
Chapter 2 Installation Site R E Q U I R E M E N T S Chapter 2 Installation This chapter discusses the following types of physical installations for the PM130 PLUS Powermeter: Mechanical Installation Electrical Installation I/O Connections COM Port Connections. 2.
Chapter 2 Installation Mechanical I N S T A L L A T I O N 2.3 Mechanical Installation Refer to the figures provided in this section to properly perform the mechanical installation. Figure 2-1.
Chapter 2 Installation Mechanical I N S T A L L A T I O N Panel Mounting To mount the meter in cutout (ANSI 4" round or DIN 92x92mm square cutout): 1. Position the meter in the cutout. 2. Affix the meter using washers and nuts. (Add short text on Panel Mounting, a heading should always have text) Figure 2-2. Mounting DIN Rail Mounting The PM130 can be mounted on a 35-mm DIN rail. Figure 2-3.
Chapter 2 Installation Mechanical I N S T A L L A T I O N Figure 2-4.
Chapter 2 Installation Electrical I N S T A L L A T I O N 2.4 Electrical Installation The equipment installation shall conform to the following instructions: a) a switch or circuit-breaker shall be included in the building installation; b) It shall be in close proximity to the equipment and within easy reach of the OPERATOR; c) It shall be marked as the disconnecting device for the equipment. Before installing, ensure that all incoming power sources are shut OFF.
Chapter 2 Installation Electrical I N S T A L L A T I O N Terminals Figure 2-7 Terminals - Rear View Power Source Connection The equipment installation shall conform to the following instructions: a) a switch or circuit-breaker shall be included in the building installation; b) It shall be in close proximity to the equipment and within easy reach of the OPERATOR; c) It shall be marked as the disconnecting device for the equipment.
Chapter 2 Installation Electrical I N S T A L L A T I O N Voltage Input connection The equipment installation shall conform to the following instructions: a) a switch or circuit-breaker shall be included in the building installation; b) It shall be in close proximity to the equipment and within easy reach of the OPERATOR; c) It shall be marked as the disconnecting device for the equipment. Before installing, ensure that all incoming power sources are shut OFF.
Chapter 2 Installation Electrical I N S T A L L A T I O N In case of a retrofit application where each external CT ends with two wires: 1. Pass one wire through the meter CT core. 2. Connect the wire to one of the meter termination screws. 3. Connect the second wire from the external CT to the termination screw to close the loop. Figure 2-8 Current Input Connection Wiring Diagrams For AC input ratings, see Technical Specifications in Appendix A for more details.
Chapter 2 Installation Electrical I N S T A L L A T I O N Figure 2-9 3-Wire 2-Element Delta Direct Connection Using 2 CTs (Wiring Mode = 3dir2) Figure 2-10 4-Wire Wye 3-Element Direct Connection Using 3 CTs (Wiring Mode = 4LL3 or 4Ln3) 26 PM130 PLUS Powermeter Series
Chapter 2 Installation Electrical I N S T A L L A T I O N Figure 2-11 4-Wire Wye 3-Element Connection Using 3 PTs, 3 CTs (Wiring Mode = 4LL3 or 4Ln3) Figure 2-12 3-Wire 2-Element Open Delta Connection Using 2 PTs, 2 CTs (Wiring Mode = 3OP2) PM130 PLUS Powermeter Series 27
Chapter 2 Installation Electrical I N S T A L L A T I O N This configuration provides accurate power measurements only if the voltages are balanced.
Chapter 2 Installation Electrical I N S T A L L A T I O N Figure 2-15 4-Wire 3-Element Delta Direct Connection Using 3 CTs (Wiring Mode = 4LL3 or 4Ln3) Figure 2-16 3-Wire 2½-Element Broken Delta Connection Using 2 PTs, 3 CTs (Wiring Mode = 3bLn3 or 3bLL3) PM130 PLUS Powermeter Series 29
Chapter 2 Installation I/ O C O N N E C T I O N S 2.5 I/O Connections Before I/O Module installation ensure that all incoming power sources are shut OFF. Failure to observe this practice can result in serious or even fatal injury and damage to equipment. Figure 2-17 Module Connector Cover – Before Module Assembly For I/O ratings, see Technical Specifications in Appendix A.
Chapter 2 Installation I/ O C O N N E C T I O N S Figure 2-19 Relay Output Connection Digital Inputs Four optically isolated status inputs are provided for status monitoring, pulse counting, external power demand period, and time synchronization. Figure 2-20 Digital Input Connection 12DI/4RO Module The 12DI/4RO module can be equipped with optional communication port COM2 – ETHERNET or RS-422/485.
Chapter 2 Installation I/ O C O N N E C T I O N S Relay Outputs There are four electro-mechanic relay outputs provided for energy pulsing, alarms, or remote control. Figure 2-22 Relay Output Connection Digital Inputs 12 optically isolated status inputs are provided for status monitoring, pulse counting, external power demand period, and time synchronization.
Chapter 2 Installation I/ O C O N N E C T I O N S 4AO Module - Analog Outputs The 4AO module has four optically isolated analog outputs with an internal power supply and current output options of 0-20 mA and 4-20 mA (current loop load of up to 500 Ohm), 0-1 mA and ±1 mA (2mA 100% overload, current loop load of up to 5 kOhm). Figure 2-24 Analog Output Connection It is recommended to connect unused Analog output channels to Common terminal.
Chapter 2 Installation I/ O C O N N E C T I O N S Digital Inputs Figure 2-25 TOU Digital Input Connection TOU – Battery Replacement WARNING! Only qualified personnel familiar with the instrument and its associated electrical equipment must perform the RTC battery backup replacement. To replace the CR1632 RTC battery: 34 1. Remove the TOU module from the PM130 PLUS compartment 2. Open the TOU MODULE case by applying a flat screwdriver at three snap-in slit (1, 2 and 3), as shown in Figure 2-26.
Chapter 2 Installation Communications C O N N E C T I O N S Figure 2-26 TOU RTC Battery Replacement 2.6 Communications Connections Before installing the Communication Module, ensure that all incoming power sources are shut OFF. Failure to observe this practice can result in serious or even fatal injury and damage to equipment.
Chapter 2 Installation Communications C O N N E C T I O N S COM1 RS-485 Connection Figure 2-27 COM1 RS-485 2-Wire Connection The connector is removable with three captured-wire terminals.
Chapter 2 Installation Communications C O N N E C T I O N S ETH module – COM2 Ethernet Connection Figure 2-28 COM2 Ethernet Connection The ETH module TERMINAL is for use only with equipment which has no live parts which are ACCESSIBLE The RATING of the insulation of the external equipment for use with the ETH module, shall comply according to Installation Category II for insulation to be suitable for SINGLE FAULT CONDITION The external equipment TERMINAL connection type is RJ-45 The
Chapter 2 Installation Communications C O N N E C T I O N S PRO module – COM2 PROFIBUS Connection Figure 2-29 COM2 PROFIBUS Connection The PRO module TERMINAL is for use only with equipment which has no live parts which are ACCESSIBLE The RATING of the insulation of the external equipment for use with the PRO module, shall comply according to Installation Category II for insulation to be suitable for SINGLE FAULT CONDITION The external equipment TERMINAL connection type is DB9 The type
Chapter 2 Installation Communications C O N N E C T I O N S RS-232/422-485 module – COM2 Connection Figure 2-30: COM2 RS-232 connection PM130 PLUS Powermeter Series 39
Chapter 2 Installation Communications C O N N E C T I O N S Figure 2-31 COM2 RS-422/485 connection The RS-232/422-485 module TERMINALS are for use only with equipment which has no live parts which are ACCESSIBLE The RATING of the insulation of the external equipment for use with The RS-232/422-485 module, shall comply according to Installation Category II for insulation to be suitable for SINGLE FAULT CONDITION The external equipment TERMINAL connection type is normally terminal block fo
Chapter 2 Installation Communications C O N N E C T I O N S The GSM/GPRS SIM must not have any incoming voice call. The customer must require from the Service Provider for DATA services only The GPRS modem module can be equipped with two different antennas: internal Antenna for installation into plastic closet or no-metallic environment. For metallic installation use external antenna See Setting Up GPRS Network in Chapter 5 for information on configuring GPRS communications in your meter.
Chapter 3 Using F R O N T D I S P L A Y Chapter 3 Indicators A N D C O N T R O L S Using Front Display This chapter provides PM130 PLUS Power meter series front panel information and operating procedures. Figure 3-1: PM130 PLUS Unit 3.1 Indicators and Controls Device Diagnostics After applying power to the meter, a one-digit start-up diagnostic code is shown for 1 second on all LEDs. Code 8 indicates a normal power-up sequence.
Chapter 3 Using F R O N T D I S P L A Y Data D I S P L A Y Load Bar Graph The load bar graph displays the amount, in percent (40% to 110%), of the present current load with respect to user-defined nominal load current. The reference nominal current can be set up in amps through the display setup (see Configuring the Display). If it is set to 0 (default), the current load is referenced to the specified CT primary current. Energy Pulse LED The PM130E and PM130EH have a red “Energy Pulse” LED.
Chapter 3 Using F R O N T D I S P L A Y Data D I S P L A Y For the PT ratio above 4.0, voltages are displayed in kilovolts with three decimal places, and power in megawatts with three decimal places. High Resolution Option Currents are displayed in amperes with up to two decimal places below 10,000 A, and in kilo amperes above 10,000 A.
Chapter 3 Using F R O N T Data D I S P L A Y D I S P L A Y Brightness The PM130 display has a 3-level adjustable brightness. It is normally preset at the factory to the highest level. You can adjust the display through the display setup (see Configuring the Display). Navigation Buttons Figure 3-2: Navigation Buttons See the following table for button operations in data display mode. Button Action Operations UP Press and release Scroll through pages backwards.
Chapter 3 Using F R O N T Data D I S P L A Y D I S P L A Y This function is not operational if the meter is password protected and the simple reset is not allowed in protected mode (see Configuring the Display). Common Measurements Display Scroll through pages with the UP and DOWN arrow buttons.
Chapter 3 Using F R O N T Data D I S P L A Y D I S P L A Y Table 4: Common Measurements (Amp-Demand version) 1 I1 I2 I3 Amps 2 In Neutral current Min/Max and Maximum Demand Display 1. Press the MAX/MIN button. The MIN, MAX, or MAX DMD LED is illuminated when in the MIN/MAX display. 2. Use the UP and DOWN arrow buttons to scroll through the Min/Max and Max. Demand pages. To see the time and date of the event occurrence: 1. Press simultaneously the SELECT and UP buttons. 2.
Chapter 3 Using F R O N T Data D I S P L A Y D I S P L A Y DMD V2/V23 V3/V31 10 MAX DMD I1 I2 I3 Maximum ampere demands 11 MAX DMD kVA/MVA PF kW/MW Maximum VA demand PF at maximum VA demand Maximum W demand 12 MAX DMD A neut. Maximum neutral current demand var Maximum var demand Table 6: Min/Max and Maximum Demands (Amp-Demand version) 1 MAX DMD I1 I2 I3 Maximum ampere demands 2 MAX DMD A neut. Maximum neutral current demand Harmonics Display (PM130EH) 1.
Chapter 3 Using F R O N T Data D I S P L A Y 19 39. V1/V12 HD% V2/V23 HD% V3/V31 HD% D I S P L A Y Order 39 harmonic distortion Table 9: Individual Current Harmonics 1 Order 3 harmonic distortion 3. I1 HD% I2 HD% I3 HD% Order 5 harmonic distortion 5. I1 HD% I2 HD% I3 HD% I1 HD% I2 HD% I3 HD% Order 39 harmonic distortion 2 … 19 39. Energy Display (PM130E/EH) 1. Press the ENERGY button. The kVAh, kvarh, or kWh LED is illuminated. 2.
Chapter 3 Using F R O N T Status D I S P L A Y 9 Ac.i 2 1234 56789 Phase L2 kWh import 10 rE.i 2 1234 56789 Phase L2 kvarh import 11 AP. 2 1234 56789 Phase L2 kVAh 12 Ac.i 3 1234 56789 Phase L3 kWh import 13 rE.i 3 1234 56789 Phase L3 kvarh import 14 AP. 3 1234 56789 Phase L3 kVAh D I S P L A Y Table 11: TOU Energy Register 1 1 r1.t1 1234 56789 Tariff 1 reading 2 r1.t2 1234 56789 Tariff 2 reading r1.
Chapter 3 Using F R O N T 3. Status D I S P L A Y D I S P L A Y Use the UP and DOWN arrow buttons to scroll through the status pages. Figure 3-3: Status Display To exit the Status Display: 1. Press ESC to return to the primary device menu. 2. Press ESC to return to the Data display. Table 13: Status Display Parameters 1 PhS rot POS/nEG/Err Phase rotation order 2 A. V1 angle V2 angle V3 angle Voltage angles (±180°, referenced to V1) A.
Chapter 3 Using F R O N T Status D I S P L A Y D I S P L A Y 11. 01.01 14 rSSi GPRS communications status (with an external GPRS modem): RSSI = received signal strength, dBm GPRS status: Uncon = not connected, UnrEG = not registered, rEG = registered Pulse and Time Counters You can use the 5-digit meter counters either as regular pulse/event counters to count external pulses or setpoint events, or as time counters to count setpoint operation time.
Chapter 3 Using F R O N T Using D I S P L A Y T H E M E N U S Frequent hardware failures may be the result of excessive electrical noise in the region of the device. If the meter continuously resets itself, contact your local distributor. A configuration reset may also be a result of the legal changes in the meter configuration when other configuration data is affected by the changes.
Chapter 3 Using F R O N T D I S P L A Y Using T H E M E N U S The menu has three entries: StA: Status Display entry (see the Status Display section) OPS: Main setup menu entry allowing to review setup options CHG: Main setup menu entry allowing changing setups, updating the clock and resetting accumulated values. To access the Status Display: 1. If the StA window is not highlighted, use the SELECT button to activate it. 2.
Chapter 3 Using F R O N T D I S P L A Y Using T H E M E N U S the bottom item acts as an assisting exit window. To select a menu entry from the main menu: 1. If the upper item is not highlighted, use the SELECT button to activate it. Figure 3-4: Main Menu 2. Scroll through the menu list by pressing briefly the UP or DOWN arrow buttons until the required menu entry appears. 3. Press the ENTER button.
Chapter 3 Using F R O N T D I S P L A Y Using T H E M E N U S pressed continuously, the number is changed approximately twice per second. 4. Press the ENTER button to store your selection or press the ESC button to leave the parameter unchanged. You return to the middle window and can continue scrolling through the remaining parameters or return to the main menu. 5. 56 Press ESC to exit the menu.
Chapter 4 Using P A S S O F T W A R E Chapter 4 Installing P A S Using PAS Software The support PAS software is a configuration and data acquisition tool that allows you to configure all of the PM130 PLUS features, monitor your meters on-line, retrieve recorded files and view reports. PAS can communicate with your PM130 PLUS via a serial port and via the Ethernet. This chapter gives information on how to install and run PAS on your computer, and how to prepare information for your meter using PAS.
Chapter 4 Using P A S S O F T W A R E Creating A N E W S I T E F O R Y O U R M E T E R Figure 4-1: Configuration Dialog Box – Instrument Setup Tab 58 2. Click the Sites button on the right-hand-side. 3. From the Look in box, select the directory where a new database will be stored. By default, it is the Sites directory. 4. Type a site name for your device in the File name box, click New, and then click OK. 5. On the Instrument Setup tab, select PM130 PLUS in the Model box.
Chapter 4 Using P A S Setting S O F T W A R E U P C O M M U N I C A T I O N S 4.3 Setting up Communications You can communicate with the PM130 PLUS via a PC RS-232 serial port or through the Internet. To configure communications with the PM130 PLUS: 1. Select Configuration from the Tools menu. Under the Communication group on the Instrument Setup tab, select the type of connection for your device. 2. Set the device communication address you assigned to the PM130 PLUS port.
Chapter 4 Using P A S Setting S O F T W A R E U P C O M M U N I C A T I O N S Figure 4-3: Protocol Setup Dialog Box 2. In the Protocol box, select the same communications protocol as you have set in your meter. 3. In the Response Timeout box, define the maximum time that PAS should wait for the meter response before announcing a failure. 4.
Chapter 4 Using P A S S O F T W A R E Setting U P T H E M E T E R Figure 4-4: Configuration Dialog Box – Connection Tab 6. In the Retries box, specify the number of retries PAS will use to receive a response from the meter if communications fail. 7. Click OK. 4.4 Setting Up the Meter Preparing Setups for the Meter PAS allows you to prepare setup data for your meter off-line without the need to have it connected to your PC. To prepare a setup for your meter: 1.
Chapter 4 Using P A S Setting S O F T W A R E U P T H E M E T E R To copy a setup from another site’s database: 1. Click Open. 2. Select the desired source site database. 3. Click OK. The opened setup is copied to your dialog window. 4. Click the Save as… button. 5. Select the target database from the file pane. 6. Click OK. To copy all setups from one site database to another site's database: 1.
Chapter 4 Using P A S S O F T W A R E Authorization 3. Click on the tab of the setup you want to read from the meter. As the dialog box opens, PAS retrieves and displays the present setup data from the meter. Click Receive if you wish to retrieve the meter setup once again. 4. To store the setup to the meter site database, click Save As, and then click OK. Batch Upload To upload all setups from the device to the site database at once: 1. Check the On-line button on the toolbar. 2.
Chapter 5 Configuring T H E P M 1 3 0 Configuring Chapter 5 PLUS P L U S C O M M U N I C A T I O N S Configuring the PM130 This chapter describes how to configure different options in your meter from the front panel display or via PAS. 5.1 Configuring Communications Setting Up Serial Communication Ports Using the Front Display Select Prt1 for COM1 or Prt2 for COM2 from the main menu.
Chapter 5 Configuring T H E P M 1 3 0 Configuring P L U S C O M M U N I C A T I O N S See Table 14 below for available communication options.
Chapter 5 Configuring T H E P M 1 3 0 Configuring P L U S C O M M U N I C A T I O N S Using PAS Select Communications Setup from the Meter Setup menu, and then click on the Network Setup tab. Figure 5-2: Communication Setup Dialog Box – Network Setup Tab The table below lists available network options. Table 15: Ethernet Setup Options Display Label 66 Parameter Options Default A Device IP Address 192.168.0.203 - Network Subnet Mask 255.255.255.
Chapter 5 Configuring T H E P M 1 3 0 Configuring P L U S C O M M U N I C A T I O N S NOTES 1. The meter provides the permanent Modbus TCP server on port 502. 2. Selecting the DNP3 TCP service port launches the second DNP3 TCP server allowing simultaneous connections on both TCP ports. Selecting the Modbus TCP port disables the DNP3 TCP server. The TCP service port can also be changed trough the COM2 serial port setup.
Chapter 5 Configuring T H E P M 1 3 0 Configuring P L U S C O M M U N I C A T I O N S Table 16: GPRS Setup Options Parameter Access Point Name (APN) Default internetg Description The mobile network APN name User name Username (if required) Password Password (if required) 2. Configure your mobile network APN, username and password. Consult your network operator regarding proper network settings. Leave the username and password fields blank if network authorization is not required. 3.
Chapter 5 Configuring T H E P M 1 3 0 P L U S Configuring C O M M U N I C A T I O N S Figure 5-4: eXpertPower Client Setup Tab The following table lists available options. Refer to your eXpertPower service provider for the correct network settings. Table 17: eXpertPower Client Setup Options Parameter Options XPW Server IP Address Default Description 207.232.60.
Chapter 5 Configuring T H E P M 1 3 0 Configuring P L U S C O M M U N I C A T I O N S Figure 5-5: TCP Notification Client Setup Tab The following table lists available client options. Table 18: TCP Notification Client Setup Options Parameter Client Enabled Options NO, YES Server IP Address Default Description NO Enables operations of the notification client 192.168.0.
Chapter 5 Configuring T H E P M 1 3 0 P L U S General M E T E R S E T U P 5.2 General Meter Setup Basic Meter Setup This section describes how to configure the PM130 PLUS for your particular environment and application. Before operating your meter, provide the device with basic information about your electrical network. Using the Front Display Select the baSc entry from the main menu.
Chapter 5 Configuring T H E P M 1 3 0 General Display Label P L U S M E T E R Parameter S E T U P Options Default Description nd.P The number of 1-15 blocks in the sliding demand window E, EH 1 The number of blocks to be averaged for sliding window demands Ad.P Volt/Ampere Demand Period 900 sec The length of the demand period for ampere and volt demand calculations 0-1800 sec 1. Always specify the wiring mode and transformer ratings prior to setting up setpoints and analog outputs. 2.
Chapter 5 Configuring T H E P M 1 3 0 P L U S General M E T E R S E T U P Wiring Mode 3LL3 Description 4-wire Wye using 2 PTs (2½ element), line-to-line voltage readings 3BLN3 3-wire Broken Delta using 2 PTs, 3 CTs (2½ element), line-to-neutral voltage readings 3BLL3 3-wire Broken Delta using 2 PTs, 3 CTs (2½ element), line-to-line voltage readings In 4LN3, 3LN3 and 3BLN3 wiring modes, Min/Max volts, volt demands and voltage harmonics represent line-to-neutral voltages; otherwise, they will
Chapter 5 Configuring T H E P M 1 3 0 General Display Label P L U S M E T E R Parameter S E T U P Options Default Description rESL Device Resolution Lo = Low Hi = High Low The voltage, current and power resolution on the front display (see Measurement Units in Chapter 3) and in communications (see communication guides) U.ScL Volts Scale, V 60-828 V 144 V The maximum voltage scale allowed, in secondary volts. See Data Scales in Appendix F C.ScL Amps Scale, A 1.0-10.
Chapter 5 Configuring T H E P M 1 3 0 P L U S General M E T E R S E T U P for volts, and THD < 10% for currents. In networks with high harmonics, the second method is preferable.
Chapter 5 Configuring T H E P M 1 3 0 General P L U S M E T E R S E T U P Figure 5-8: General Setup Dialog Box – Digital Inputs Dialog Box The available options are shown in Table 22. Table 22: Digital Input Options Display Label Parameter Options Default Description Input Polarity NORMAL INVERTING NORMAL For the normal polarity, the open to closed transition is considered closed. For the inverting polarity, the closed to open transition is considered closed PuLS Pulse Input Mode PLS.
Chapter 5 Configuring T H E P M 1 3 0 P L U S General M E T E R S E T U P Configuring Relay Outputs The PM130 PLUS can be provided with two optional relay outputs. Each relay can be operated either locally from the alarm/control setpoints in response to an event or by a remote command sent through communications. It can also be linked to an internal pulse source to produce energy pulses. Using the Front Display Select reL from the main menu.
Chapter 5 Configuring T H E P M 1 3 0 General P L U S M E T E R S E T U P Figure 5-9: General Setup Dialog Box – Relay Outputs Tab The available relay outputs options are shown in Table 23. Table 23: Relay Output Options 78 Display Label Parameter Options Default Description tYPE Operation mode UnLt = UNLATCHED Ltch = LATCHED PLS.A = PULSE PLS.
Chapter 5 Configuring T H E P M 1 3 0 P L U S General Display Label Parameter PuLS Pulse width Src Unit M E T E R Options 20-1000 ms S E T U P Default Description 100 ms The actual pulse width is a multiple of the 1-cycle time rounded to the nearest bigger value. The pause time between pulses is equal to the pulse width. Pulse source NONE Ac.Ei = kWh IMP Ac.EE = kWh EXP rE.Ei = kvarh IMP rE.EE = kvarh EXP rE.Et = kvarh TOT AP.
Chapter 5 Configuring T H E P M 1 3 0 General 1. P L U S M E T E R S E T U P Press the ENTER button when the middle window is highlighted. You are returned to the upper window and can select another analog output or exit the menu. 2. Press ESC to exit the menu. See Table 24 for the available analog output options. Using PAS Select General Setup from the Meter Setup menu, and then click on the Analog Outputs tab.
Chapter 5 Configuring T H E P M 1 3 0 P L U S General Display Label Option Hi Full scale M E T E R S E T U P Range Description Defines the high engineering scale (in primary units) for the analog output corresponding to a highest output current (1 or 20 mA) When you select an output parameter for the analog output channel, the default engineering scales are set automatically. They correspond to the maximum available scales.
Chapter 5 Configuring T H E P M 1 3 0 General P L U S M E T E R S E T U P ±2 mA: set the 1 mA scale to ½ of the required full-scale output for both uni-directional and bi-directional parameters. For example, to provide the 0 to 2 mA output current range for Volts measured by the meter in the range of 0 to 120V, set the 1 mA scale to 60V; then the 120V reading will be scaled to 2 mA.
Chapter 5 Configuring T H E P M 1 3 0 P L U S General Display Label M E T E R Option SCAL Multiplier - Counter Value S E T U P Range 1-9999 Default 1 Description The value added to the counter when a pulse is detected on the pulse source input Displays the present counter contents Figure 5-11: General Setup Dialog Box – Pulse/Event Counters You can preset a counter to a required value or clear it without affecting the counter setup. To preset or clear a counter: 1.
Chapter 5 Configuring T H E P M 1 3 0 General P L U S M E T E R S E T U P The logical controller provides very fast response to events. The scan time for all setpoints is 1 cycle time (16.6 ms at 60Hz and 20 ms at 50/400 Hz). Using the Front Display Select SEtP from the main menu to enter the setup menu. Use the UP and DOWN arrow buttons to scroll to the required setpoint. To select a setpoint parameter: 1. Press the SELECT button to activate the middle window. 2.
Chapter 5 Configuring T H E P M 1 3 0 P L U S General Display Label Option M E T E R S E T U P Range Description OFF Release limit The threshold (in primary units) at which the conditional expression would be evaluated to false. Defines the hysteresis for analog triggers. Not applicable for digital triggers. On d Operate delay 0.1-999.9 sec The time delay before operation when the operate conditions are fulfilled OFFd Release delay 0.1-999.
Chapter 5 Configuring T H E P M 1 3 0 General P L U S M E T E R S E T U P In the PM130, the binary events are level-sensitive events. An event is asserted all the time while the corresponding condition exists. Delaying Setpoint Operations Two optional delays can be added to each setpoint to extend monitoring triggers for a longer time before reaching a decision on whether the expected event occurred or not.
Chapter 5 Configuring T H E P M 1 3 0 P L U S General M E T E R S E T U P Table 27: Display Setup Options Display Label Parameter Options Default Description UPdt Display update rate 0.1-10.
Chapter 5 Configuring T H E P M 1 3 0 General P L U S M E T E R S E T U P Figure 5-13: General Setup Dialog Box – Local Settings Tab The available options are described in Table 28. Table 28: Local Time Options Display Label 88 Parameter Options Default, or country name Default Description - Country Default Defines calendar setting. The default setting stands for the U.S.A.
Chapter 5 Configuring T H E P M 1 3 0 Configuring P L U S M E T E R S E C U R I T Y Daylight Saving Time When the daylight saving time is enabled, the meter automatically advances the device clock by one hour when daylight saving time begins and puts the clock back one hour when it ends. The default daylight saving time change points are preset for the U.S.A. The daylight saving time option is disabled in the PM130 by default.
Chapter 5 Configuring T H E P M 1 3 0 Configuring P L U S M E T E R S E C U R I T Y When password protection is enabled, you are not able to change the device settings through the display or communications unless you provide a correct password. If you cannot provide a proper password, contact your local distributor for the appropriate password to override password protection.
Chapter 5 Configuring T H E P M 1 3 0 P L U S Configuring B I L L I N G / T O U 5.4 Configuring Billing/TOU The TOU battery-backed clock unit is highly recommended in case of using time-scheduled tariff rates, otherwise a long power outage may cause the meter clock to lose time so your tariff counters would not comply with the calendar schedule.
Chapter 5 Configuring T H E P M 1 3 0 Configuring P L U S B I L L I N G / T O U Figure 5-15: Energy/TOU Setup Dialog Box – Billing/TOU Registers tab 2. Configure the register options according to the valid parameters shown in Table 29.
Chapter 5 Configuring T H E P M 1 3 0 P L U S Configuring Parameter Options B I L L I N G / T O U Default Description Multiplier 0.001 to 100.000 1.000 The multiplication factor for the energy source. Unchangeable for internal energy sources. Target Reg#1- Reg#4 None Defines the target billing register for the energy source. It is set automatically.
Chapter 5 Configuring T H E P M 1 3 0 Configuring P L U S B I L L I N G / T O U Configuring the Season Tariff Schedule To configure your season tariff schedule, select Energy/TOU from the Meter Setup menu, and then click on the TOU Calendar tab. Figure 5-17: TOU Calendar Setup Dialog Box – TOU Calendar Tab The meter TOU calendar allows you to configure any tariff schedule based on any possible utility regulation.
Chapter 5 Configuring T H E P M 1 3 0 P L U S Configuring B I L L I N G / T O U before allocating the remaining days to another daily schedule without specified month days, so it would be checked first for a match. The above picture shows a typical single-season tariff schedule with two daily tariff profiles configured for working days, and weekends and the designated U.S.A. holidays.
Chapter 5 Configuring T H E P M 1 3 0 P L U S Configuring R E C O R D E R S 5.5 Configuring Recorders The PM130E/EH PLUS has a 58-KByte onboard non-volatile memory for data and event recording. The memory is fully configurable and can be freely partitioned between log files.
Chapter 5 Configuring T H E P M 1 3 0 P L U S Configuring R E C O R D E R S 1. Double click on the file you want to change. 2. Select desired parameters for your log. 3. Click OK. For your reference, the record size and the number of records available for your file are reported in the dialog box. To delete an existing file partition: 1. Click on Delete. 2. Click OK. NOTES 1.
Chapter 5 Configuring T H E P M 1 3 0 Configuring No. 17 File Data log #16 Size, Bytes 8640 P L U S R E C O R D E R S Channels Number of Records Number of Events 4 90 90 Factory-set Configuration Daily billing/TOU profile for 90 days, 4 registers, totals + 3 tariffs Configuring the Event Recorder To configure the Event log file: 1. Double click on the Event Log file partition with the left mouse button. 2. Select a desired file type for your file. 3.
Chapter 5 Configuring T H E P M 1 3 0 P L U S Configuring R E C O R D E R S 2. Select a partition type for your file. 3. Select the number of parameters you want to be recorded in the file records. 4. Select the maximum number of records you want to be recorded in the file. 5. Click OK, and then send your new setup to the meter, or save to the device database. To define the contents of the file: 1.
Chapter 5 Configuring T H E P M 1 3 0 Configuring P L U S R E C O R D E R S 2. Configure the list of parameters to be recorded in a log file. You are not allowed to select more parameters than you defined when configuring your file. Refer to Appendix D for a list of available parameters. 3.
Chapter 5 Configuring T H E P M 1 3 0 P L U S Configuring R E C O R D E R S Factory Preset Data Log Files Conventional Data Log #1 Data log #1 is factory preset for 15-min periodic recording of the standard energy and demand quantities. You can freely change the list of recorded parameters and the file update rate. The default list of parameters is shown in the following table. No.
Chapter 5 Configuring T H E Configuring C P M 1 3 0 P L U S O M M U N I C A T I O N P R O T O C O L S 5.6 Configuring Communication Protocols This section describes how to customize protocol options for use with your application software. Configuring Modbus Modbus Point Mapping The PM130 PLUS provides 120 user assignable registers at addresses 0 to 119.
Chapter 5 Configuring T H E P Configuring M 1 3 0 P L U S C O M M U N I C A T I O N P R O T O C O L S Changing 32-bit Register Format The PM130 PLUS allows you to read 32-bit Modbus analog registers, energy counters and binary counters either in integer format, or in IEEE single precision floating point format. The 32-bit Modbus registers are factory-set to integer format. To change the register format: 1. Select Protocol Setup from the Meter Setup menu, and click on the Modbus Registers tab. 2.
Chapter 5 Configuring T H E Configuring C P M 1 3 0 P L U S O M M U N I C A T I O N P R O T O C O L S Table 30: DNP Options Parameter Options Default Description Binary Inputs (BI) Binary Input Object Single-bit With Status Single-bit The default BI object variation for requests with qualifier code 06 when no specific variation is requested Analog Input Object 32-bit 32-bit–Flag 16-bit 16-bit–Flag Binary Counter Object 32-bit+Flag 32-bit–Flag 16-bit+Flag 16-bit–Flag 16-bit AI Scaling Disa
Chapter 5 Configuring T H E P Configuring M 1 3 0 P L U S C O M M U N I C A T I O N P R O T O C O L S Configuring DNP Class 0 Responses The most common method of getting static object information from the meter via DNP is to issue a read Class 0 request. The PM130 allows you to configure the Class 0 response by assigning ranges of points to be polled via Class 0 requests. To view or build a DNP Class 0 response message: 1.
Chapter 6 Device C O N T R O L A N D Resetting A C C U M U L A T O R S , U P G R A D I N G M A X I M U M V A L U E S A N D F I L E S Chapter 6 Device Control and Upgrading This section describes operations on the meter you can perform from the front display or via PAS. To access device control options from PAS, you should have your meter online. 6.1 Resetting Accumulators, Maximum Values and Files Using the Front Display Select the rst entry from the main menu.
Chapter 6 Device C O N T R O L A N D Updating U P G R A D I N G T H E M E T E R C L O C K Figure 6-1: Reset Dialog To reset the desired values or files: 1. Click on the corresponding button, and then confirm your command. 2. If an entry has more than one target, you are allowed to select targets to reset. 3. Check the corresponding boxes, and then click OK. Figure 6-2: Reset Maximum Demands Dialog Box 6.
Chapter 6 Device C O N T R O L A N D Updating U P G R A D I N G T H E M E T E R C L O C K To change the time or date: 1. Use the UP and DOWN arrow buttons to select a setup option 2. Highlight an item you want to change by pressing briefly the SELECT button. 3. When you access the time setup display, the hours and minutes are frozen allowing you to adjust the time. 4. Adjust the selected item with the UP and DOWN arrow buttons. 5.
Chapter 6 Device C O N T R O L A N D Viewing A N D C L E A U P G R A D I N G R I N G D E V I C E D I A G N O S T I C S Figure 6-3: Real Time Clock Window To synchronize the meter clock with the PC clock, click Set. 6.3 Viewing and Clearing Device Diagnostics Using the Front Display See Diagnostics Display in Chapter 3 on how to view and clear device diagnostics from the front display.
Chapter 6 Device Viewing C C O N T R O L A N D U P G R A D I N G O M M U N I C A T I O N S T A T U S A N D S T A T I S T I C S 6.4 Viewing Communication Status and Statistics Ensure that the On-line button on the PAS toolbar is checked, select Device Control from the Monitor menu, and then click on the Communications tab.
Chapter 6 Device C O N T R O L A N D Upgrading U P G R A D I N G D E V I C E F I R M W A R E Figure 6-6: Device Control Dialog Box – Remote Relay Control Tab To send a remote command to a relay: 1. Select a desired command in the Relay Command box for a relay: OPERATE – to operate a relay RELEASE – to remove your remote command, or to release a latched relay 2. Click Send. 6.6 Upgrading Device Firmware Your meter has upgradeable firmware.
Chapter 6 Device C O N T R O L A N D Upgrading 112 U P G R A D I N G D E V I C E F I R M W A R E 4. Point to the firmware upgrade file for your meter, click Open, and then confirm upgrading the meter. 5. You are asked for the password regardless of the password protection setting in your meter. Type the meter password, and click OK. If you did not change the password in the meter, enter the default password 0. 6. Wait until PAS completes upgrading your device.
Chapter 7 Monitoring Viewing M E T E R S Chapter 7 R E A L - T I M E D A T A Monitoring Meters 7.1 Viewing Real-time Data Real-time data can be continuously retrieved from your devices and updated on the screen at the rate you defined in the Instrument Setup. To get real-time data from your meter: 1. Ensure that the On-line button on the PAS toolbar is checked. 2. Select the device site from the list box on the PAS toolbar. 3.
Chapter 7 Monitoring M E T E R S Viewing R E A L - T I M E D A T A window is linked to the current site and does not change if you select another site in the site list. You can view acquired data in a tabular form or in a graphical form as a data trend. Organizing Data Sets PAS supports 33 programmable data sets with up to 40 data parameters. Set #0 is intended for simple meters, which have a limited number of parameters, and is not recommended for the use with the PM130 PLUS.
Chapter 7 Monitoring M E T E R S Viewing R E A L - T I M E M I N / M A X L O G Viewing Data Trend To view a data trend, click on the button on the local toolbar. To change the time range for your graph, click on the button on the local toolbar, and then select the desired date and time range. See Working with Graphic Windows in Chapter 9 for more information on working with graphs.
Chapter 7 Monitoring Viewing M E T E R S 3. Ensure that the On-line button checked. 4. Click on the Poll button R E A L - T I M E W A V E F O R M S on the PAS toolbar is . PAS supports 9 programmable data sets that you can organize as you wish. To build your data sets, select MinMax Data Sets from the Monitor menu or click on the button on the local toolbar. See Working with Tables in Chapter 9 for more information on working with tables. 7.
Chapter 7 Monitoring M E T E R S Viewing R E A L - T I M E W A V E F O R M S Figure 7-2: RT Waveform Monitor Window Viewing a Frequency Plot Click on the button to view a cycle-by-cycle frequency plot for the sampled voltage waveforms. Viewing a Harmonic Spectrum Click on the button to view a spectrum chart for the selected waveform channel. PAS provides voltage, current, active power and reactive power spectrum charts.
Chapter 7 Monitoring M E T E R S Viewing R E A L - T I M E H A R M O N I C S P E C T R U M the Symmetrical components box on the Channels tab, and then click OK. Viewing Phase-to-phase Voltages PAS can transform phase-to-neutral voltage waveforms in configurations with a neutral into phase-to-phase waveforms allowing you to view the waveshape, angle relationships and harmonics of the phase-to-phase voltages. Click on the button on the waveform window toolbar.
Chapter 7 Monitoring Viewing M E T E R S R E A L - T I M E H A R M O N I C S P E C T R U M spectrum to let you view a shape of the voltage and current waveforms in your network. Viewing a Spectrum Chart Click on the button to view a spectrum chart for the selected channel. To change a channel, click on the window with the right mouse button, select Channels..., check the channel you want displayed, and then click OK. PAS provides voltage, current, active power and reactive power spectrum charts.
Chapter 7 Monitoring M E T E R S Viewing R E A L - T I M E H A R M O N I C S P E C T R U M The spectrum table shows voltage, current, active power and reactive power harmonic components both in percent of the fundamental and in natural units, and harmonic phase angles. To change a phase, click on the window with the right mouse button, select Options..., check the phase you want displayed, and then click OK.
Chapter 7 Monitoring M E T E R S Viewing R E A L - T I M E H A R M O N I C S P E C T R U M Figure 7-6: RT Harmonic Monitor – Synthesized Waveforms PM130 PLUS Powermeter Series 121
Chapter 8 Retrieving A N D S T O R I N G Uploading Chapter 8 F I L E S F I L E S O N D E M A N D Retrieving and Storing Files PAS allows you to retrieve recorded events and data from your meters and to save them to files on your PC in the Microsoft Access database format. Historical data can be uploaded on demand any time you need it, or periodically through the Upload Scheduler that retrieves data automatically on a predefined schedule, for example, daily, weekly or monthly.
Chapter 8 Retrieving A N D S T O R I N G Using T H E F I L E S U P L O A D S C H E D U L E R 8.2 Using the Upload Scheduler To setup the Upload Scheduler: 1. Select Upload Scheduler from the Logs menu. Figure 8-1: Upload Scheduler Setup Dialog Box 2. Click Add Site, point to the site database for which you want to organize the schedule, and then click OK. 3.
Chapter 8 Retrieving A N D Using S T O R I N G T H E F I L E S U P L O A D S C H E D U L E R 5. Select a daily, weekly or monthly schedule, and adjust the start time. If you wish to upload data periodically in predefined intervals, click on Periodic and define the time period in hours and minutes. 6. Select the number of attempts to upload data in the event of temporary communication problems or unavailability of your device, and the delay between attempts in minutes and seconds. 7.
Chapter 8 Retrieving A N D S T O R I N G Viewing F I L E S F I L E S O N - L I N E Reviewing Upload Problems When the Upload Scheduler fails to retrieve data from the device, or some data is missing, or another problem occurs, it puts an error message to the log file. To review this file, select System Log from the View menu. 8.3 Viewing Files On-line Sometimes, it is useful to review a particular piece of historical data online at the time you expect new events to appear in the log.
Chapter 8 Retrieving A N D S T O R I N G Exporting F I L E S F I L E S 3. Select a folder where you want to store your exported files, type a file name that identifies your files, select a file output format, and then click on the Save button. 4. The PQDIF files are commonly recorded in compressed format. If you do not want your files to be compressed, uncheck the Compress box before saving the file. In COMTRADE format, each waveform event is recorded into a separate file.
Chapter 8 Retrieving A N D S T O R I N G F I L E S Archiving F I L E S Exporting Files in Excel Format PAS allows you to convert data tables into the Microsoft Excel workbook format, either manually, or automatically while retrieving data from your meters via the Upload Scheduler. To store files in Excel format, follow instructions in the previous section and select Excel Workbook as the output file format.
Chapter 9 Viewing Operations F I L E S Chapter 9 W I T H F I L E S Viewing Files 9.1 Operations with Files Files you read from the meters are stored in one or in a number of tables in the meter database. Sections of multi-section files like energy load profiles are stored in multiple tables – each file section in a separate database table. Opening a Database Table To open a database table: 1. Click on the Open button on the PAS toolbar, or select Open... from the File menu. 2.
Chapter 9 Viewing Viewing F I L E S 2. Select the preferred timestamp format. 3. Click OK. O P T I O N S Working with Tables Selecting Font and Grid To change the table font or a type of the grid lines: 1. Click with right mouse button on the table, select Options and click on the Table tab. 2. Select the font type and size and how you wish the table grid to be shown. 3. Click OK. Selecting Primary and Secondary Units Voltages and currents can be displayed in primary or secondary units.
Chapter 9 Viewing F I L E S Viewing O P T I O N S Selecting Primary and Secondary Units Voltages and currents can be displayed in primary or secondary units. To change units, click on the table with the right mouse button, select Options, select the desired units for voltages and currents, and then click OK. Selecting the Time Axis In waveform views, the horizontal axis can be displayed either in absolute time with date and time stamps, or in milliseconds relatively to the beginning of a waveform.
Chapter 9 Viewing Viewing F I L E S T H E E V E N T L O G Using a Zoom You can use a horizontal and, for waveforms, also a vertical, zoom to change size of your graph. Use the buttons on your local toolbar to zoom in and zoom out. One click gives you a 100-percent horizontal or 50-percent vertical zoom. Two buttons representing magnifying glasses give you a proportional zoom in both directions.
Chapter 9 Viewing Viewing F I L E S T H E D A T A L O G Figure 9-1: Event Log Window See Working with Tables for more information on viewing options. Filtering and Sorting Events You can use filtering to find and work with a subset of events that meet the criteria you specify. Click on the Filter button , or click on the report window with the right mouse button and select Filter.... Check the causes of events you want to display, and then click OK.
Chapter 9 Viewing Viewing F I L E S T H E D A T A L O G Figure 9-2: Data Log Window Viewing Data Trend To view data in a graphical form, click on the Data Trend the local toolbar. button on To change the time range for your graph, click on the Time Range button on the local toolbar, and then select the desired date and time range.
Appendix A Technical Specifications Appendix A A.1 Technical Specifications Environmental Conditions Operating temperature: -30°C to 60°C (-22°F to 140°F) Storage temperature: -40°C to 85°C (-40°F to 185°F) Humidity: 0 to 95% non-condensing A.2 Construction Dimensions see Figure 2-1 Weight: 0.70 kg (1.54 lb.) Materials Case enclosure: plastic PC/ABS blend Front panel: plastic PC PCB: FR4 (UL94-V0) Terminals: PBT (UL94-V0) Connectors-Plug-in type: Polyamide PA6.
Appendix A Technical Specifications A.4 Input Ratings Voltage Inputs Operating range: 690VAC line-to-line, 400VAC line-to-neutral Direct input and input via PT (up to 828VAC line-to-line, up to 480VAC lineto-neutral) Input impedance: 1000 k Burden for 400V: < 0.4 VA Burden for 120V: < 0.04 VA Over-voltage withstands: 1000 VAC continuous, 2000 VAC for 1 second Wire size: up to 12 AWG (up to 3.5mm2) Current Inputs (via CT) Wire size: 12 AWG (up to 3.
Appendix A Technical Specifications Release time: 0.25 ms max. Update time: 1 cycle Connector type: removable, 4 pins. Wire size: 14 AWG (up to 1.5 mm2) A.6 Optional Digital Inputs 4 Digital Inputs Dry Contacts, internally wetted @ 24VDC (DI/DO Optional module) Sensitivity: Open @ input resistance >100 k, Closed @ Input resistance < 100 Galvanic isolation: 3750 VAC 1 min Internal power supply: 24VDC Scan time: 1 ms Connector type: removable, 5 pins. Wire size: 14 AWG (up to 1.5 mm2) A.
Appendix A Technical Specifications Number of simultaneous connections: 4 (2 Modbus/TCP + 2 DNP3/TCP). Connector type: RJ45 modular. Profibus DP (IEC 61158) RS-485 optically isolated Profibus interface. Connector type: removable, 5 pins. Baud rate: 9600 bit/s – 12 Mbit/s (auto detection). 32 bytes input, 32 bytes output. Supported protocols: PROFIBUS. RS-232/422-485 Port RS-232 or RS-422/485 optically isolated port Isolation: 3000 VAC 1 min Baud rate: up to 115.2 kbps.
Appendix A Technical Specifications IEC 61000-4-6 level 3: Conducted Radio Frequency IEC 61000-4-8: Power Frequency Magnetic Field Meets ANSI/IEEE C37.90.1: Fast Transient SWC Electromagnetic Emission: Comply with IEC 61000-6-4: Radiated/Conducted class A Comply with IEC CISPR 22: Radiated/Conducted class A Safety/Construction: UL File no. E236895 Meets IEC 61010-1: 2006 AC and Impulse Insulation: Comply with IEC 62052-11: 2500 VAC during 1 minute 6KV/500Ω @ 1.
Appendix A Technical Specifications A.12 Measurement Specifications Table 33: Measurement Specifications Parameters Parameter Full Scale @ Input Range Accuracy % Reading % FS Range Conditions Voltage 120VxPT @ 120V 400VxPT @ 690V 0.2 0.02 10% to 120% FS 0 to 1,150,000 V Starting voltage 1.5-5.0% FS (selectable) Line current CT 0.2 0.02 For In 1% to For In 5% to 0 to 50,000 A Starting current 0.1% FS Active power 0.36PTCT @ 120V 1.2PTCT @ 690V 0.3 0.02 |PF| 0.
Appendix A Technical Specifications 140 2. Specifications assume: voltage and current waveforms with THD 5% for kvar, kVA and PF, and reference operating temperature 20C - 26C. 3. Measurement error is typically less than the maximum error indicated.
Appendix B A N A L O G O U T P U T Appendix B P A R A M E T E R S Analog Output Parameters The following table lists parameters that can be provided on the meter’s analog outputs. Table 34: Analog Output Parameters Display Code Designation Description none NONE None (output disabled) rt.U1 V1/12 RT 1 V1/V12 Voltage rt.U2 V2/23 RT 1 V2/V23 Voltage rt.U3 V3/31 RT 1 V3/V31 Voltage rt.U12 V12 RT V12 Voltage rt.U23 V23 RT V23 Voltage rt.U31 V31 RT V31 Voltage rt.
Appendix B Analog Output P A R A M E T E R S Display Code Description kvar IMP ACD Accumulated kvar import demand Acd.q.E kvar EXP ACD Accumulated kvar export demand Acd.S kVA ACD Accumulated kVA demand 1 142 Designation Acd.q.i In 4LN3, 3LN3 and 3BLN3 wiring modes, the voltages will be line-to-neutral; for any other wiring mode, they will be line-to-line voltages.
Appendix C S E T P O I N T T R I G G E R S Appendix C Actions A N D A C T I O N S Setpoint Triggers and Table 35: Setpoint Triggers Display Code Designation Description nonE NONE None (condition is not active) S1.On STAT INP #1 ON Status input #1 ON S2.On STAT INP #2 ON Status input #2 ON S3.On STAT INP #3 ON Status input #3 ON S4.On STAT INP #4 ON Status input #4 ON S1.OFF STAT INP #1 OFF Status input #1 OFF S2.OFF STAT INP #2 OFF Status input #2 OFF S3.
Appendix C Setpoint Triggers A N D Display Code A C T I O N S Designation Description 1-Sec Total Values A.Hi.P.i HI kW IMP AVR High total kW import A.Hi.P.E HI kW EXP AVR High total kW export A.Hi.q.i HI kvar IMP AVR High total kvar import A.Hi.q.E HI kvar EXP AVR High total kvar export A.Hi. S HI kVA AVR High total kVA A.PF.LG HI PF LAG AVR Low total PF Lag A.PF.Ld HI PF LEAD AVR Low total PF Lead 1-Sec Auxiliary Values A.nEU.C HI In AVR High neutral current A.Hi.
Appendix C S E T P O I N T T R I G G E R S Display Code A N D Designation A C T I O N S Description In.Cn.2 INC CNT #2 Increment counter #2 In.Cn.3 INC CNT #3 Increment counter #3 In.Cn.4 INC CNT #4 Increment counter #4 ti.Cn.1 TIME CNT #1 Count operation time using counter #1 ti.Cn.2 TIME CNT #2 Count operation time using counter #2 ti.Cn.3 TIME CNT #3 Count operation time using counter #3 ti.Cn.
Appendix D Parameters for D A T A M O N I T O R I N G A N D L O G G I N G Appendix D Parameters for Data Monitoring and Logging The following table lists parameters measured by the meter that are available for monitoring through communications and for recording to a data log file. The left column shows data abbreviations used in PAS. Parameter groups are highlighted in bold.
Appendix D P A R A M E T E R S F O R D A T A M O N I T O R I N G Designation A N D Description I3 TDD I3 Current TDD V12 V12 Voltage V23 V23 Voltage V31 V31 Voltage RT TOTAL 1-Cycle Total Values kW Total kW kvar Total kvar kVA Total kVA PF Total PF PF LAG Total PF lag PF LEAD Total PF lead kW IMP Total kW import kW EXP Total kW export kvar IMP Total kvar import kvar EXP Total kvar export V AVG 3-phase average L-N/L-L voltage V LL AVG 3-phase average L-L voltage I
Appendix D Parameters for D A T A M O N I T O R I N G A N D L O G G I N G Designation 148 Description I3 KF I3 K-Factor I1 TDD I1 Current TDD I2 TDD I2 Current TDD I3 TDD I3 Current TDD V12 V12 Voltage V23 V23 Voltage V31 V31 Voltage AVR TOTAL 1-Second Total Values kW Total kW kvar Total kvar kVA Total kVA PF Total PF PF LAG Total PF lag PF LEAD Total PF lead kW IMP Total kW import kW EXP Total kW export kvar IMP Total kvar import kvar EXP Total kvar export V AVG
Appendix D P A R A M E T E R S F O R D A T A M O N I T O R I N G Designation A N D L O G G I N G Description kvar IMP SD kvar import sliding window demand kVA SD kVA sliding window demand kW IMP ACD kW import accumulated demand kvar IMP ACD kvar import accumulated demand kVA ACD kVA accumulated demand kW IMP PRD kW import predicted sliding window demand kvar IMP PRD kvar import predicted sliding window demand kVA PRD kVA predicted sliding window demand PF IMP@kVA DMD PF (import)
Appendix D Parameters for D A T A M O N I T O R I N G A N D L O G G I N G Designation 150 Description kVAh L1 kVAh total L1 kVAh L2 kVAh total L2 kVAh L3 kVAh total L3 %HD V1 V1/V12 Harmonic Distortions EH 1 V1 %HD01 H01 Harmonic distortion V1 %HD02 H02 Harmonic distortion … ... V1 %HD40 H40 Harmonic distortion %HD V2 V2/V23 Harmonic Distortions EH 1 V2 %HD01 H01 Harmonic distortion V2 %HD02 H02 Harmonic distortion … ...
Appendix D P A R A M E T E R S F O R D A T A M O N I T O R I N G Designation A N D L O G G I N G Description I1 H02 ANG H02 Harmonic angle … ... I1 H40 ANG H40 Harmonic angle ANG I2 I2 Harmonic Angles EH I2 H01 ANG H01 Harmonic angle I2 H02 ANG H02 Harmonic angle … ... I2 H40 ANG H40 Harmonic angle ANG I3 I3 Harmonic Angles EH I3 H01 ANG H01 Harmonic angle I3 H02 ANG H02 Harmonic angle … ...
Appendix D Parameters for D A T A M O N I T O R I N G A N D L O G G I N G Designation 152 Description MIN AUX Minimum 1-Cycle Auxiliary Values In MIN In Current FREQ MIN Frequency MAX PHASE Maximum 1-Cycle Phase Values V1 MAX V1/V12 Voltage 1 V2 MAX V2/V23 Voltage 1 V3 MAX V3/V31 Voltage 1 I1 MAX I1 Current I2 MAX I2 Current I3 MAX I3 Current MAX TOTAL Maximum 1-Cycle Total Values kW MAX Total kW kvar MAX Total kvar kVA MAX Total kVA PF MAX Total PF MAX AUX Maximum 1-
Appendix D P A R A M E T E R S F O R D A T A M O N I T O R I N G Designation A N D L O G G I N G Description TOU REG2 Billing TOU Energy Register #2 E, EH REG2 TRF1 Tariff #1 register REG2 TRF2 Tariff #2 register … … REG2 TRF8 Tariff #8 register TOU REG3 Billing TOU Energy Register #3 E, EH REG3 TRF1 Tariff #1 register REG3 TRF2 Tariff #2 register … … REG3 TRF8 Tariff #8 register TOU REG4 Billing TOU Energy Register #4 E, EH REG4 TRF1 Tariff #1 register REG4 TRF2 Tariff #
Appendix D Parameters for Short Data Name 154 D A T A M O N I T O R I N G A N D L O G G I N G Long Data Name Description kW IMP ACD kW IMP ACC DMD Accumulated demand kW IMP PRD kW IMP PRD DMD Predicted sliding window demand PF IMP@kVA MD PF IMP@kVA MXDMD PF (import) at maximum kVA demand REG1 ACD SUM REG1 ACC DMD Billing summary (total) register accumulated demand REG1 BD SUM REG1 BLK DMD Billing summary (total) register block demand REG1 SD SUM REG1 SW DMD Billing summary (total)
Appendix E B I L L I N G / T O U Appendix E P R O F I L E L O G F I L E Billing/TOU Profile Log File The following table shows the record structure for the daily billing data profile log file. The second column shows data abbreviations used in the PAS data log reports. Data log file sections are highlighted in bold. Table 38: Daily Billing/TOU Profile Data Log (Data Log #16) Field No.
Appendix E Billing/TOU P R O F I L E L O G F I L E The number of parameters in each section is automatically configured depending on the number of actual tariffs you defined in the TOU Daily Profiles.
Appendix F D A T A S C A L E S Appendix F Data Scales The maximum values for volts, amps and power in the PM130 PLUS setup and in communications are limited by the voltage and current scale settings. See Device Options in Chapter 4 on how to change the voltage and current scales in your meter. The following table shows the meter data scales.
Appendix G Device Diagnostic C O D E S Appendix G Device Diagnostic Codes Table 40: Device Diagnostic Codes Diagnostic Code Diagnostic Message Description Reason 2 dAtA Memory/Data fault Hardware failure 3 rSt Hardware watchdog reset Hardware failure 5 CPU CPU exception Hardware failure 6 runt Run-time software error Hardware failure 7 tout Software watchdog timeout Hardware failure 8 PWr.
Index Index A Accuracy, 136 Active energy, 136 Active power, 136 analog outputs, 15, 32, 70, 77, 79, 138 Apparent energy, 136 Apparent power, 136 Auto Scroll, 43 L Low Resolution Option, 42 M Maximum Demand Load Current, 69 menus, 52 Modbus, 98 B billing, 89 Broken Delta, 25, 29, 71 N notification, 67 O C Open Delta, 25, 27, 28, 71 communication, 57, 62 counters, 80 CT Primary Current, 69 P D Data recorder, 95 daylight saving, 87 Delta, 25 demand, 17, 70 diagnostic, 51, 106 digital inputs, 13, 1