Chapter 5 Setting Up the ETC2002 Configuring Data Server
ETC2002 Network Communicator 45
The following table lists available options.
Parameter Options Default Description
XPW Server IP Address 207.232.60.18 The IP address of the
eXpertPower server
XPW Server Port 0-65535 5001 The TCP service port of the
eXpertPower server
XPW Client Enabled NO, YES NO Enables operations of the
eXpertPower client
Time to Next Session, min
1-99999
The time remaining to the
next connection session
Configuring Data Server
Using HyperTerminal or Telnet
See Data Server in Chapter 3 for information on Data server operations.
To view or change the Data server settings, type datasrv and press Enter.
>datasrv
You will be prompted for the password. The factory-set password is 0 unless
you have changed it in your ETC2002.
Enter password:*
Data Server Configuration Commands
------------------------------------
h - Display this text
p - Server parameters
s [N] - Set address range *
i [N] - Display address range settings *
q - Quit menu
*(N - address range number)
Data server>