Chapter 5 Configuring the EM920
Configuring Communications
EM920 Power Quality and Revenue Meter 71
Parameter Options Default Description
Client Enabled NO, YES NO Enables operations of the
notification client
Server IP Address 192.168.0.3 The IP address of the
notification server
Server Port 0-65535 502 The TCP service port of the
notification server
Message Exchange
Address
0-65535 1000
Connection via Network Ethernet,
GPRS/Modem
Automatically selected
depending on the network
module installed
Client connections are triggered via programmable setpoints.
To send event notifications to a server, configure a setpoint
to respond to desired triggers or to periodic time events and
add the "Send notification" action to the end of the setpoint
actions list (see Using Control Setpoints
).
Setpoint operation events triggered by regular analog and
digital triggers are reported twice - when the event starts and
when it ends, except of the pulsed events and time triggers
that will be reported once.
In case of triggering notifications with events generated by
the PQ and Fault recorders, like the PQ EVENT, FAULT EVENT,
EXTERNAL TRIGGER or FAULT DETECTED triggers, the
recorded power quality or/and corresponding fault events are
reported instead of setpoint-triggered notifications. If regular
triggers are added to the setpoint triggers list, then the
setpoint operation events will also be reported.