Appendix B Setpoint Parameters
EM920 Power Quality and Revenue Meter 201
Appendix B Setpoint Parameters
Setpoint Triggers
For setpoint triggers, see Appendix A Parameters for
Monitoring and Logging.
Setpoint Actions
The available setpoint actions are listed in the following table.
Setpoint Actions
Action Target Description
NONE No action
SET EVENT FLAG 1-8 Set user event flag 1-8
CLEAR EVENT FLAG 1-8 Clear user event flag 1-8
OPERATE RELAY 1-7 Operate relay RO1-RO7
RELEASE RELAY 1-7 Release latched relay RO1-RO7
INCREMENT COUNTER 1-8 Increment counter 1-8
CLEAR COUNTER 1-8 Clear counter 1-8
RESET ALL COUNTERS Clear all counters
RESET DEMANDS ALL Reset all engineering maximum demands
RESET DEMANDS POWER Reset engineering maximum power demands
RESET DEMANDS VOLT/AMP Reset maximum volts and ampere demand
RESET DEMANDS VOLT Reset maximum volt demand registers
RESET DEMANDS AMP Reset maximum ampere demand registers
RESET DEMANDS HRM Reset maximum harmonic demand registers
RESET TOU DEMANDS Reset billing/TOU maximum demands (end of billing period)
CLEAR MIN/MAX LOG Clear Min/Max log
EVENT LOG OPER Event log on setpoint operated
EVENT LOG RELS Event log on setpoint released
EVENT LOG ANY Event log on any setpoint transition
DATA LOG 1-14 Conventional data log 1-14
WAVEFORM LOG 1-2 Waveform Log 1-2
SEND NOTIFICATION Send a notification message to a remote TCP server