Chapter 5 Configuring the EM920
Configuring the EN50160 Recorders
EM920 Power Quality and Revenue Meter 125
The default EN50160 compliance limits are shown in the
picture above. You can change the number of the evaluated
harmonics and interharmonics via the EN50160 Advanced
Setup.
EN50160 Advanced Setup
The EN50160 Advanced Setup allows you to configure the
EN50160 evaluation options in your meter.
To configure the EN50160 evaluation options:
1. Select Memory/Log from the Meter Setup menu, and
then click on the EN50160 Advanced Setup tab.
2. Change the EN50160 evaluation options if required.
3. Download your setup to the device.
The default EN50160 evaluation options set in your device
are shown in the picture below.
The available options are listed in the following table.
Option Range Default Description
EN50160 Compliance Statistics
Evaluation Disabled, Enabled Enabled Enables the EN50160 evaluation
Evaluation Period Daily, Weekly Weekly Defines the EN50160 statistics evaluation
period
First Day of the
Week
Sunday-Saturday Sunday Defines the first day of the week for
statistics evaluated on a weekly basis
EN50160 Harmonics Survey
Evaluation Disabled, Enabled Enabled Enables the harmonics survey log
Evaluation Period Daily, Weekly Weekly Defines the harmonics survey evaluation
period