Instruction Manual
Chapter 5 Configuring the EM720
General Meter Setup
68 EM720 Power Quality and Revenue Meter
General Meter Setup
Basic Meter Setup
The Basic Setup provides the meter with basic information
about your electrical network.
Using the Front Display
Select Basic from the main menu. See Viewing and Changing
Setup Options in Chapter 3 for information on navigating in
menus.
See the table below for available options.
Using Pas
Select General Setup from the Meter Setup menu.
The following table lists available meter configuration options.
Display Label Parameter Options Default Description
Basic Configuration
Wiring Wiring Mode See Table
below
4LN3 The wiring connection of the
device
PT Ratio
PT Ratio
1
1.0-6500.0 1.0 The phase potential
transformer’s primary to
secondary ratio