Chapter 4 Setup Menus 25
Table 4-3 Analog Output Setup Options
Code Option Description
OutP
Output parameter The output parameter for the analog output channel
Lo
Zero scale (0/4 mA) The reading of the parameter corresponding to a zero-
scale current output
Hi
Full scale (1/20 mA) The reading of the parameter corresponding to a full-scale
current output
Table 4-4 Analog Output Parameters
Code Parameter Unit Scale
nonE Output disabled 0
Real-time Measurements
r. U 1
Voltage L1/L12 V/kV 0 to Vmax
r. U 2
Voltage L2/L23 V/kV 0 to Vmax
r. U 3
Voltage L3/L31 V/kV 0 to Vmax
r. C1
Current L1 A 0 to Imax
r. C2
Current L2 A 0 to Imax
r. C3
Current L3 A 0 to Imax
r. P
Total kW kW/MW -Pmax to Pmax
r. q
Total kvar kvar/Mvar -Pmax to Pmax
r. S
Total kVA kVA/MVA 0 to Pmax
r. PF
Total PF -0.000 to 0.000
r. PF.LG
Total PF lag 0 to 1.000
r. PF.Ld
Total PF lead 0 to 1.000
r. Fr
Frequency Hz 0 to 100.00
Average Measurements
A. U 1
Voltage L1/L12 V/kV 0 to Vmax
A. U 2
Voltage L2/L23 V/kV 0 to Vmax
A. U 3
Voltage L3/L31 V/kV 0 to Vmax
A. C1
Current L1 A 0 to Imax
A. C2
Current L2 A 0 to Imax
A. C3
Current L3 A 0 to Imax
A. P
Total kW kW/MW -Pmax to Pmax
A. q
Total kvar kvar/Mvar -Pmax to Pmax
A. S
Total kVA kVA/MVA 0 to Pmax
A. PF
Total PF -0.000 to 0.000
A. PF.LG
Total PF lag 0 to 1.000
A. PF.Ld
Total PF lead 0 to 1.000
A. neU.C
Neutral current A 0 to Imax
A. Fr
Frequency Hz 0 to 100.00
Present Demands
Accd.P
Accumulated kW demand kW/MW 0 to Pmax
Accd.S
Accumulated kVA demand kVA/MVA 0 to Pmax
Imax (20% over-range) = 1.2 × CT primary current [A]
Direct wiring (PT Ratio = 1):