Owner's manual

v
SETUP (see Chapter 4 for full instructions)
Setups can be performed directly on the front panel
or via PComTest communication software.
Press .
Press to activate middle window.
Press to scroll to desired option.
Press to activate lower window.
Press to scroll to desired value.
Press to save selected value.
Basic and Communications Default Setups
Code Parameter Options Description
ConF
Wiring mode
4Ln3
4-wire Wye using 3 PTs (3 element), line to
neutral voltage readings
Pt
PT ratio
1.0
The phase potential transformer ratio
Ct
CT primary current
5
The primary rating of the phase current
transformer, A
d.P
Power demand
period
15
The length of the demand period for power
demand calculations, in minutes. E = external
synchronization
n.dp
Number of power
demand periods
1
The number of demand periods to be averaged
for sliding window demands
1 = block interval demand calculation
A.dP
Ampere/Volt
demand period
900
The length of the demand period for
volt/ampere demand calculations, in seconds
0 = measuring peak current
buF
Averaging buffer
size
8
The number of measurements for RMS sliding
averaging
rSt
Reset
enable/disable
diS
Protects all reset functions, both via the front
panel or communications.
Freq
Nominal frequency
50/, 60
The nominal power utility frequency, Hz
LoAd
Maximum demand
load current
0
The maximum demand load current used in
TDD calculations (0 = CT primary current)
Prot
Communications
protocol
ASCII
ASCII protocol
Addr
Address
0 (ASCII)
Powermeter address
bAud
Baud rate
9600
9600 bps
dAtA
Data format
8n
8 bits, no parity
CPtb
ASCII compatibility
mode
diS
Disables ASCII compatibility mode (For more
information, see ASCII Communications
Protocol Reference Guide)
Port
ASCII
Prot
men
u
option
value
bASc
4L-n
ConF
men
u
option
value
SELECT
CH
G
ENTER
SELECT
SELECT
ENTER