Owner's manual
Appendix: Technical Specifications 51
Measurement Specifications
Accuracy, % Range Display resolution (%Rdg)
Parameter Full scale Rdg FS Conditions @
range
120V×PT
@120V or
400V×PT
@690V
For L-N reading
and for
3OP2/3OP3
wiring
modes
Voltage
208V×PT
@120V or
690V×PT
@690V
For L-L reading
except
3OP2/3OP3
wiring modes
0.25 10% to 120%
FS
0 to 999,000 V Direct wiring (PT=1):
0.1 V
@
0.1V to 999.9 V
Wiring via PTs (PT>1):
0.001 kV
@
0.001kV to 9.999 kV
≤0.1%
@
10.00 kV to 999.0 kV
Starting voltage 1.5% FS
Line current CT PRIMARY CURRENT 0.25 2% to 120%
FS
0 to 9999 A
0.01 A
@
0.01A to 99.99 A
≤0.1%
@
100.0 A to 9999 A
Starting current 0.5% FS
Active power
0.36×PT×CT @ 120V input
1.2×PT×CT @ 690V input
0.5
|PF| ≥ 0.5
-2,000,000 to
+2,000,000 kW
Direct wiring (PT=1):
0.001 kW
@
0.001kW to 9.999 kW
Wiring via PTs (PT>1):
0.001 MW
@
0.001MW to 9.999 MW
≤0.1%
@
10.00 MW to 2000 MW
Reactive power
0.36×PT×CT @ 120V input
1.2×PT×CT @ 690V input
0.5
|PF| ≤ 0.9
-2,000,000 to
+2,000,000
kvar
Direct wiring (PT=1):
0.001 kvar
@
0.001kvar to 9.999 kvar
Wiring via PTs (PT>1):
0.001 Mvar
@
0.001Mvar to 9.999 Mvar
≤0.1%
@
10.00 Mvar to 2000Mvar
Apparent power
0.36×PT×CT @ 120V input
1.2×PT×CT @ 690V input
0.5
|PF| ≥ 0.5
0 to
2,000,000 kVA
Direct wiring (PT=1):
0.001 kVA
@
0.001kVA to 9.999 kVA
Wiring via PTs (PT>1):
0.001 MVA
@
0.001MVA to 9.999 MVA
≤0.1%
@
10.00 MVA to 2000 MVA
Power factor 1 1
|PF| ≥ 0.5,
I ≥ 10% FSI
-0.999 to
+1.000
0.001