Return
3520 24VDC 1.0AMP Regulated and Filtered Power Supply
110-120 VAC
Connector
to power on LED
HOT
NEUT
GND
1 2 3
AC F
Low voltage AC
From transformer
AC
DC
DC
Output
NOTE: This drawing shows the
BPS Series. The PM Series has no
line voltage input, fuse or connector
to power on LED.
2.5 AMP polyswitch breaker
Red
Black
Unconnected
terminal for switch
hookup
Battery Pack
Wiring Notes:
1. Rail, raceway, electric hinge and
pigtail 8-pin connector terminations
and wire colors all match.
2. A fire alarm tie-in is required on fire
rated openings.
3. The fire alarm contact (when
required) must be wired to drop
24VDC power to rail.
In this case, terminate fire alarm
contact between the red (+24VDC)
wire and supply +24VDC output.
Sample Wiring #3 – 59- Electroguard™ Exit Device with Fire Alarm, Keypads and Fail Safe ET
During a fire alarm condition, the contact opens which de-energizes the rail electromagnet and allows immediate
egress. A valid code entry at the 4291 (Inside) keypad shunts the Electroguard™ exit device and allows egress for a
time period programmable at this keypad. A valid code entry at the 4292 (Outside) keypad unlocks the 773 or 775 Fail
Safe ET and shunts the Electroguard™ exit device and allows ingress for a time period programmable at this keypad.
Line voltage
fuse (1 AMP)
System Wiring Examples (Continued)
9
Voltage adjust for
battery backup
28 1-800-810-WIRE • www.sargentlock.com • A7690E
Copyright © 2013, Sargent Manufacturing Company, an ASSA ABLOY Group company. All rights reserved.
Reproductions in whole or in part without express written permission of Sargent Manufacturing Company is prohibited.
04/15/13
Electroguard
®
59- Prefix 80 Series Exit Device