User Manual
Red (+24), 2
White, 3
Black, (-Return), 1
Green (EG), 4
6, Blue (DS)
3520 24VDC 1.0AMP Regulated and Filtered Power Supply
Line voltage
fuse (1 AMP)
Connector to
power on LED
HOT
110-120 VAC
NEUT
GND
123
AC F
Low voltage AC
From transformer
AC
DC
DC
Output
NOTE: This drawing shows the
BPS Series. The PM Series
has no line voltage input, fuse
or connector to power on LED
2.5 AMP polyswitch breaker
Red
Black
Unconnected
terminal for
switch hookup
Plug pigtail harness
connector into
8-pin hinge connector
at frame side of door
Electric hinge with
8-pin connectors
Battery pack
Raceway harness with 8 & 4-pin
connectors. The 4-pin
connectors are not used here.
Brown (RAR - C), 7
RAR contact shown in
rail powered on state
3287
Door status
switch
59- 80 Series Rail with
8 & 4-pin connector. The
4-pin connector is not
used here.
Note: Typical raceway location is
shown. Other locations may exist
depending on door type.
4380H
(remote)
horn
8, Yellow (RAR - NO)
8
6
4
5
2
3 1
(+)
Pigtail harness
assembly with
8-pin connector
When door is closed,
the green wire is
shorted to white wire
Green (NC)
White (C)
(-)
4291
Keypad
(inside)
C
1 2 3
4 5 6
7 8
*
9
0 #
NO
(-)
(+)
Wiring Notes:
1. Rail, raceway, electric hinge and
pigtail 8-pin connector terminations
and wire colors all match.
2. Tape or cap off ends of unused pigtail
wires (not shown) to ensure that they
don’t short to anything.
3. A fire alarm tie-in is required on fire
rated openings.
4. The fire alarm contact (when required)
must be wired to drop 24VDC power
to rail. In this case, terminate fire alarm
contact between the red (+ 24VDC)
wire and supply + 24VDC output.
5. Connect the white wire to the black
(-return) wire.
Sample Wiring #2 – 59- Electroguard™ Exit Device with inside Keypad,
Fire Alarm, Door Status and Remote Horn
A valid code entry at the 4291 (Inside) keypad shunts the Electroguard™ exit device and allows egress for a time period
programmable at the keypad. During a fire alarm condition, the contact opens which de-energizes the rail electromagnet and
allows immediate egress. When the rail is armed and the door is forced open, the 3287 door status switch signals the rail
sounding the rail alarm. When the rail is armed and violated, the remote alarm relay sends 24VDC to the 4380H remote horn.
Normally Closed Fire
Alarm Contact
(If Required)
7
5, Orange (EI)
Voltage adjust for
battery backup
System Wiring Examples (Continued)
9
27 1-800-810-WIRE • www.sargentlock.com • A7690E
Copyright © 2013, Sargent Manufacturing Company, an ASSA ABLOY Group company. All rights reserved.
Reproductions in whole or in part without express written permission of Sargent Manufacturing Company is prohibited.
04/15/13
Electroguard
®
59- Prefix 80 Series Exit Device