User Manual
Harness I/O Circuit
Connector Board Function
Pin No. Pin No.
8-2 J1-1 24VDC Power Supply Input (+)
This input may be tied to the normally closed contact of a building’s fire alarm system.
If the fire alarm is activated, this contact will open, voiding the 15 second delay for egress.
8-1 J1-2 Return - Power Supply -return (-).
8-3 J1-4 Remote Reset - This input may be tied to a momentary normally open contact at
a remote location to reset the device when in alarm. Additionally when the device is armed
this input may be used for momentary egress with the time per the Dip switch settings.
8-4 Chassis Ground Chassis Ground - The chassis ground wire must terminate at earth ground of the
equipment power supply or the main power source.
8-5 J1-5 External Inhibit Input - Used to provide remote override of the delayed egress
when in the armed condition. Most common exter nal inhibits are: card readers, keypad,
key switches, or remote control console. More than one exter nal inhibit device must be
wired in parallel.
8-6 J1-6 Door Position Sensor - An exter nal door status switch can be connected to
the Electroguard™ to provide additional security. If the door status switch is utilized, an
irreversible alarm will sound if the door is forced open while the device is armed.
Unit will not arm if door is not shut. Once the irreversible alarm sounds, it will have
to be reset at the door. If the door status switch is not utilized, connect the Blue wire to
-Return (Black wire) of the 5-pin harness.
8-7 J1-8 Remote Alarm Relay Output - A SPDT (Single Pole Double Throw) 1A, 24VDC contact
8-8 J1-9 relay is provided for external alarm indication. The contacts change state when the unit
4-1 J1-10 goes into an irreversible alarm or if the door is forced open while the device is armed.
A door position sensor is required for monitoring a door forced open condition.
This contact can be utilized to drive a horn, lamp or other monitoring device.
4-2 J1-11 Latchbolt Monitor Relay - A SPDT (Single Pole Double Throw) 1A, 24VDC relay contacts,
4-3 J1-12 are provided for monitoring the latchbolt status at a remote location. This contact can be
4-4 J1-13 used to drive a horn, lamp or other monitoring device.
flying leads J1-14 Gang - Relay contact – SPDT (Single Pole Double Throw) 1A, 24VDC.
J1-15
J1-16 Gang Option - Allows multiple doors that are ganged together to unlock simultaneously
after the delayed egress time has expired during an alarmed egress state.
The LED (Red or Green according to dip switch setting) on all ganged units shall light when
unlocked. The rail horn shall sound only on the unit that initiated the delayed egress state
(not on the other ganged units). Resetting the rail which initiated the delayed egress state
with the key switch will relock and rearm all ganged rails back to the delayed egress mode.
Refer to page Section 15 for wiring and application requirements.