User Manual
Troubleshooting (Continued)
Symptom / Failure
* Refer to Diagnostic LED Table/Description and Minimum Requirements to Arm Rail sections.
A. Rail won’t arm
(Armed LED won’t turn ON / Horn sounds immediately or after a delay)
When trying to arm, the rail goes into alarm immediately after momentary egress times out or after a short
delay after the momentary egress times out.
Are the Yellow, Red and Orange Diagnostic LEDs OFF?
YES – Replace defective PCB module assembly.
*NO – All of these LEDs should be OFF. Troubleshoot according to which LED is ON. If any
LED stays ON after troubleshooting, consult 800-810-WIRE.
B. Rail won’t arm
(Armed LED won’t turn ON / Horn stays OFF)
- The rail is receiving an external inhibit signal.
- The Orange wire is connected to Black wire (-Return) through external device or directly.
- The rail is in fire alarm condition.
D. Rail Arms, but the external electromagnet is not locked when depressed
(Armed LED and Green Diagnostic LED are ON)
-Defective magnet or open magnet wires. If wires can’t be repaired, consult 800-810-WIRE.
(Armed LED is ON and Green Diagnostic LED is OFF).
E. Rail Arms, but will not go into alarm when depressing push bar
Does the Red Diagnostic LED turn ON when depressing push bar?
YES – Replace defective PCB module assembly.
NO – The push rail hall switch is defective or out of activation range. If wires can’t be repaired or if
switch can’t be adjusted (on rails which allow adjustment), consult 800-810-WIRE.
11
C. Rail won’t arm
(Horn sounds / Insert LEDs flash RED then GREEN sequence every (10) seconds. No diagnostic
LEDs are on.
- Push rail hall switch circuit defective or out of activation range. Consult 800-810-WIRE.
F. Rail flashes RED, flashes GREEN and sounds horn every ten (10) seconds
-Defective push rail assembly or hall switch. Consult 800-810-WIRE.
IMPORTANT: RAIL IS NOT ARMED WHEN IN THIS CONDITION!