User Manual

Visible Insert LEDs Function
Green (Default) or Red ON only Rail is Armed - Delayed Egress Mode
Red(Default) or Green ON only Rail is Disarmed – Maintained (Free) Egress Mode
Red (Default) or Green “Flashing” Rail is in Momentary Egress Mode
Green and Red “Alternate”, Rail Horn is ON Rail is in violation
Diagnostic LEDs Function
Yellow
ON – *Jumper is missing or in wrong position
OFF – should always be OFF
Green (Magnet)
ON – External Magnet is energized (+24VDC from main board)
OFF – External Magnet is de-energized
Red (Push Rail Switch) ON – Rail Push Bar is depressed
OFF – Rail Push Bar is released
Orange (Door Status Switch) ON – Door Status Switch is open. Door is open/violated.
OFF – Door Status Switch is closed. Door is closed and secure.
*See Jumper position and function table on following page
Troubleshooting
The tables below are provided to assist in the installation and troubleshooting of the 57- exit device.
11
IMPORTANT: Always remove power to the rail before disconnecting or reconnecting connectors at the
57- PCB module assembly. Disconnect the 24VDC Power Supply or remove the Red (+24VDC)
power wire at the rail.
The diagnostic LEDs are visible after install with end cap removed.
The following table lists the status and function of the (2) Green/Red LEDs located on the rail insert.
Diagnostic
LEDs
Refer to the following table and notes for an explanation of each LED’s function.
Insert LEDs
21 1-800-810-WIRE • www.sargentlock.com • A7743C
Copyright © 2013, Sargent Manufacturing Company, an ASSA ABLOY Group company. All rights reserved.
Reproductions in whole or in part without express written permission of Sargent Manufacturing Company is prohibited.
04/15/13
57- Prefix 80 Series Exit Device