Owner`s manual
18
Adirondack Spas®
OWNER'S MANUAL
110 / 220 VOLT CONVERTIBLE MODELS
• Keene(SEModelOnly)
110 VOLT ELECTRICAL REQUIREMENTS:
The above model is manufactured with the Adirondack Spas® 110V/220V convertible spa pack.
The unit is factory wired for 220 Volt applications with 4 kW heater operation. The model can
be converted for 110 Volt applications and to run with a 1 kW heater operation.
The 110 Volt model must be connected to a “dedicated” 110 Volt 20 Amp grounded
circuit. The term “dedicated” means the electrical circuit is not being used for any other
electricalitems(lights,appliances,etc.).Ifthespaisconnectedtoanon-dedicated
circuit, overloading will occur and nuisance tripping of the GFCI breaker switch at the
house breaker panel or GFCI cord will occur. Never connect the spa to an extension
cord due to the potential for fire from wires overheating.
The 110 Volt models may be optionally equipped with a GFCI power cord
(approximately13feetlong).Thismodelmustbepluggedintoagroundingtype,
110 Volt 20 Amp receptacle as shown below. No other electrical appliances or fixtures
should be used on this circuit.
The use of any other receptacle or the connection of the plug to a 220 Volt service may
cause the spa pack to operate improperly, create the potential for an electrical hazard and
may void the spa warranty.
Adirondack Spas® models must be wired in accordance with all local electrical codes.
All electrical work should be done by an experienced, licensed electrician familiar with
spa installations.
Note: AsofJanuary1,1996theNationalElectricalCode(NEC)requiresaGFCI
(GroundFaultCircuitInterrupter)onallspainstallations.
CORRECT INCORRECT
Data label amperage rating of 16 Amps must use
this type of 20 Amp dedicated receptacle and plug.
Dedicated 110V, 20A Receptacle
Dedicated 110V, 15A Receptacle
Do not use this type.
!
!
!
!