Owner`s manual

16
Adirondack Spas®
OWNER'S MANUAL
ELECTRICAL REQUIREMENTS AND PRECAUTIONS
Your Adirondack Spas® model has gone through numerous tests to verify that all of the spa
functions operate. Beyond the tests, your Adirondack Spas® model has been designed to
provide the maximum safety against electrical shock. Read and follow the electrical installation
requirements and instructions completely. The next few pages will assist you in properly
connecting the electrical input. Follow the electrical instructions for your specific spa model.
Serious risks or injuries may occur if the spa is improperly wired.
220 Volt Permanently Connected SE and LE Models:
• Keene* Champlain Saranac Caroga Cascade Marcy • Georgian • Regent LE
*This model is convertible to 110V—See page 18 for installation instructions.
Adirondack Spas® must be wired in accordance with all applicable local electrical
codes.UseNEC250-122(table)andlocalcodesformoreinformation.Allelectrical
work should be done by an experienced, licensed Electrician. We recommend the use of
appropriate electrical conduit, fittings and wire for all circuits.
220 Volt installations require a 60Hz, single phase, three-wire electrical service plus
ground(Line1,Line2,NeutralandGround)andmustbeconnectedusingaminimum
supply conductor ampacity of 50 AMPs and a minimum circuit breaker size of 50 AMPs.
Note:Usecopperwireonly(3wirewithground;8gaugeunder50',6gaugeover50')
220 Volt model spas must be connected to a “dedicated” 220 volt 50 Amp grounded
circuit. The term “dedicated” means the electrical circuit is not being used for any other
electricalitems(lights,appliances,etc.).Ifthespaisconnectedtoanon-dedicated
circuit, overloading will occur and nuisance tripping of the GFCI breaker switch at the
house breaker panel will occur.
Agroundlugconnectorisprovidedontheexteriorsurfaceofthespapack(operations
center)insidetheequipmentcompartment.Thisistopermittheconnectionofa
bonding wire between this point and any metal equipment, enclosures, pipe or conduit
withinfivefeet(1.5m)ofthespa.Thisbondingwiremustbeatleast8AWGsolid
copper wire.
Due to the risk of equipment damage or fire, use only approved pressure-type wire
splicing lugs or connectors suitable for the size and type of wiring used.
Electrical Installation Instructions for 220 Volt Models
1. To connect the electrical service, first remove the screws from the equipment compartment
door. Carefully remove the access panel.
2. Locate the spa power pack. Loosen the screws on the front of the control box. Remove the
screws and the control box cover.
3. Input the electrical service from the GFCI breaker into the spa equipment compartment.
The GFCI breaker must be placed in sight of the spa, at a minimum distance
offivefeet(1.5m)away.
AsofJanuary1,1996theNationalElectricCode(NEC)requiresGFCI
(GroundFaultCircuitInterrupter)onallspainstallations.
4. Connect the supply conduit to the spa power pack.
!
!
!
!
!
!