Installation Manual

36
The Sapling Company, Inc.
670 Louis Drive
Warminster, PA 18974
USA
P. (+1) 215.322.6063
F. (+1) 215.322.8498
www.sapling-inc.com
Alternative Inputs - Clock-Side - Sync-Wire
Dukane
Description:
Midnight Reset or Once a Day Pulse
J1-
1
2
3
4
5
6
7 8
9
J2-
1 2
Reset
Minute Pulse
Ground
J1-
1 2 3 4 5 6
7
9
8
Neutral
Reset
110VAC or
230VAC Interface
1 2
3
4 5
6
7
8 9
Neutral
Reset
J1-
24VAC Interface
J1-
1
2
3
4
5
6
7 8
9
J2-
1 2
Relay
N.O.
COM
Dry Contact Closure
Description:
Dukane - Applying a 4-10 millisecond pulse on the minute line will increment the clock in one minute.
Applying a 12-50 millisecond pulse on the reset line will bring the clock back to 12:00 a.m.
Midnight Reset or Once a Day Pulse - Applying a pulse for more than two (2) seconds will bring the
clock to the correct time.