4. Service procedures
4) Symptom: LCD on the remote controller is displaying “CHECK E04”. (Unusual
communication between the indoor and outdoor units.)
5) Symptom: LCD on the remote controller is displaying “CHECK E05”. (Unusual
communication between the indoor and outdoor units)
Yes
No No
Yes
No
Yes
0335_M_I
Start
Is the contact good at the 2P 
connector for indoor serial 
communications on the outdoor 
unit PCB?
Is the contact good at the 2P 
connector for indoor serial 
communications on the outdoor 
unit PCB?
Correct the connections.
No
Correct the connections.
Replace the indoor unit PCB.
Replace the indoor unit PCB.
 Indoor/outdoor unit 
control lines are cut off
 Correct the wiring.
Cut the breaker, remove the 
indoor/outdoor unit control 
lines connected to U1 and U2 of
the outdoor unit 8P terminal plate. 
After shorting the test pin (CN11) on 
the outdoor unit PCB, switch the 
breaker on. Do the LEDs (red, × 2) 
on the PCB flash?
Cut the breaker and remove the 
indoor/outdoor unit control lines 
connected to U1 and U2 of the 
indoor unit 8P terminal plate. 
After shorting the test pin (CN2) 
on the indoor unit PCB, switch the 
breaker on. Does the LED 
(red) on the PCB light up?
0336_M_I
Start
Indoor unit PCB transmission/
reception circuit defect
Replace the indoor unit PCB.