Air Conditioner User Manual
4. Service procedures
1
2
3
4
Section
SM830082
IV - 10
2) Symptom: LCD on the remote controller displays “CHECK E01”. (Unusual
communication between remote controller and indoor unit.)
OK
No
No
Yes
Yes
NG
2096_THS_I
Start
Remote controller judges itself 
with self-diagnostic functions
Replace the remote controller.
Correct the wiring.
Open the inspection pin.
Is there an open or a contact 
defect in the No. 1 line of the 
remote controller?
No
Yes
Yes
Is there 230 -208 V AC between 
U1 and U2 of terminal plate?
Mis-wiring between the power 
supply line and indoor/ outdoor 
unit operation lines.
Correct the wiring, and pull out the 
socket connected to the OC plug 
to replace with the EMG plug.
Is the indoor 
unit PCB’s
 inspection 
pin shorted?
Replace the indoor 
unit PCB
.
3) Symptom: LCD on the remote controller displays “CHECK E02”. (Unusual
communication between remote controller and indoor unit)
OK
NG
2097_M_I
Start
Replace the remote controller.
Remote controller judges itself with 
self-diagnostic functions.
Replace the indoor unit PCB.