Specifications
Multipoint
5
5
WATER REQUIREMENTS
3.1 The heater must be connected via the pressure relief valve to a cold supply
having a minimum pressure of 0.1Mpa (1bar) and a maximum of 0.5Mpa (5bar).
Both inlet and outlet connections are suitable for 15mm diameter copper pipe.
Outlet pipe from unit may reduce to 10mm diameter to improve performance.
3.2 The tee piece and pressure relief valve must be situated where shown and the
relief valve discharge port plumbed via an air break (tundish) to a safe, visible
place where there is no risk from hot water to persons using the building.
3.3 The discharge pipe must fall continuously from the valve outlets and be
unobstructed.
3.4 The provision of a service stop valve in the cold supply pipe will assist in the
event of any subsequent servicing or maintenance.
3.5 To obtain optimum performance a ow restrictor must be tted where shown
(see gure 3). This provides the user with the means to govern the ow (and
therefore temperature which is dependent upon ow) at the outlet (see under
SETTING FLOW RATE).
3.0 SITE REQUIREMENTS
A - OUTLET VALVE
B - FLOW RESTRICTOR
C - POWERPACK
D - PRESSURE RELIEF VALVE
E - SERVICES STOP VALVE
A
B
C
D
E
Figure 3