Install Instructions
9
800.533.7533 | Santa-Fe-Products.com Santa Fe ULTRA120V Installation & Operation Instructions
Fresh air ventilation is optional.
Fresh air may be brought into the structure by connecting an insulated duct from outside the structure to
the 6" inlet of the Santa Fe Ultra120V. A ventilation control is needed to program the time and frequency that
the unit introduces outside air. The time and frequency of ventilation should be based on the size and
occupancy of the residence.
• The fresh air ventilation duct should be connected to the 6" damper on the top of the Santa Fe Ultra120V.
• An insulated 6" diameter duct can provide up to 100 CFM of outside air.
• If the fresh air ventilation duct is to be used, the return of the Santa Fe Ultra120V must be ducted or an
inline fan may be required on the fresh air ventilation line to bring in outside air.
• If a motorized damper is not being used, fresh air is controlled by the manual damper in the 6” collar of the
Santa Fe Ultra120V.
• Performance of the Santa Fe Ultra120V can be impacted by inside and outside air conditions.
• When a 6" motorized damper is used, a digital control is required.
• It may be necessary to use 8" duct work if additional fresh air is required.
• In cold climates or at times when the dew point is low, ventilation can be used to dehumidify the
structure, making the Santa Fe Ultra120V capable of year-round drying.
FRESH AIR VENTILATION
Fresh Air Ventilation With Dehumidier O and Fan Only Operation
Outside air mixes with the dehumidier’s return air before being supplied to the home. Outside
temperature, inside temperature and relative humidity will impact the combined outlet air conditions.
Note: Temperature and relative humidity may vary depending on duct distribution scheme.
70°F and 60% RH
90 pints/day
6.0 Pints/kWh
Shipping
24”
49”
21”
138 lbs.
6" Fresh Air Intake (Optional)
10" Return Air Duct
8" Supply Air Duct #1
8" Supply Air Duct #2 (Optional)
Front
View
Hot Climate Cold Climate
Indoor Air
70°F, 50%RH
Outdoor Air
90°F, 65%RH
Indoor Air
70°F, 50%RH
Outdoor Air
30°F, 65%RH
Outlet Air
76°F, 59%RH
Outlet Air
76°F, 59%RH
Outlet Air
59°F, 60%RH
Outlet Air
59°F, 60%RH
Front
View