Install Instructions

7
800.533.7533 | Santa-Fe-Products.com Santa Fe ULTRA120V Installation & Operation Instructions
The Santa Fe Ultra120V generates condensate.
Place a secondary drain pan with a oat switch under the dehumidier if it is suspended above a nished
area or above an area where water leakage could cause damage.
The Santa Fe Ultra120V contains an internal drain trap for proper dehumidier operation. Install a 3/4” threaded
male NPT adapter to the external condensate tting. Install a drain pipe assembly utilizing 3/4” PVC pipe to
transport the condensate to a drain. Pitch of drain should be 1" per 10'.
An optional condensate pump kit is available for use with the Santa Fe Ultra120V and may be installed if lift
is
required to dispose of condensate. Condensate is automatically pumped to a remote location when the
water level in the pump’s reservoir rises to close the oat switch.
The pump also contains a safety oat
switch. If the pump fails, this switch opens
the common control circuit and stops water
production before the reservoir overows.
Note: An optional condensate pump kit can
be purchased through your dealer or online.
Refer to the kit literature for installation
instructions.
Side View
Supply
Air
Outlet
3/4" FPT
Fitting
DRAIN INSTALLATION
Drain Installation