Install Instructions

12
Santa Fe ULTRA120V Installation & Operation Instructions Santa-Fe-Products.com | 800.533.7533
The Santa Fe Ultra120V is equipped with a MERV-13 (Dimensions: 1.75” x 15.50” x 19.50”) lter. An optional
MERV-14 lter is available at www.ThermastorFilters.com. The MERV-13 lter should be checked and replaced
every three to six months. If the MERV-14 lter is used, the MERV-13 should act as a pre-lter and sit on top of
the MERV-14 lter. Replacing the MERV-13 lter every three to six months extends the life of the MERV-14 lter.
The MERV-14 lter should be replaced every two to three years if a MERV-13 is used as a pre-lter and replaced
every three to six months. Operating the unit with a dirty lter will reduce dehumidier capacity and eciency.
DO NOT operate the unit without the recommended lter. Filter non-compliance voids the product warranty.
AIR FILTRATION
Changing the Filter
For greatest ltration and eciency of
the Santa Fe Ultra120V, it is recom-
mended the air lter be replaced every
three to six months with a MERV-13
lter.
Step 1: The lter access door is located
above the front panel of the dehumidier.
Pull straight up on the door latch to disengage
from the front panel, then lift door to it’s
vertical position.
Step 2: Remove the used lter(s)
from the housing. Insert the new lter by
gently pushing it straight into the lter
cavity. Make sure the air ow arrows on
the lter are pointing down into the unit.
Step 3: Close the lter access door by push-
ing up on the door latch, inserting the latch
into the front panel, then releasing. Ensure
that the latch is rmly engaged
with the front panel.
CAUTION!CAUTION!
MAKE SURE UNIT IS OFF BEFORE CHANGING THE FILTER.
Side View
Filter
A
ccess
Door
Filter
Access
Door
Side
View
70°F and 60% RH
90 pints/day
6.0 Pints/kWh
Shipping
24
49
21
138 lbs.
Front View
Door
Latch
Filter
Access
Door
Side View
A
Step 1
Step 2
Step 3