User Guide

6
Santa Fe ULTRA98/ULTRA120 Installation & Operation Instructions Santa-Fe-Products.com | 800.533.7533
The Santa Fe Dehumidier plugs into a common grounded 115 VAC outlet. Locate the dehumidier in an
area where the cord’s length (9') easily reaches a 115 VAC electrical outlet with a minimum of 15 Amp circuit
capacity. If used in an area that may become wet, a GFCI protected circuit is recommended. Consult local
electrical codes for further information.
Santa Fe oers a variety of control devices for use with the Santa Fe Dehumidier. The control is to be located
remotely from the dehumidier and placed in the space to be conditioned. A low voltage (24 Volt) control MUST be
used with the Santa Fe Dehumidier and MUST be connected with low voltage (18-22 gauge) thermostat wire.
ELECTRICAL REQUIREMENTS
CAUTION!CAUTION!
DO NOT ALLOW THE 24V TERMINAL TO CONTACT THE COM/DMPR TERMINALS ON THE
SANTA FE DEHUMIDIFIER OR DAMAGE TO THE TRANSFORMER WILL RESULT.
Electrical Precautions
Do not install the control where it may not accurately sense the relative humidity such as near HVAC
supply registers, near exterior doors, on an outside wall, near a window, or near a water source.
The screw terminals on the Santa Fe Dehumidier and the control are labeled to prevent confusion.
Be sure to consult the electrical schematic in the CONTROLS Section (page 12) of this manual or inside
the access panel of the Santa Fe Dehumidier before making control connections.
WARNING!WARNING!
THE REMOTE CONTROLS OF THE SANTA FE DEHUMIDIFIER ARE POWERED BY A LOW VOLTAGE
CIRCUIT (24 VAC) AND MUST NEVER CONTACT OR BE CONNECTED TO A HIGH VOLTAGE CIRCUIT.
CAUTION!CAUTION!
SOME OF THE SCREW TERMINALS ON THE SANTA FE DEHUMIDIFIER MAY NOT BE USED WITH
CERTAIN CONTROLS AND SHOULD BE LEFT UNCONNECTED.
Santa Fe ULTRA98H Wiring Diagram Santa Fe ULTRA120H Wiring Diagram