The Santa Fe Dehumidier generates condensate.
Place a secondary drain pan with a oat switch under the dehumidier if it is suspended above a nished
area or above an area where water leakage could cause damage.
A drain trap is required for the dehumidier to drain properly. Install a 3/4" threaded male NPT adapter to the
drain pan. Install a drain pipe assembly utilizing 3/4" PVC pipe to transport the condensate to a drain. Pitch
of drain should be 1" per 10'.
An optional condensate pump kit is available for use with the Santa Fe Dehumidier and may be installed if
lift is required to dispose of condensate. Condensate is automatically pumped to a remote location when the
water level in the pump’s reservoir rises to close the oat switch.
The pump also contains a safety oat switch. The white leads from this switch extend from beneath the
pump cover. This switch should be installed in series with the eld wire that connects to the common lead
from the Santa Fe Dehumidier to the control panel. If the pump fails, this switch opens the common control
circuit and stops water production before the reservoir overows. Contact a qualied electrician to install the
safety oat switch to the Santa Fe Dehumidier.
Note: An optional condensate pump kit and an automatic cut-o device can be purchased through your
dealer or online.
DRAIN INSTALLATION
Drain Installation
Drain
Trap
Drain
Port