Specifications
OWNER’S GUIDE CONDITIONERS, PAD | 14365
PAD Modules Table
Module Chs
Input
type
Ranges
Bandwidth
(BW)
Filters
(FILT)
Isolation
(ISO)
Overvoltage
protection
(OP)
Special
functions
Voltage measurement
PAD-V8-P
V
8
Voltage ±100 mV to ±50 V
BW: 6 Hz
FILT: 1 / 4 / 8
values
ISO: 350 VDC
OP: 150 VDC
Separate 24-bit
ADC per channel
Current ±20 mA
Temperature and Ωic measurement
PAD-TH8-P + PAD-CB8-J/K/T
8
Voltage
±15, ±50, ±100, ±150 mV
-150 mV to +1.5V
BW: 6 Hz
FILT: 1 / 4 / 8
values
ISO: 350 VDC
OP: 15 VDC
Separate 24-bit
ADC per channel
Thermocouple
Types J, K, T with PAD-CB8
breakout box
PAD-TH8-P + PAD-CB8-RTD
8
RTDs
Pt100, Pt200, Pt500,
Pt1000, Pt2000, Ni120
BW: 6 Hz
FILT: 1 / 4 / 8
values
ISO: 350 VDC
OP: 15 VDC
Separate 24-bit
ADC per channel
Resistors up to 2 MΩ
Analog and digital outputs
PAD-DO7
7 Digital output Relay outputs (dry contacts) -- ISO: 300 VDC
Max load:
0.5 A @ 60 VAC,
1 A @ 24 VDC
PAD-AO1
OUT
1
Voltage output 0 to 10V
-- ISO: 300 VDC
--
Current output 0 to 20 mA, 4 to 20 mA
Please see the following pages for details about each of the available PAD series modules and accessories.
- Note: if you want to also use DAQ or HSI series modules in this expansion rack, then you must also have an
analog cable connecting it to the DEWE-3210 or DEWE-3211. In addition, there must be an A/D card inside the
DEWE-321x chassis with the appropriate number of ADCs available.
Hook-up Notes:
- If using RS232 com port, you must congure the port used for additional PAD modules in the DS-7 settings >
hardware setup > analog tab.
- Make sure “PAD modules” are checked