Contents Preparation for installation . .............................................................................................................................................................................................. 3 Deciding on where to install the indoor unit . .......................................................................................................................................................... 4 Indoor unit installation . ................................................
Our units should be installed in compliance with the spaces shown in the installation manual, to ensure accessibility from both sides and allow repairs or maintenance operations to be carried out. The unit’s components should be accessible and easy to disassemble without endangering people and objects.
Preparation for installation Accessories The following accessories are supplied with the indoor unit. The type and quantity may differ depending on the specifications.
ENGLISH Unit Depth(D)+50mm Deciding on where to install the indoor unit Unit Width(W) "A"=W+100mm "B"=500mm 20mm or more 20mm or more You must have20mm or more space between the ceiling and the bottom of indoor unit. Otherwise, the noise from the vibration of indoor unit may bother the user.When the ceiling is under construction, the hole for check-up must be made to take service, clean and repair the unit. It is possible to install the unit at an height of between 2.2~2.
Deciding on where to install the indoor unit AA Drawing of the indoor unit Unit:mm NS035LDXEA 3 256=768 71 100 10 11.9 28 28 600 477(Suspension position) 938.4 (Suspension position) 8 100=800 860 (Air outlet duct flange) 22-ø3.2 hole (Air around) 900 650 Inspection hole 900 1000 6 No. Name 1 2 3 4 5 6 7 8 Liquid pipe connection Gas pipe connection Drain pipe connection Drain pipe connection Power supply connection Air discharge flange Air filter Hook 30.5 OD32 72.5 55 100 151.
Unit:mm NS052LDXEA/NS071LDXEA ENGLISH (Suspension position) (Suspension position) (Air outlet duct flange) hole (Air around) 650 Inspection hole 1100 1200 500 Discharge side No. Name 1 2 3 4 5 6 7 8 Liquid pipe connection Gas pipe connection Drain pipe connection Drain pipe connection Power supply connection Air discharge flange Air filter Hook Suction side Description ø6.35(1/4") 052: ø12.70(1/2"); 071: ø15.
Deciding on where to install the indoor unit AA Drawing of the indoor unit Unit : mm NS052SDXEA 397 (Suspension position) 900 1000 135x5=675 7 87 500 97 900 844 (Air outlet duct flange) 6 936 (Suspension position) 530 480 8 222 Discharge side 185 90 260 Inspection hole 2 1 5 No.
NS071SDXEA NS090SSXE NS100SSXE Unit : mm ENGLISH 530 480 18-Ø3.2 hole (Air around) 1150 97 1250 1188 (Suspension position) 1150 904 (Air outlet duct flange) 6X135=810 397 (Suspension position) 220 500 90 90 260 185 Inspection hole 67 117 Discharge side ODØ32 No. 1 2 3 4 5 6 7 8 Suction side 76 132 144 Name Liquid pipe connection Gas pipe connection Drain pipe connection Drain pipe connection Power supply connection Air discharge flange Air filter Hook Description 071:ø6.
Deciding on where to install the indoor unit AA Drawing of the indoor unit Unit : mm NS090SDXEA 530 500 102 1150 1250 (Air outlet duct flange) (Suspension position) (Suspension position) Discharge side 10 Suction side Inspection hole No. Name Description 1 2 3 4 5 6 7 8 Liquid pipe connection Gas pipe connection Drain pipe connection Drain pipe connection Power supply connection Air discharge flange Air filter Hook ø9.52(3/8") ø15.
NS100SDXEA NS125SDXEA NS140SDXEA Unit : mm ENGLISH 700 650 1300 500 102 1200 1000 (Air outlet duct flange) 1236 (Suspension position) 534 (Suspension position) Discharge side Suction side Inspection hole No. Name Description 1 2 3 4 5 6 7 8 Liquid pipe connection Gas pipe connection Drain pipe connection Drain pipe connection Power supply connection Air discharge flange Air filter Hook ø9.52(3/8") ø15.
Indoor unit installation AA When deciding on the location of the air conditioner with the owner, the following restrictions must be taken into account. 1 Place the pattern sheet on the ceiling at the spot where you want to install the indoor unit. • Since the diagram is made of paper, it may shrink or stretch slightly due to temperature or humidity. For this reason, before drilling the holes maintain the correct dimensions between the markings. Concrete 2 Insert bolt anchors.
Purging the unit AA From factory the unit is supplied and set with a pre-charge of nitrogen gas. (insert gas) Therefore, all insert gas must be purged before connecting the assembly piping. NS035/052/071LDXEA Unscrew the pinch pipe at the end of each refrigerant pipe. • To prevent dirt or foreign objects from getting into the pipes during installation, do NOT remove the pinch pipe completely until you are ready to connect the piping.
Connecting the refrigerant pipe There are two refrigerant pipes of different diameters : A smaller one for the liquid refrigerant A larger one for the gas refrigerant The inside of copper pipe must be clean & has no dust 1. Remove the pinch pipe on the pipes and connect the assembly pipes to each pipe, tightening the nuts, first manually and then with a torque wrench, a spanner applying the following torque. Refrigerant oil Torque wrench Spanner Flare nut Union Outer Diameter (D) Torque (N•m) ø6.
Cutting/Flaring the pipes 1. Make sure that you have the required tools available. (pipe cutter, reamer, flaring tool and pipe holder) 2. If you wish to shorten the pipes, cut it with a pipe cutter, taking care to ensure that the cut edge remains at a 90° angle with the side of the pipe. Refer to the illustrations below for examples of edges cut correctly and incorrectly. Oblique Rough ENGLISH Pipe cutter Burr Pipe 3.
Performing leak test & insulation AA NS035/052/071LDXEA Leak test LEAK TEST WITH NITROGEN (before opening valves) In order to detect basic refrigerant leaks, before recreating the vacuum and recirculating the R-410A, it’s responsable of installer to pressurize the whole system with nitrogen (using a cylinder with pressure reducer) at a pressure above 30 bar (gauge). LEAK TEST WITH R-410A (after opening valves) Before opening valves, discharge all the nitrogen into the system and create vacuum.
Pipe size Liquid pipe Ø6.35 ~ Ø9.52 Ø12.7 ~ Ø19.05 Ø6.35 Ø9.52 Ø12.70 Ø15.88 Ø19.05 Gas pipe Insulation Type (Heating/Cooling) Standard [30°C, 85%] High humidity [30°C, over 85%] EPDM, NBR 9t 9t 13t 13t 13t 19t 19t Remarks ENGLISH Pipe Internal temperature is higher than 120°C 25t When installing insulation in places and conditions below, use the same insulation that is used for high humidity conditions.
Drainpipe and drain hose installation AA Drainpipe Connection Without the drain pump 1. Install horizontal drainpipe with a slope of 1/100 or more and fix it by hanger space of 1.0~1.5m. 2. Install U-trap at the end of the drainpipe to prevent a nasty smell to reach the indoor unit. 3. Do not install the drainpipe to upward position. It may cause water flow back to the unit. 1~1.5m Hanger Flexible hose Horizontal drainpipe more than 1/100 slope Ceiling With the drain pump 1.
Connecting the connection cord The indoor unit is powered by the outdoor unit by means of a H07 RN-F connection cable (or a more power model), with insulation in synthetic rubber and jacket in polychloroprene(neoprene), in accordance with the requirements of standard EN 60335-2-40. 1. Remove the screw on the electrical component box and remove the cover plate. 2. Route the connection cord through the side of the indoor unit and connect the cable to terminals; refer to the figure below. 3.
Adjusting air flow AA E. S. P(External Static Pressure) setting for phase control motor With its phase control motor, you can adjust the indoor unit fan speed depending on the installation condition. If the external static pressure is high so that the duct becomes longer or if the external static pressure is low so that the duct becomes shorter, adjust the fan speed by referring the following table. Static Pressure (mmAq) 0 2 2.
0 Model NS035LDXEA NS052LDXEA NS052SDXEA 2.5 4 5 8 - - - - 011034 -196106 -27343C -370010 011034 -19630D -27343C -370010 ENGLISH Static Pressure (mmAq) Option code for indoor unit 011037 -136153 -272328 -370010 011014 -156360 -27343C -370010 011014 -19625E -27343C -370010 011037 -1361DB -272328 -370010 011014 -1563E6 -27343C -370010 011014 -1963A2 -27343C -370010 011047 -136220 -272328 -370010 011034 -15616C -27343C -370010 - • represents E. S.
Setting the indoor unit option code AA Setting the option code with wireless remocon is availble if receiver kit is installed. Please use the proper wireless remocon such as MR-DH00 which set 24 digit option code. Following is the instruction of setting option code with wired remocon(WMR-WH02). In order to set the indoor unit option code using the wired remote controller, hold down the buttons at the same time for 5 seconds. and 1 The menu will display .
Setting an indoor unit address and installation option AA ENGLISH Set the indoor unit address and installation option with remote controller option. Set the each option separately since you cannot set the ADDRESS setting and indoor unit installation setting option at the same time.You need to set twice when setting indoor unit address and installation option.
Setting an indoor unit address and installation option AA Setting an indoor unit installation option In order to check and set the indoor unit DIP option code using the wired remote controller, hold and buttons at the same time for 5 seconds. down the 1 The menu will display Press the 2 Press the . button until is displayed. button. The current DIP option code set in an indoor unit will be displayed. 3 Press button and change the page number. The total option codes are 24digits.
Option No.
Troubleshooting AA If an error occurs during the operation, one or more LED flickers and the operation is stopped except the LED. If you re-operate the air conditioner, it operates normally at first, then detect an error again.
LED Display on the receiver & display unit ENGLISH Indicators Concealed Type Abnormal conditions Green Remarks Red Standard Type Communication error between indoor units X X X 1. Error of electronic expansion valve close 2. Error of electronic expansion valve open 3. 2’nd detection of high temperature cond 4. 2’nd detection of high temperature discharge X X Detection of the float switch X X Error of setting option switches for optional accessories X X 5. Error of reverse phase 6.
Troubleshooting AA Wired remote control If an error occurs, is displayed on the wired remote control. If you would like to see an error code, press the Test button. Display Explanation Remark Indoor unit Communication Error Indoor/Outdoor unit Communication Time Out Error 60 Packet Over data Indoor unit is not connected Communication Error Communication Error between Outdoor Main and Inverter Micom (Occurred after 1 minute detection in Main and Inverter) Indoor Temp.
Memo ENGLISH 29
"EEE Yönetmeliğine Uygundur" "This EEE is compliant with RoHS"
Duct Type Series NSLDXEA NSSDXE NSSSXE Air Conditioner installation manual This manual is made with 100% recycled paper. imagine the possibilities Thank you for purchasing this Samsung product. To receive more complete service, please register your product at www.samsung.