USER’S MANUAL CHINESE ENGLISH MIM-D00 DMS (Data Management Server) K E C DB98-29777A(4)
Safety Precautions • Before using the DMS, read carefully these instructions. • After reading the instructions, keep this user's manual in a handy and safe place. If a user is changed, you must hand over the manuals. • Never attempt to install the air conditioning system or to move the DMS by yourself. WARNING Do not attempt to install or repair this DMS by yourself. This DMS contains no user-serviceable parts. Always consult authorized service personnel for repairs.
ENGLISH Contents General Description INTRODUCTION OF DMS ............................................................................. 4 ADVANTAGES OF DMS SYSTEM ................................................................ 4 TERMS ............................................................................................................... 5 Main Function INTERFACE WITH UPPER LEVEL CONTROLLER ........................................... 6 SAVE ERROR HISTORY ...................................
General Description INTRODUCTION OF DMS (DATA MANAGEMENT SERVER) The DMS is an Internet based device for central management of Samsung system air-conditioners. It supports LAN & WAN and operates 24 hours without a separate PC. ADVANTAGES OF DMS SYSTEM The DMS provides the following advantages: Everyday Device –The DMS is operational all year long 24 hours. Independent Operation–The DMS can operate schedule control, peak power control, and power distribution without a PC.
ENGLISH TERMS DMS The abbreviation of Data Management Server. UPPER CONTROLLER It means S-NET Series, a local controller of the DVM system. S-NET 3, S-NET mini and S-NET i are linked to a DMS. CENTRALIZED CONTROLLER A device that controls 16 groups of the DVM air conditioner. A central control device of a DVM system which is located between a DMS and an outdoor unit transmitter. TRANSMITTER A data transmitter of a DVM system which is located between a central controller and an outdoor unit.
Main Function Interface with Upper Level Controller The DMS receives control data from the upper level controller and sends the received data to the lower level system. The upper level controllers of the DMS are the S-NET series and the connectible S-NET series are S-NET 3, S-NET i and S-NET mini. S-NET 3 is a program that is used by installing on a PC: S-NET mini and S-NET i are touch screen type controllers. Save Error History The DMS saves at most 256 cases of error history.
Set and Run Schedule Content Item ENGLISH The schedule function of the DMS can be set through the Web or using the upper level controller.
Main Function (Continued) Save Integrated Power Distribution Data Overview The DMS calculates and distributes the power consumed by each indoor unit by receiving the total power usage from the watt-hour meter interface modules (SIM) and taking into account the operation status of the indoor units. The DMS saves at most 93 days worth of data. After 93 days, the oldest data is deleted and the latest data is saved. This data can be viewed through the built-in Web page of the DMS or by S-NET 3.
ENGLISH Time Segmentation Time segmentation is used to divide 24 hours into different sections and to distribute power according to each section. This function is used when the power consumption fee is different according to different time slots or when a building is charged differently depending on the consumption time. Time can be divided into 1 section (a), 2 sections (a,b,a), and 3 sections (a,b,c,b,a).
Using the DMS through the Web Setting the Web Environment Install JRE 1.3.1 or later version Java Runtime Environment 1.3.1 or a later version must be installed on the PC. JRE is installed automatically if the PC is connected to the Internet and when the DMS is accessed for the first time. JRE can also be downloaded from http://java.sun.com/j2se. Install Internet Explorer 6.0 or later version IE6.0 or later version must be installed on the PC. Please install IE6.
Login Function Details ENGLISH Login allows only authorized users to access the web page. There is no limit on the number of users that can access the DMS at the same time, however, less than 5 users are recommended for access speed reasons. Login 1 Type in an ID and a password and click on the LOGIN button. 2 If an ID and a password are valid, the monitoring and control page will be displayed. 3 If the ID and the password are not matched, the LOGIN page is displayed again.
Using the DMS through the Web (Continued) Monitoring and Control Function Details On this screen users can monitor the operation status of all indoor units and control each indoor unit. (But, if the ERV system is installed, can check the whole ERV control status.) Monitoring and Control 1 The status of all indoor units can be viewed from the ‘Monitor all indoor units.’ The color of the squares represents the following meaning and the name of each indoor unit is displayed inside of squares.
Select and click on the indoor unit and the background color of the indoor unit is changed to green. The operation status of the selected indoor unit is displayed on the upper part. Displayed items are as follow: ENGLISH 2 Displays the name of the selected indoor unit. Selected indoor unit address Error Power Celsius(°C) Displays whether there is an error on the selected indoor unit. (Only when an error is occurred, it is displayed as red.
Using the DMS through the Web (Continued) 3 Enable/Disable Remote Control. When pressing the button, selected indoor unit will be underlined. When pressing the button, underline on selected indoor unit will disappear. If remote control LEVEL1 is set on upper level controller, selected indoor unit will be underlined. 4 Select All/Clear all. The simultaneous control of whole installed indoor units is possible.
ENGLISH 5 [Current Temperature] Selection. When selecting the check box, display the current temperature of the whole installed indoor units. In order to return to the monitoring screen, select again the [Current Temperature]. 6 Emergency Stop status button is displayed in red if the DMS is currently in the emergency stop status. In the emergency stop status, the indoor units may be monitored but not controlled.
Using the DMS through the Web (Continued) Monitoring and Control (ERV System) Function Details On this screen users can monitor the operation status of all ERVs and control each ERV. Monitoring and Control 1 The status of all ERVs can be viewed from the ‘Monitor all indoor units.’ The color of the squares represents the following meaning and the name of each ERV is displayed inside of squares. Gray Blue Green Red E-16 MIM-D00_IB_E_29777-2.
ENGLISH 2 Select and click on the ERV and the background color of the ERV is changed to green. The operation status of the selected ERV is displayed on the upper part. Displayed items are as follow: Displays the name of the selected ERV. Selected indoor unit address Error Power Click on this button to turn on and turn off the selected ERV. The current mode of the selected ERV is displayed in light blue. Click on the desired mode to change modes.
Using the DMS through the Web (Continued) 3 Enable Remote Control/Disable Remote Control. When pressing the button, cannot control the ERV by the wired remote control in each room and can control the ERV only on the DMS webpage screen. When ending the DMS after selecting the on the DMS webpage screen, cannot use the ERV in each room. In order to control the ERV in each room, a user must press the on the DMS webpage screen. When pressing the button, can use the wired remote control in each ) room.
ENGLISH 5 [Current Temperature] Selection. When selecting the check box on the ERV system, display with “- -”. In order to return to the monitoring screen, select again the [Current Temperature.] 6 Emergency Stop status button is displayed in red if the DMS is currently in the emergency stop status. In the emergency stop status, the indoor units may be monitored but not controlled. (The emergency stop function can only be used when the external contact control of the DMS is used.
Using the DMS through the Web (Continued) View Error History Function Details The DMS users can view and delete error history of the DVM system. The DMS saves up to 256 errors. Viewing the Error History 1 All error history can be checked from the ‘View Error History’ page. 2 The error history can be viewed according to date. Select the date in the list box and press the ‘Search’ button to view the error history according to the selected period.
Set, Run and View Schedule ENGLISH Function Details Users can set, edit, and delete schedules for controlling the DVM system. Using the Schedule Function The Schedule List screen shows all current schedule information saved in the DMS. 1 On the schedule screen, a schedule can be created, edited, viewed, and deleted. 2 Press the ‘New schedule’ button in to create a new schedule.
Using the DMS through the Web (Continued) Adding a New Schedule On the Create New Schedule screen, users can set the Schedule Name, Schedule Period, Applied Indoor Unit, and Event. E-22 MIM-D00_IB_E_29777-2.indd 22 1 For the event, users can set the Repeat or not, Day, On Time, Off Time, Temperature, Mode, ERV Mode and Remote Control Allow or not. Users can assign the maximum 10 events. (Set the ERV mode only when the ERV is connected.
When pressing the ‘Select indoor unit’ button from the , users can select the schedule indoor unit. 4 Users can set one of schedule repetition or not, which are every week, every day, and one day from the drop down menu . If setting to one day, assign the same date of starting date and ending date. 5 When pressing the ‘Add Event’ button from the , a new event is added. When pressing the ‘Delete Event’ button from the after selecting a check box from the , the selected event is deleted.
Using the DMS through the Web (Continued) Setting and Viewing the Power Distribution Function Function Explanation Users can set, inquire, and edit the information of power distribution section. Refer to pg. 4 for more information on the Power Distribution Function. Using the power Distribution Function 1 If clicking the ‘Edit’ button from the , area is activated and users can set the desired section. Select one of possible settings which are 1 section, 2 sections, and 3 sections.
ENGLISH n 3 Section A and Section B are existed in 2 Sections. Can inquire and set the border time between Section A and Section B. When pressing the ‘Save’ button from the after editing the border time from the area , set time is adopted. If the border time between Section A and Section B is 08:00, Section A is 00:00~08:00 and Section B starts from 08:01. 4 3 Sections are classified into Section A, Section B, and Section C. The setting method is same as 2 sections’ setting method.
Using the DMS through the Web (Continued) Setting and Viewing the Power Distribution Environment Function Explanation Users can view or edit the connection between the indoor units and assigned watt-hour meter. DMS will distribute power based on the information which has been set up from this menu. 1 Check the address and the channel on the SIM transmitter that is connected to the watt-hour meter. SIM Transmitter with the address 0~7 will be displayed as 16~23 on DMS when tracking.
Check the indoor/outdoor units connected to the watt-hour meter. 3 Check the SIM transmitter channel (watt-hour meter). If the indoor unit power is supplied from the outdoor unit, set the ‘Outdoor SIM ch.’ only. (‘Outdoor SIM ch.’ signifies the watt-hour meter connected to the outdoor unit.) If the indoor unit power is supplied separately, set both ‘Outdoor SIM ch.’ and the ‘Indoor SIM ch.’. (‘Indoor SIM ch.’ signifies the watt-hour meter connected to the indoor unit.
Using the DMS through the Web (Continued) Note Indoor/Outdoor unit SIM channel setting - If there is SIM transmitter connected to the DMS, user can set up the SIM channel. - User will not have to inspect the watt-hour meter since power distribution will be done automatically. Indoor/Outdoor unit Virtual channel setting - When there is no SIM transmitter connected to the DMS, user can set up the Virtual channel.
Inquire Power Distribution Result ENGLISH Function Explanation Users can inquire operation breakdowns and power usage by indoor units that is saved in the DMS. Inquiring the result Total Indoor units (by period) 1 Select ‘Total Indoor units (by period)’ in to check the power consumption and the rate by period for all the indoor units. 2 Select whether to check the power consumption or the rate for all indoor units (by period) in .
Using the DMS through the Web (Continued) Individual Indoor unit (by period) 1 Select ‘Individual indoor units (by date)’ in to check the power consumption and the running rate by date for individual indoor unit. 2 Select the indoor unit to check in . (If the DMS is set to group mode and one group has more than two indoor units, each individual indoor unit will be checked.) 3 Select ‘watt-hour’ or ‘Running’ in .
ENGLISH Viewing Power Distribution Result 1 Click ‘SETUP FOR POWER DISTRIBUTION’ on the DMS web page. 2 When the Virtual channel for the Indoor/Outdoor unit is set, above screen will appear. 3 Select the time period and click ‘calculation’ to display the result. E-31 MIM-D00_IB_E_29777-2.
Using the DMS through the Web (Continued) 4 Check the result of power distribution. Click ‘Search’ to re-enter the power usage for each channel. Click ‘Save As File’ to save the result as excel file. Select ‘rate’ to check the result of power distribution in rate. If you use virtual channel, you cannot check the power usage for individual day. You may check the individual indoor unit’s daily operation time regardless of the channel type or settings.
Setting the Indoor Unit Restriction ENGLISH Function Explanation The DMS users can restrict the indoor unit as cool only or heat only. Setting the Indoor Unit Restriction 1 Click ‘RESTRICTED INDOOR UNIT USE’ on the DMS web page. 2 Click ‘Edit’ on the restricted indoor unit use screen. ‘Edit’ will change to ‘Save’. E-33 MIM-D00_IB_E_29777-2.
Using the DMS through the Web (Continued) 3 Click [] to select operation mode limit. Users can select ‘None’, ‘Cool only’ or ‘Heat only’. 4 Set the control mode. If you set the control mode, indoor unit operating in limited operation mode will be automatically set to operate in pre-set control mode. You can set the different control mode to each of the indoor units. - Cool only indoor unit : Users can select between fan and cool mode.
ENGLISH 5 Set lower limit temperature(Cool). You can set the lower limit temperature by selecting ‘Cancel’ or ‘Apply’. If the desired temperature is lower than lower limit temperature when the indoor unit is operating in cool mode, DMS controls the desired temperature in the lower limit temperature. You can set the lower limit temperature between 18°C(65°F) and 30°C(86°F). 6 Set upper limit temperature(Heat). You can set the upper limit temperature by selecting ‘Cancel’ or ‘Apply’.
Using the DMS through the Web (Continued) Note Mixed operation can occur even if you set control mode limit. If the indoor unit with control mode limit is in mixed operation, DMS will solve the problem automatically by controlling it in control mode limit. CAUTION All indoor units under the same outdoor unit should be on same control mode limit in the following situations. Mixed operation can occur continuously when you set some of indoor unit as cool only and the other as heat only.
Setting and Viewing the System Environment ENGLISH Function Explanation The DMS users can set and view information related to the DMS system installation and operation. (The installer must complete the system environment setup when installing the DMS.) System environment setup E-37 MIM-D00_IB_E_29777-2.
Using the DMS through the Web (Continued) 1 DMS Network Information Change the set information by inquiring the existing set network information from the DMS network information and clicking the ‘Edit’ button. If this information is changed, the DMS is restarted automatically. 2 System Time Change the system time by inquiring the current system time and clicking the Edit button. (The time is set when the DMS is installed and it is recommended not to be modified if possible.
Send error report email In order to send automatically to an e-mail when an error of the air conditioner is occurred, input an e-mail address, ID, password, and SMTP server information by clicking the ‘Edit’ button. When an input is completed, must check whether an e-mail is arrived to an inputted e-mail address by pressing the ‘Test’ button after pressing the ‘Apply’. (When the delivery: It is set to ‘Cancel.
Using the DMS through the Web (Continued) Setting the Operation mode of A/C Running LED 1 Click ‘SYSTEM ENVIRONMENT’ on the DMS web page. 2 Click ‘Edit’ on the Operation mode of A/C Running LED. ‘Edit’ will change to ‘Save’. 3 Select the mode you wish to set. DMS status: indicates whether or not DMS operates normally. Green light will flicker every 5 seconds when DMS operates normally.
Log ENGLISH Function Explanation You can view the history of all the settings. 1 Check the setting history from the Log window. DMS saves maximum 256 histories of each setting. If the number of history exceeds 256, DMS will delete the oldest history. Setting history will be saved in following categories: Tracking, Power distribution setting, Power distribution environment setting and Time setting.
Using the DMS through the Web (Continued) Tracking Function Details Tracking is the most initial stage that a DMS recognizes the DVM indoor/outdoor units. When performing a Tracking, some information may be lost; thus, use with care. User can order the Retry of a Tracking and manage the name of devices on the Tracking information screen. (Information may be lost if ‘Tracking’ is executed. Consult the installer if possible when executing ‘Tracking.
ENGLISH 2 When the Tracking Password Input window appears, enter the password. 3 When the Tracking Confirm window appears, press ‘Confirm’. Tracking will start. E-43 MIM-D00_IB_E_29777-2.
Using the DMS through the Web (Continued) 4 Notification with ‘Now tracking, please wait’ sign will appear. Tracking may take from few seconds up to 3 minutes. Tracking time may differ depending on the number for controllers. 5 When the tracking is done, press ‘Edit’. When the tracking fails, re-start the tracking. ‘Edit’ button will change to ‘Save’ button. Following window will appear when there are indoor units not using the centralized control.
ENGLISH 6 Enter the name of the centralized controller and the indoor units. 7 Press ‘Save’. Changed name of the centralized controller and the indoor unit will be saved on DMS. E-45 MIM-D00_IB_E_29777-2.
Using the DMS through the Web (Continued) Do not run Tracking except for the following conditions: Note After initial installation. - After initial installation, run Tracking for DMS to recognize the installation structure. - Make sure actual system air conditioner information matches the Tracking information displayed on DMS. - When the actual system air conditioner information does not match the Tracking information on DMS, check the installation.
ENGLISH User Management Adding New User 1 Click ‘USER MANAGEMENT’ on the DMS web page. 2 When User Management screen appears, enter user ID, Password and Description. ID should be 4~10 letters long, starting with a alphabet and can be used with numbers. 3 Click ‘Add’. There are no limits on number of users. Entered user information will be saved on DMS. Note MS manager should change the ID and the password D for security and maintenance. E-47 MIM-D00_IB_E_29777-2.
Using the DMS through the Web (Continued) Editing User 1 Click ‘USER MANAGEMENT’ on the DMS web page. 2 When User Management screen appears, select the user you wish to edit. You can select number of users at once or select individual user. 3 Edit the Password and the Description on selected ID. ID cannot be edited. 4 Click ‘Edit’. Edited user information will be saved on DMS. E-48 MIM-D00_IB_E_29777-2.
ENGLISH Deleting User 1 Click ‘USER MANAGEMENT’ on the DMS web page. 2 When User Management screen appears, select the user you wish to delete. You can select number of users at once or select individual user. 3 Click ‘Delete’. If confirmation window appears, click ‘OK’ to delete selected user. E-49 MIM-D00_IB_E_29777-2.
Software Software License used in this product This product uses softwares distributed under GPL and LGPL liscense. Therefore, you can receive the source code of GPL and LGPL used in this product by requesting the email address below. E-mail : oss.request@samsung.com GPL Software - Monta Vista Linux Kernel 2.4.20 - PeerSec Networks MatrixSSL Evaluation - busybox-1.00 - yaffs - vivi - console-tools-0.2.3 - commerr-dev-1.2.7 - e2fsprogs-1.27 - gcc-3.3.1 - samba-2.2.8 - pam-0.72 - procps-2.0.
ENGLISH Berkeley DB software is used in this product. The source code of Berkeley DB software can be received when request to the following email address or can be downloaded from the website. E-mail: oss.request@samsung.com Berkeley DB software : db-3.2.9 Refer to ‘APPENDIX’ for original text of licence. (1) GPL2.0 (2) LGPL2.1 (3) ApacheLicense1.1 (4) Enhydra Public License 1.
MIM-D00_IB_E_29777-2.