Technical data
30
X Ratings shown are net capacities.
X Capacities are based on following conditions;
- Equivalent refrigerant piping length : 5m / Level difference : 0m.
;
Note
2
Mini 4 way cassette
2-2. Capacity tables
3) RC052DHXEA + ACN052NDEHA
(1) Cooling
Indoor
Temperature(°C)
Outdoor Temperature (°C, DB)
-10 21 35 46
WB DB TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14 20
4.8 3.8 1.2 4.8 3.8 1.1 4.6 3.7 1.5 3.0 2.4 1.2
16 22
4.9 3.9 1.2 4.9 3.9 1.1 4.8 3.8 1.5 3.0 2.4 1.2
18 25
5.0 4.0 1.2 5.0 4.0 1.1 4.9 3.9 1.5 3.1 2.5 1.3
19 27
5.1 4.1 1.3 5.1 4.1 1.2 5.0 4.0 1.6 3.2 2.6 1.3
22 30
5.3 4.2 1.3 5.2 4.2 1.2 5.1 4.1 1.6 3.3 2.6 1.3
24 32
5.4 4.3 1.3 5.4 4.3 1.2 5.2 4.2 1.6 3.4 2.7 1.4
(2) Heating
Indoor
Temperature(°C)
Outdoor Temperature (°C, DB)
-15 -10 7 24
DB TC PI TC PI TC PI TC PI
16
4.3 1.8 4.6 2.0 5.6 1.6 6.8 1.7
18
4.2 1.8 4.5 1.9 5.6 1.5 6.8 1.7
20
4.2 1.8 4.5 1.9 5.5 1.5 6.7 1.7
21
4.2 1.8 4.5 1.9 5.4 1.5 6.6 1.7
22
4.1 1.8 4.4 1.9 5.4 1.5 6.6 1.7
24
4.1 1.7 4.4 1.9 5.3 1.5 6.5 1.6
Indoor
Temperature(°C)
Outdoor Temperature (°C, DB)
-15 -10 7 24
DB TC PI TC PI TC PI TC PI
16
4.8 2.4 6.1 2.9 7.1 2.2 8.6 2.9
18
4.7 2.4 6.1 2.8 7.1 2.2 8.5 2.8
20
4.7 2.4 6.0 2.8 7.0 2.2 8.4 2.8
21
4.6 2.4 5.9 2.8 6.9 2.2 8.3 2.8
22
4.6 2.4 5.9 2.7 6.9 2.1 8.2 2.7
24
4.5 2.3 5.8 2.7 6.8 2.1 8.2 2.7
(2) Heating
TC(Total Capacity, kW), SHC(Sensible Heat Capacity, kW), PI(Power Input, kW)
4) RC060DHXEA + ACN060NDEHA
Indoor
Temperature(°C)
Outdoor Temperature (°C, DB)
-10 21 35 46
WB DB TC SHC PI TC SHC PI TC SHC PI TC SHC PI
14 20
5.9 4.7 1.5 6.5 5.2 1.5 5.4 4.3 1.7 5.5 4.4 2.9
16 22
6.0 4.8 1.5 6.6 5.3 1.6 5.5 4.4 1.7 5.7 4.5 3.0
18 25
6.1 4.9 1.6 6.8 5.4 1.6 5.7 4.5 1.8 5.8 4.6 3.0
19 27
6.3 5.0 1.6 7.0 5.6 1.7 5.8 4.6 1.8 6.0 4.8 3.1
22 30
6.5 5.2 1.6 7.1 5.7 1.7 5.9 4.8 1.9 6.1 4.9 3.2
24 32
6.6 5.3 1.7 7.3 5.8 1.7 6.1 4.9 1.9 6.2 5.0 3.3
(1) Cooling
TC(Total Capacity, kW), SHC(Sensible Heat Capacity, kW), PI(Power Input, kW)
TC(Total Capacity, kW), PI(Power Input, kW)
TC(Total Capacity, kW), PI(Power Input, kW)